OVERPRESSURE LEAK DETECTOR DLR-P ..
DLR-
P ..
1. Subject
Overpressure leak detector for double walled pipes, double walled fittings or a combination of
the above with air used as the leak detection medium.
DLR-P .. The dots are used in place of the alarm pressure. The alarm pressure may also be
followed by letters to describe the design variant of the leak detector in more detail.
2. Field of application
2.1. Requirements for interstitial spaces
•Verified pressure resistance of the interstitial spaces (see section 3.1)
•Verification of suitability of the interstitial space (for Germany: Allgemeine bauaufsichtliche
Zulassung (General Building Authority Approval), approval in individual cases).
•Tightness of the interstitial space (see section 6.4.7)
•The number of interstitial spaces to be monitored depends on the overall volume of the
interstitial space. According to EN 13160, this must not exceed 10m3. In order to make it
possible to verify the tightness of the interstitial space, we recommend that a value of 4 m3is
not exceeded.
The length of pipe which is to be monitored (per pipe branch) should not exceed 2500 m,
and it should comply with the approval requirements of the pipe.
2.2. Pipes
Double walled pipes (overground and underground) made of metal or plastic, designs
manufactured in the plant or on-site.
For Germany: More far reaching requirements for double walled pipes may result from TRbF 50,
the DIBt approval principles or EN 13160.
2.3. Fittings
Double walled fittings (overground and underground) made of metal or plastic, designs
manufactured in the plant or on-site.
For Germany: with Allgemeine bauaufsichtliche Zulassung (General Building Authority
Approval), provided this is not part of the approval of the pipeline.
2.4. Products conveyed in the pipes / leak detection medium
•Liquids which are hazardous to waters with a flash point > 55°C
•Liquids which are hazardous to waters with a flash point < 55°C
ONLY for double walled pipes / fittings with walls which are permeation-proof on the side of
the material being conveyed.
On pipes / fittings which are permanently filled with liquid, it must be ensured that the
equipment carrying the product (delivery pumps, ...) is suitable for zone 0, as air is forced
into the product in the event of a leak.
22/01/2009 - 2 -