Sinclair SDV5-MOD Manuale utente

SDV5-MOD
COMMERCIAL AIR CONDITIONERS SDV5

CONTENTS
1 Overview
1.1 Maintenance by Customer
01
1.2 System Architecture
01
1.3 Installation Method
02
1.4 Preparation before installation
02
1.5 Function Codes for Commands
03
1.6 Error Responses
03
2 Using the Product
2.1 Configuring the PC IP Address
04
2.2 Configuring the Gateway
05
2.3 Restoring Factory Settings
06
2.4 Checking Air Conditioner Information
06
2.5 Examples
07
2.5.1 Modbus RTU Data Frame
07
2.5.2 Modbus TCP Data Frame
10
3 Mapping Tables of SDV5-MOD
3.1 Mapping Table Description — Discrete Inputs
12
3.1.1 IDU
12
3.1.2 ODU
13
3.2 Mapping Table Description — Input Registersles
14
3.2.1 IDU — HTHM
14
3.2.2 IDU — Non-HTHM
16
3.2.3 ODU
18
3.3 Mapping Table Description — Holding Registers
19

Once the installation work is completed, test to verify that the device is operating
normally, and hand over the manual to the customer for safekeeping.
Caution: Improper handling may lead to personal injury or material loss.
Warning: Improper handling may lead to death or serious injury.
!
!
Safety Precautions
The product, and its Operation and Installation Manual describes the following content, including
how to handle the product, prevent harm to others and prevent property losses, as well as how to
use the product correctly and safely. Read the following carefully and make sure you understand
the content (identifiers and marks), and observe the below precautions.
!
Caution
Read the safety precautions carefully prior to installation.
Make sure you observe the important safety precautions provided below.
Meanings of marks:
Get your distributor or a professional to install the product.
The installation personnel must be equipped with the
professional knowledge. When you install on your own, any
mistake you made during the operations may lead to a fire,
electric shock, or injury.
Icon
Warning
Name
Prohibited. Specific information about the prohibited item is described within the
icons or in the form of graphics or text next to where the symbol is located.
Mandatory. Specific information about the mandatory item is described within the
icons or in the form of graphics or text next to where the symbol is located.
Commissioned
installation
Do not use combustible paints to spray directly on the data
converter as this may cause a fire.
Do not handle the product with wet hands, and do not let water
seeps into the device, as this will cause electric shocks.
Using
Warning
Prohibited
Prohibited
!
Warning
Get your distributor or a professional to install the product.
Non-professionals may not install the equipment properly which may in turn lead to
electric shock or fire.
Do not install the product to where there is a danger of flammable gas leakages. Any
leakage within the vicinity of the device may cause a fire.
Caution
!
[Note] The "harm" means that the affected party does not need to be admitted to hospital or
require long-term treatment.This generally refers to wounds, scalds, or electric shocks.
Icons Material losses refer to property and material losses.

1 Overview
1.1 Maintenance by Customer
No. DescriptionName
1 Supplies power.GND 12V
2
Provides the Web service for debugging. Modbus settings
can be configured on the Web page.
Supports the Modbus TCP/IP protocol.
Supports Category 5 network cables.
LAN
3 Supports the Modbus RTU protocol.A1B1E
4 ReservedA2B2E
5 Connects to port X/Y/E of an ODU.XYE
SDV5-MOD supports the SDV5 and SDV5-3P models. *Note 1
SDV5-MOD supports a maximum of 8 refrigerant systems and 64 IDUs. The addresses of
IDUs and ODUs connected to SDV5-MOD cannot be duplicated. *Note 2 When a system
change occurs, SDV5-MOD needs to be restarted.
A third party can conduct integrated development through the Modbus RTU or Modbus TCP/IP
protocol.
*Note 1: For details about supported models, contact technical support engineers.
*Note 2: The addresses of IDUs connected to the same SDV5-MOD cannot be duplicated.
The addresses of ODUs must be unique.
1.2 System Architecture
01
X Y E
CTR1
X Y E
CTR2
X Y E
ODU

1.3 Installation Method
I. Structural Dimensions (Unit:mm)
Direction A
225
128
95
28
209
1.4
Preparation before installation
Check whether the following assemblies are complete
1
2
3
4
1
3
2
1
No. Name Qty. Remarks
SDV5-MOD
Installation Manual
For Mounting on the Wall
Plastic expansion pipe
Wall
6 mm bit drilling,
bit depth not less than 30 mm
Cross round head wood screw,
GB950-86 M4X20
II. Installation Diagram
02
Power Adapter
Accessory Bag
12V/2A

1.5 Function Codes for Commands
NO. Function Name Function
0x02 Read Discrete Inputs Reads data.
0x03 Read Holding Register Reads data.
0x04 Read Input Register Reads data.
0x06 Write Single Holding Register Writes data.
0x10 Write Holding Registers Writes data.
1.6 Error Responses
A third-party device serves as the master Modbus device while SDV5-MOD serves as the
slave device.
The master device sends a request and waits for a response from the slave device. When no error
occurs, the slave device responds normally. If a data check error occurs, the slave device does
not respond. When data sent by the master device have an error other than the data check error,
the slave device responds with an error.
Meaning
The slave device receives a function
code that cannot be executed.
The received data address is not supported by the
slave device.
Code
0x01
0x02
0x03
0x06
Name
Invalid function code
Invalid data address
Invalid data
The slave device is busy
The slave device is busy processing a time-consuming
programcommand and the master device needs to
send the messagewhen the slave device is idle.
The value queried in the data area is not supported
by the slave device.
03

2. Using the Product
2.1 Configuring the PC IP Address
The default IP address of the SDV5-MOD is 192.168.1.185. The PC used for accessing the
Web page of SDV5-MOD must be in the same network segment as SDV5-MOD.
Open the "Internet Protocol Version 4 (TCP/IPv4) Properties" dialogue box and set the IP address
and subnet mask, for example, set the IP address to 192.168.1.10 and the subnet mask to
255.255.255.0.
After configuration, click "OK".
Note: The above configuration is for reference purposes only. Please follow instructions of IT
personnel during actual projects.
04

2.2 Configuring the Gateway
In the address bar of the browser (*Note 3), enter "http://192.168.1.185:8586". The Web page of
the SDV5-MOD is displayed, as shown in the figure below.
*Note 3: Internet Explorer (IE) is the recommended browser.
The table below describes the parameters.
Parameter
Description
SN
Reserved
Version
Software version
IP
address
of
SDV5-MOD
IP address
If the Modbus TCP/IP protocol is adopted, the IP addresses of the
SDV5-MOD
gateways
in
the
same
network
segment
must
be
unique.
The default value is 255.255.255.0.
Mask
Enter the value according to actual project requirements.
Gateway
Local gateway IP address
Baud rate: The default value is 9600.
Port setting
Parity bit: There is no parity check by default.
Stop bit: The default value is 1 bit.
Modbus address
Modbus address
If
there
are
multiple
SDV5-MOD
gateways
on
the
same
bus,
their Modbus addresses cannot be duplicated.
After modifying parameters, click "Save" to save the settings.
After settings are modified, the SDV5-MOD automatically restarts.
05

2.3 Restoring Factory Settings
2.4 Checking Air Conditioner Information
Click the "DataView" tab on the Web page, and click "Discrete inputs" or "Holding registers" to
check information about air conditioners.
When "Discrete inputs" is selected, a page as shown in the figure below is displayed.
Press "SW1" three times consecutively within 5 seconds after SDV5-MOD is powered on, to
enable the device to enter the factory setting restoration mode. The RUN indicator blinks rapidly
at a frequency of 5 Hz. After factory settings are restored, the system automatically restarts, and
the RUN indicator blinks normally at a frequency of 1 Hz.
Click the address No. of an IDU or ODU. Operation information about the air conditioner is
displayed.
When "Holding registers" is selected, a page similar to the one shown in the figure below is
displayed.
06

In the figure above, the first column indicates addresses, the second column indicates register
names, the third column indicates original values, and the fourth column indicates parsed values.
2.5 Examples
2.5.1 Modbus RTU Data Frame
Request/Response:
Device Address Function Code Data Error Check and Correction
1 byte 1 byte N bytes 2 bytes
1) 0x02 Read Discrete Inputs
Example: Requesting the device to read discrete input addresses 0–15
Request packet: 01 02 00 00 00 0F 38 0E
Response packet: 01 02 02 05 05 7A EB
07
Indice
Altri manuali Sinclair Invertitore

Sinclair
Sinclair SDV6-DM Series Manuale operativo

Sinclair
Sinclair SDV4-140HB3P Manuale utente

Sinclair
Sinclair SDV6 Guida

Sinclair
Sinclair SDV5 Series Istruzioni operative

Sinclair
Sinclair SDV5-56FA Manuale utente

Sinclair
Sinclair SDV6 Manuale utente

Sinclair
Sinclair SDV6-C Series Manuale operativo

Sinclair
Sinclair SDV5 Series Guida

Sinclair
Sinclair SDV5 Series Istruzioni operative

Sinclair
Sinclair SDV6-CC Series Manuale operativo