Menu tree
attention: For some parts of the menu the access is denied.
Level A B C D Input / indication comments
1 Info Version
WT-1.9917ff Indication of the software version, no
input possible
2
Ser.No.
SN: XXXX Indication of the serial number, no input
possible
3 Params Flow1 dp dP1.min Input of dP-value for
0/4mA Does not appaer, if a velocity sensor is
chosen
4
dP1.max Input of dP-value for
20mA
5
dp2.min Input of dP-value for
0/4mA Attention: if no second dp- transmitter is
connected, the values for dp2.min +
dp2.max must be set to zero
6
dP2.max Input of dP-value for
20 mA
7
k-factor Input of value Specification of the k-factor
8
velocity Puls/V Input of value Does not appaer, if a dp-sensor is
chosen
9
Vmin
Input of value Zero point in m³/h
10
Vmax Input of value span in m³/h
11
Pipe-ID
Input of value Internal pipe diameter
12
Schleich
Input of value cutoff in %
13
%Wetstm Input of value
14
Temp1 T1.min
temperature according to
0/4mA Does not appear for Sat.st2 and for
RTD-Direct-input
15
T1.max
temperature according to
20mA
16
Temp2 T2.min
temperature according to
0/4mA Appears only, if "1" is chosen in the
Menu RETRN
17
T2.max
temperature according to
20mA
18
press1 p.min
Pressure according to
0/4 mA Only appears for Sat.st2, superheated
steam und water
19
p.max
Pressure according to
20 mA
20
Signal Damping Input of value
21
Timebas
Hours, minuts, seconds, choosing the timebase
22
UNIT m.form kg, t, lbs Choosing the unit for mass flow in line1
23
m.backw kg, t, lbs Choosing the unit for mass flow in line 2
24
*
åm.forw kg, t, kt Choosiing the unit for total mass in line 1
26
*
åm.back kg, t, kt Choosiing the unit for total mass in line 2
27
*
åV m³, l Choosing the unit for the totalized flow
28
t °C, K Unit for temperature
29
p bar, kPa, hPa, psi Unit for pressure
30
Q. kW, MW Unit for heat
31
Q kJ, MJ, kWh, MWh Unit for energy
32
NKS
0NKS, 1NKS Digits after the decimal point
33
Outputs Relay1 fnction V.act, m.vorw, m.back,
Q.forw, Q.backw, Q.total,
t.forw, t.backw, p
Function of Relay
34
Charakt Water, Supply, min, max Characteristic of Relay
35
value Input of value
36
Relay2 fnction V.act, m.vorw, m.back,
Q.forw, Q.backw, Q.total,
t.forw, t.backw, p
Function of Relay
37
Charakt Water, Supply, min, max Characteristic of Relay
38
value Input of value
39
Analog1 fnction V.act, m.forw, m.back,
Q.forw, Q.backw, Q.total,
t.forw, t.backw, p
Function of analog output
40
Charact 4-20, 0-20 Current characteristic
41
Lo-Val Input of value Value for 0/4 mA