6 - Table of parameters and Menus
Control SET Escale
Temperature Adjustment (SetPoint)
(limits depending on probe type) *
-
NTC: -50...+99°C
PTC: -50...+150°C
Calibrating probe 1 (Offset) 0.0 -20.0...+20.0°C
Time relay ON in case of faulty probe
(If C7=0 and C=80, the relay will always be OFF deenergised)
10 0...120 minutes
Probe 1 differential (Histeresis) 2.0 0.1...20.0K
Protection delay time
(value of the option selected in parameter C4)
00...120 minutes
Upper blocking of the set point
(cannot be set above this value)
99
-
NTC: C3...+99°C
PTC: C3...+150°C
Lower blocking of the set point
(cannot be set below this value)
-50 -50...C2
Type of delay for protection of the compressor:
0 = OFF/ON (since the last disconnection);
1 = ON (since the last start-up/reset);
2 = OFF-ON/ON-OFF (since the last shut-down /start-up)
00 / 1 / 2
Status of COOL relay with probe fault
0 = OFF; 1 = ON; 2 = Average based on last 24 hours prior
to probe fault; 3 = ON-OFF as prog. C7 and C8
00 / 1 / 2 / 3
Time relay OFF in case of fault of probe 1
(If C8=0 and C7=0, the relay will always be ON energised)
50...120 minutes
Maximum duration of fast freezing mode.
(0=off)
24 0...48 hours
Change set point (SP) in fast freezing mode, when it reaches
this point (SP + C10) returns to normal.
(SP+C10>C3) (0=OFF)
-50 0°C...C3-SP
Length of inactivity at digital input to activate ECO mode
(Only if P10 or P11=1 and P0=0) (0=OFF)
20...24 hours
Change set point (SP) in ECO mode
(SP+C12 <C2) (0=off)
20...C2-SP
Exit to Main menu
DEFROST Control (if P0=0 Direct, Cold) SET Escale
Defrost frequency (Time between two starts) *0...96 hours
Maximum defrost duration (0=defrost deactivated) *0...255 minutes
Type of message during defrost:
0 = Current temperature
1 = Temperature at start of defrost
2 = Display dEF message
20 / 1 / 2
Maximum duration of message
(time added at the end of the defrost)
5 0...255 minutes
Defrost end temperature (probe 2) (If P4 = 1) 8 -50...+99,9°C
Defrost on equipment start-up
0 = NO, First defrost as per d0
1 = YES, First defrost as per d6
0 0 / 1
Exit to Main menu
Defrost start delay on equipment start-up 0 0...255 minutes
Calculated time between defrost periods:
0 = Total actual time
1 = Sum of times the compressor is on
0 0 / 1
Drip time at end of defrost
(compressor and fans off) (if P4 = 1)
1 0...255 minutes
Within the program you will find five menus, where you can adjust each parameter to the needs of your installation. SET column shows factory-set default parameters. Those
marked with * are variable parameters depending on the application chosen in the wizard or the P3 parameter (see table "Default parameters by application"). If not indicated
otherwise, the temperature values are in ºC. (Equivalent velues in °F)
- Appliances which have not been connected or used following the instructions that accompany it.
We will not accept any responsibility for damage caused to the appliance by poor handling. The
guarantee does not include:
Reserved the right of modify without prior notice.
- Appliances with a damaged, effaced or altered series number.
- Appliances damaged by blows or liquid spills or gaseous emissions.
This appliance has a three-years guarantee limited to replacement of defective parts.Transport not
included.
- Appliances which have been altered without the prior consent of the manufacturer.
8 - Guarantee Conditions
Avda. La Llana, 93 - 08191 RUBÍ - (Barcelona) SPAIN
Shop: www.sonder.es - Técnica: www.sonder-regulacion.com
7495VØ ESP - MAY16
Sonder Regulación, S.A.
Working environment:....................................................... -10 a +50°C, humedad <90%
Panel cutout dimensions:............................................................................. 70 x 28 mm
Rating of control device: ...............built-in, automatic operation feature Type 1.B, for
use in clean environments, Class A software and continuous operation. Pollution
classification 2 s/ UNE-EN 60730-1. Double insulation between supply, secondary
circuit and relay output.
Measurement range NTC:.................................. -50.0°C to +99.9°C ( -58.0°F to +211°F)
Types of probe:................................................................................. NTC 10K / PTC 2000
Resolution:............................................................................................................. 0.1°C
PTC:................................... -50.0°C to +150°C (-58.0°F to +302°F)
Number of relay operations:........................................ EN60730-1: 100.000 operations
Maximum Voltage SELV circuits:......................................................................20V
Connections:.................................................. Screw terminals for cables up to 2.5 mm²
Power supply:............................................................. 230V~ +10, -15% 50/60Hz 3.5VA
Depth:................................................................................................................. 62 mm
Front panel dimensions:.......................................................................... 77.2 x 35.2 mm
Relay:........................................................................................................................ 16A
Class of protection - front panel:.............................................................................. IP65
Fixation: ........................................................................... Panel-mounted with anchors
Inputs (According to P4):.........................2 inputs NTC/PTC + digital input PTC
Ambient storage humidity:............................................... -30 to +70°C, Humidity <90%
7 - Technical specifications
ALARMS control SET Escale
Configuration of temperature alarms
0 = Relative to SP; 1 = Absolute 00 / 1
Maximum alarm probe 1 (must be greater than SP) 99.9 NTC: A2...99.9°C
PTC: A2...150.0°C
Show warning if defrost is terminated by time-out
0 = No, 1 = Yes
00 / 1
Minimum alarm probe 1 (must be less than SP) -50 -50...A1
External alarm / Severe external alarm delay when receiving
digital input signal (P10 or P11=2 or 3)
00...120 minutes
00...120 minutes
Temperature alarm delay after completion of a defrost 00...99 minutes
Temperature alarm delay after reaching the value of
A1 or A2
30 0...99 minutes
Desactivation delay of the external alarm/Severe external alarm
when the signal of the digital input disappears (P10 or P11=2 or 3)
00...120 minutes
Temperature Alarm Differential (A1 and A2) 1.0 0.1...20.0°C
Door open alarm delay (if P10 or P11=1) 20...120 minutes
General status SET Escale
Type of operation 0=Direct, Cold;1=Inverted, Heat *0 / 1
Delay of all functions on receiving electrical power 00...255 minutes
Access code (password) functions
0=Inactive; 1=Block access to parameters; 2=Keyboard lock
20 / 1 / 2
Selection of type of input
1 = 1 probe + 2 digital inputs, 2 = 2 probes +1 digital input
1 1 / 2
Temperature display mode
0 = Whole in ºC 1 = One decimal in ºC
2 = Whole in ºF 3 = One decimal in ºF
00 / 1 / 2 /3
Configuring digital input 1
0=Off 1=Door contact; 2=External alarm
3=Severe external alarm; 4=Slave defrost
5=Act. ECO mode by pushbutton; 6=Act. Fast Freezing
7= Not used; 8=Remote defrost; 9=Act. ECO mode by switch
Probe to be displayed (as per parameter P4) 0 = visualization
of all the probes in sequence; 1 = Probe 1; 2 = Probe 2
1 1 / 2
Selection of probe type 0 = NTC; 1 = PTC 0 0 / 1
Temperature alarm delay during start-up
00...9
Configuring digital input 2
0= Off; 1=Door contact; 2=External alarm;
3=Severe external alarm; 4=Slave defrost
5=Act. ECO mode by pushbutton; 6=Act. Fast Freezing
7= Not used; 8=Remote defrost; 9=Act. ECO mode by switch
00...9
Digital input polarity 1
0=Energised on closed contact; 1=Energised on open contact
Exit to Main menu
Access and information control SET Escale
Access code (Password) -0...99
Program version (Information)
Program revision (Information)
Reset parameters and settings, return to SET
Exit to Main menu
Selecting the type of configuration according to application *0...8
1
Multi
purpose
2
Frozen 3
Fruits and
vegetables
4
Fresh
fish
5
Soft Drinks 6
Bottle Racks 7
AC 8
Heat/
Incubators
Digital input polarity 2
0=Energised on closed contact; 1=Energised on open contact
Exit to Main menu
2 -18 10 0 3 12 21 37
4 4 4 4 24 24 96 -
20 20 20 20 20 20 0 -
8 0 30 8 8 30 99 -
1 0 1 1 1 1 1 -
0 0 0 0 0 0 0 1
00 / 1
00 / 1
0 (cancel)/ 1 (reset)