
To fit or release module
Insert screw driver into
slot and lever latch
away from body
MECHANICAL INSTALLATION
Enclosure
Style DIN Rail Mount
Material Blend PC/ABS self extinguishing
Terminals Screw terminal
Cable 2.5 mm Max
Colour Gray
Ø 3 mm
MOUNTING
Screw driver
EN60715 DIN RAIL
1
2
Ambient Range
+ 70 °C Max
- 20 °C Min
Ø 3mm
Screw Driver
Shielded Cable Twisted Pair Cable TC Compensation Cable
Screened
TURN OFF SUPPLY BEFORE
WORKING ON ANY ELECTRICAL
CONNECTION
INPUT CONNECTION
For cable length < 3 Meters no shielded
cable or twist pair required.
Thermocouple inputs must use correct
compensation cable.
Pt100 inputs all three wires must be equal
length (resistance).
Max input cable length 30 meters.
Temperature Process Current
Externally
Powered
Voltage TRIP 1(A)
TRIP 2(B)
Current
Internal
Powered
ANALOG OUTPUT CONNECTION
For cable length < 3 meters no shielded cable
or twisted pair required.
Use twisted pair or shielded cable for current
output < (30 to 1000) meters.
Voltage output use shielded cables (3 to 30)
meters, cable lenghts > 30 meters not advised.
TRIP OUTPUT
CONNECTION
Trip outputs are isolated
from each other.
Max switching current 1 A
@ 240 V ac, 1 A @ 30 V dc
SUPPLY CONNECTION
Supply input is not polarity
sensitive.
Max supply 240 V ac or
240 V dc
ELECTRICAL INSTALLATION
+
-T/C
4
2
PT100
5
2
3
Slide Wire
V
+
-
V /mV
4
mA
+
-
mA Sense
T
x
+
-
Transmitter
1
3
3
4
26
4
2
Load
7
8
V s
+
-
Load
8
9Vout
10
7
+
-
8
16
17
18
a
b
c
14
13
15
a
b
c11
12
a.c. d.c.
+
-
IMPORTANT- CE & SAFETYREQUIREMENTS
ThisproductissuitableforenviromentInstallationcategoryII pollutiondegree.
Theproductisclassedas"PERMANENTLYCONNECTEDEQUIPMENT".
ProductmustbeDINrailmounted,insideasuitableenclosureprovidingenvironmentalprotectiontoIP65orgreater.
DCsupplymustbederivedfromalocalsupplyandnotadistributionsystem.
Maxrelaycontactrating240VAC@1a(30VDC@1A).Anycircuitconnectedtoacontactmustbefusedwitha2A(T)fuse.
TomaintainCEEMCrequirements,inputandsupplywires mustbelessthan30meters.
Theproductcontainsnoserviceableparts,orinternaladjustments.noattemptmustbemadetorepairthisproduct.Faultyunitsmustbereturnedtosupplierforrepair.
Thisproductmustbeinstalledbyaqualifiedperson.Allelectricalwiringmustbecarriedoutinaccordancewiththeappropriateregulationsfortheplaceofinstallation.
Beforeattemptinganyelectricalconnectionwork,pleaseensureallsuppliesareswitchedoff.
ABSOLUTEMAXIMUM CONDITIONS:-
SupplyVoltage ±240Vdc ±240Vac(Protectedforovervoltage)
InputVoltage ±24V betweenanyterminals
InputCurrent ±50mAbetweenterminals
Output 30Vdc
Trips 240Vac@1A30Vdc@1A noninductive
Ambient Temperature (-4to158)°F Humidity(10to95)%RH(Noncondensing)
PRODUCT SPECIFICATION
Please refer to the product data sheet for full specification, available to down load at www.status.co.uk.
RECEIVE AND UNPACKING
Please inspect the packaging and instrument thoroughly for any signs of transit damage. If the instrument has been damaged, please notify your supplier
immediately.
CONFIGURATION
IMPORTANT During configuration the device takes its power from the USB port, therefore no power connection is required. The device can be configured while powered
but the computer used must be isolated from the mains supply earth to avoid ground loop effects.
Device
M-CONFIG or USB_LINK software
(usb_link V2.0 or greater)
USB CABLE
Disk or download @
www.statInst.com
COMPUTER
The following parameter can be configured by simply entering as prompted by the software package.
· Input type / input sensor / units(temperature inputs) / sample rate
· Scale input to process variable (process inputs only)
· Analog Output / Set Type voltage or current / scale output signal range / scale output to process
Set adjustable damping for both rising and falling output. Set correction for voltage output load.
· Trip Outputs / Set action / Set setpoints / Set deadband / Set adjustable delay on and delay off
· Set burnout direction on sensor failure or input overrange.
· Set the function of the front panel user buttons to off, trim or configure.
. TAG number
Factory default:
Input type = P
Sample rate = 1000 mS
Units = °C
Output = (4 to 20) mA damping 0
High Range = 100
Low Range = 0
Burnout = UPSCALE
User Trim = off
Trips = off, delays 0
Damping = 0
Status Instruments Inc, PO Box 548, 456 Park Avenue, Scotch Plains, NJ 07076
Web
Page:
www.statinst.com
Tel
:
(800)
700-3272
Fax:
(
800)
700-5468
email
:
[email protected]SEM1700 USER GUIDE
Temperature/Process Conditioner with
Universal input, outputs supply plus
manual config/trim.
Every effort has been taken to ensure the accuracy of this document, however we do not accept responsibility for damage, injury, loss or expense resulting from errors and omissions, and we reserve the right of amendment without notice.
Important - Please read this document before any installing.
INPUT
2
3
4
5
External Powered
(4-20) mA Output
SEM1700
8
9
1
7
Internal Powered
current Output
14
13
15
16
17
18
a
a
b
b
c
c
TRIP 1 (A)
TRIP 2 (B)
12 11 ANALOGUE OUTPUT
USB
6
Slide Wire
PT100
V
+
+
-
-
T/C
V /mV
4
4
2
Temperature
5
2
3
Process
mA
+
-
mA Sense
T
x
+
-
Transmitter
1
3
3
4
26
4
2
V s
+
-
Load
7
8
Load
8
9
TRIP OUTPUT
10
Vout
10
7
+
-
Voltage
OUTPUT
8
SUPPLY (20 to 240) V AC or DC
All Dimensions in mm