SYStronics UC-3300B Manuale utente

UC-3300B MANUAL
1
UC-3300B
USER MANUAL
Integrated Unit Cooler Controller
VER:201805-1.0SYStronics. Co. ltd.,
1404, 301, Bucheon Techno park, 345, Seokcheon-ro, Bucheon-si, Gyeonggi-do, Republic of Korea
Phone : +10-32-324-2777 Fax : +10-32-324-2717 Homepage : www.ss22.com

UC-3300B MANUAL
2
Be sure to read and ensure that your safety precautions are used to protect your safety and prevent property
damage. We shall not accept any liability for any loss caused by the use or carelessness caused by the use
or handling of this manual.
Warning
If this product is not intended as a safety device, use a double safety device for fear of accidents, damage of
critical peripheral equipment, and equipment that is feared to cause extensive property damage.
Safety instructions
1. Be sure to check the equipment after disconnecting mains.
2. Do not disassemble and repair this product ; it is not possible to manufacture any product.
3. Do not spray water directly or clean it with benzene, jazzy, or alcohol.
Notes on the environment
Do not install this product in the following locations and environments :
1. Places directly exposed to mechanical vibration or shock
2. Places exposed to corrosive gases or combustible gases
3. Position directly exposed directly to direct sunlight
4. Places affected by electromagnetic waves
5. Places where high temperature or humidity is high (sites with over 85 % of ambient humidity)
6. Places where dust and salt are plentiful
Precautions on installation
1. Make sure that the installation work is related to the installation or qualified personnel only.
2. Do not place any device or wiring that caused noise (NOISE) near the product.
3. Avoid near heating apparatus.
4. Disconnect all appliances (OFF) after disconnecting them from the wiring.
5. Do not work with wet hands. Risk of electric shock.
6. Install and use the method described in the User Manual as instructed in the Instructions for Use.
7. Do not turn on (power on) prior to the connection between the unit of manufacture of this unit.
8. Do not use any load exceeding the opening and closing capacity of the output contacts.
Immunity condition
1. In addition to the contents set forth herein, no warranties and responsibilities shall be made regarding this
product.
2. Whether or not this product is likely to be unforeseen defects and natural disasters due to the use of this
product, the user or the third person We shall not be held liable for any indirect damage.
Precautions

UC-3300B MANUAL
3
Product Overview
·Integrated Unit Cooler Controller
·Cooling / Automatic, Forced Defrost Function
·Pump Down / Cooling and Blowing Delay after Defrosting Function
·Power Failure Return / Cooling Delay Function
The combination of the FND display and LED lamp effectively indicates the operation and alert
status of the controller to enhance the visibility of the product. Since the display and I/O board are
built in an all-in-one format, it is easy to install and perform maintenance activities. This controller can
be applicable to units used for freezing, refrigerating. Configured as a button-based input system
and all-in-one body, it is easy to operate and perform control and monitoring of the equipment at a relatively
affordable price.

UC-3300B MANUAL
4
Product Component
Sensor Component
Normal Type
NTC Sensor
(1EA / SCTS-01)
Basic Type
Standard Sensor
Advanced Type
NTC Sensor
(1EA / SCTS-02)
Selectable
Option Sensor
Well Type
NTC Sensor
(1EA / SCTS-04)
Selectable
Option Sensor
(Choose one of the three sensor)
Unit Cooler Controller
(1EA / UC-3300B)
Guide
(1EA)
Guide Screw
(2EA / N3)

UC-3300B MANUAL
5
Product Specifications
Controller Specification
Input Power 100 ~ 220VAC, 50/60Hz
Output Voltage 100 ~ 220VAC, 50/60Hz (Main fuse 3A / 250V)
Output Contact Capacity 220VAC, 3A (Relay output)
Input Port 2 Port (Non-powered contact)
Output Port 5 Port (Input power Output)
Sensor Port 1 Port (NTC : 10K at 25℃ ±1%)
Operation Temperature -10 ~ 60℃ (Non condensing)
Operation Humidity 5 ~ 90% (Non condensing)
Storage Temperature -20 ~ 60℃ (Non condensing)
Control Temperature -45℃ ~ 45℃ (Firmware Specification)
Body Weight 420g
Guide Weight 63g
Sub Function Cooling, Automatic defrost, Forced defrost, Pump down, Cooling and
blowing delay after defrosting, Power failure return, Cooling delay
Normal Type Cable Sensor (SCTS-01 / Basic type standard sensor)
Temperature Range -45 ~ 80℃
Accuracy NTC : 10K at 25℃ ±1%
Sensor Weight 58g (Cable Basic 3M standard)
Advanced Type NTC Sensor (SCTS-02 / Selectable type option sensor)
Temperature Range -45 ~ 105℃
Accuracy NTC : 10K at 25℃ ±0.5℃
Sensor Weight 37.5g (Cable Basic 3M standard)
Well Type NTC Sensor (SCTS-04 / Selectable type option sensor)
Temperature Range -45 ~ 80℃
Accuracy NTC : 10K at 25℃ ±1%
Sensor Weight 84g (Cable Basic 3M standard)

UC-3300B MANUAL
6
Product Dimension
Top view
Front view
Guide Dimension (Unit : mm)
Controller Dimension (Unit : mm / Piercing size: W111.0 ×H126.0)
Side view
Top view
Front view Side view

UC-3300B MANUAL
7
Well Type NTC Sensor (SCTS-04 / Selectable type option sensor)
Temperature Range -45 ~ 80℃
Accuracy NTC : 10K at 25℃ ±1%
Sensor Weight 84g (Cable Basic 3M standard)
Advanced Type Cable Sensor (SCTS-02 / Selectable type option sensor)
Temperature Range -45 ~ 105℃
Accuracy NTC : 10K at 25℃ ±0.5℃
Sensor Weight 37.5g (Cable Basic 3M standard)
Normal Type Cable Sensor (SCTS-01 / Basic type standard sensor)
Temperature Range -45 ~ 80℃
Accuracy NTC : 10K at 25℃ ±1%
Sensor Weight 58g (Cable Basic 3M standard)
Sensor Dimension

UC-3300B MANUAL
8
Product Installation Method
1. After drilling a hole (W111.0 x H126.0 / mm) that meets the specifications of the panel or equipment, push
the controller in the direction and fix it.
2. Align the guide provided with the product to the groove on the back side of the controller and securely
tighten the controller with the guide fixing screws (2EA / N3).

UC-3300B MANUAL
9
51F
51CF
51C
AC220V
R
N
ALARM
SV
52CF
52F
52DEF
HPC
HPS 49INT
HTC
DEF
LPS
Input·Output Specification
Product Wiring Method
TEMP.
SENSOR
R
N
1
2
3
4
5
IN1
C1
IN2
C2
SEN (+)
SEN (-)
52C
Input Output
IN1 Integrated alarm
DO1
Integrated alarm
IN2 Forced defrost
DO2
Liquid electronic valve
DO3
Compressor
DO4
Air blower
DO5
Defrost
Product Input·Output Specification
Forced Defrost
If an input is entered during operation, the system
enters the defrost mode forcibly and returns to
normal operation after defrost operation for the set
defrost time.
(Ex : Used for defrost synchronization if there are
two or more units in the storage)

UC-3300B MANUAL
10
Operating Function
Name Image Main Screen Setting Screen
Power
Button Operation run (Press for 2 seconds) ·
Stop
Button Operation stop (Press for 2 seconds) Operation stop (Press for 2 seconds)
Reset
Button
Change all setting values to initial
value (Press for 5 seconds) Go to main menu (Short press)
Menu
Button
Go to general setting (Short press)
Go to detailed setting
(Press for 5 seconds)
Go to bottom menu (Short press)
Save
Button ·Save setting value
(Press for 2 seconds)
Up
Button
Go to hidden setting
(Press for 5 seconds)
Increase of setting value
and operation state ON
(Short press : Move slowly)
(Long Press : Move quickly)
Down
Button ·
Decrease of setting value
and operation state OFF
(Short press : Move slowly)
(Long Press : Move quickly)
Forced
Defrost
Button
Forced defrost operation start and
release (Press for 2 seconds) ·
Up Button
Save Button
Forced Defrost Button
Menu Button Down Button
Reset ButtonPower Button
Stop Button