Trolex TX6649 Manuale utente



TX6649 User Manual
TX6649-UM-EN-02 3
TX6649 Intrinsically Safe Power Supply (Ex eq)
Contents
1. Product Overview 4
1.1 Operating Features 5
1.2 Application 5
1.3 Product Options 5
1.4 Dimensions 6
1.5 Technical Information 7
2. Certification 9
2.1 Certification Parameters 10
2.1.1 Input and IS Output
Connectors 10
2.1.2 Other Connections 10
3. Installing 11
3.1 Safety Precautions 11
3.1.1 Handling 11
3.2 Tools and Test Equipment
Required 11
3.3 Siting Recommendations 12
3.3.1 Positioning Requirements 12
3.4 Connections 13
3.4.1 Group 1 Areas 13
4. Maintenance 14
4.1 Technical Maintenance 14
4.2 Troubleshooting 14
4.2.1 Warranty 14
4.2.2 Diagnostics 14
4.2.3 Connectivity 15
4.2.4 Support 15
5. Compliance with ATEX
Directives 16
Disclaimers 17
Trademarks 17
Document History 17
Contact Details 17
www.trolex.com

4 TX6649-UM-EN-02
1. Product Overview
The TX6649 Power Supply converts an ac supply voltage into a stabilised and
regulated Intrinsically Safe source of power to approved sensors and electronic
control devices.
www.trolex.com

TX6649 User Manual
TX6649-UM-EN-02 5
1.1 Operating Features
• Input voltage options: 110 V ac or 230 V ac
• Input supply is protected by two primary fuses
• Intrinsically Safe output voltage: 12 V dc
• Output circuit is resistively limited in accordance with certification standards for
Intrinsically Safe, ia, equipment
• Output circuit incorporates voltage regulation, current limiting and continuous
short circuit protection
• Robust stainless steel housing
• Integral 20 Ah back-up battery with automatic uninterrupted power transfer and
charge to full capacity
• Output relay contact to signal power failure
• Analogue output signal to indicate battery charge condition
1.2 Application
• Mining
• Tunnelling
1.3 Product Options
TX6649.105.101 110 V ac input
TX6649.106.101 230 V ac input
www.trolex.com

6 TX6649-UM-EN-02
1.4 Dimensions
www.trolex.com

TX6649 User Manual
TX6649-UM-EN-02 7
1.5 Technical Information
1Input voltage 110 V ac ± 10% or 230 V ac ± 10% - 50/60 Hz
2Output voltage 12 V dc
Output current 750 mA
Output ripple/noise 150 mV max
Line regulation <5% over the input voltage range
Load regulation <5% over 0 to 90% of load current
<10% between 90% and 100% of load current
Voltage limiting Over voltage detection with crowbar protection and
short circuit protection
Current limiting Automatic current limiting of the intrinsically safe
output also limits the current to less than the
rupturing capacity of the output protection fuse.
www.trolex.com

8 TX6649-UM-EN-02
3Max. operating
temperature
–20°C to +40°C
Storage
temperature
–20°C to +70°C
Humidity 0 to 95% RH, non-condensing
Vibration limits / low
frequency
0.25 mm peak, sinusoidal vibration in the range
10 Hz to 100 Hz in 3 perpendicular planes
Medium frequency 2g peak, sinusoidal vibration in the range 10 Hz to
600 Hz in 3 perpendicular planes
Mechanical shock 1000 shocks of 40g minimum in 3 perpendicular
planes
Housing material Stainless steel
4Back-up battery Sealed lead-acid. 20 Ah
Automatic charge control to full capacity
Automatic uninterrupted output power transfer
following input power failure
Power fail indication Relay contacts change state on power failure.
Contact rating: 0.25 A at 30 V dc max.
Charge condition Analogue output signal proportional to the charge
level of the battery
Choice of 0.4 V to 2.0 V or 4 to 20 mA signals
Battery life 6 years at 20°C
3 years at 30°C
1.5 years at 40°C
Net weight 35 kg
Important note Following initial commissioning or long periods of
storage the TX6649 requires a minimum of
24 hours charge time before the batteries will be at
full capacity.
www.trolex.com

TX6649 User Manual
TX6649-UM-EN-02 9
2. Certification
Ex certified for Group I applications:
Europe:
Ex Certificate Number: SIRA 02ATEX3419X
Ex eq [ia Ma] Mb I (when mains powered)
Ex ia I Ma (when battery powered)
Special Conditions for Safe Use:
All cables used for external connections shall be terminated by the
use of suitably certified Ex e cable glands. The use of conduit is not
permitted.
General Conditions for Safe Use:
Prior to installation, it is essential that the user refers to the above Ex
certificate to ensure that the termination and cable parameters are
fully complied with and are compatible with the application. Copies of
certificates are available from Trolex.
ATEX directive 94/9/EC
EMC directive 2004/108/EC
International (IECEx):
Ex Certificate number: IECEx SIR 10.0109X
Special Conditions for Safe Use:
All cables used for external connections shall be made by the use
of suitably certified Ex e cable glands. The use of conduit is not
permitted.
General Conditions for Safe Use:
Prior to installation, it is essential that the user refers to the above Ex
certificate to ensure that the termination and cable parameters are
fully complied with and are compatible with the application. Copies of
certificates are available from Trolex.
www.trolex.com

10 TX6649-UM-EN-02
South Africa (MASC):
Ex Certificate number: MASC M/11-315X
Russia: GOST-R version is available.
Please contact Trolex for more information
2.1 Certification Parameters
2.1.1 Input and IS Output Connections
TX6649.106.101 (230 V ac, 12 V dc, 750 mA)
TX6649.105.101 (110 V ac, 12 V dc, 750 mA)
Um 250 V ac
Uo 13.0 V
Io 1.76 A
Co 30.29 µF
Lo/Ro 36.17 µH/Ω
Po 12.73 W
2.1.2 Other Connections
Refer to appropriate certificate for Certification Parameters for analogue output
(charge condition), relay contact and switch terminals.
See section 5 Compliance with ATEX directives for more information applicable
to your location.
MASC
www.trolex.com
Altri manuali per TX6649
1
Indice
Altri manuali Trolex Alimentazione elettrica