Trox Technik RM-O-M Manuale utente

RM-O-M
Duct smoke detector
Installation and operating manual GB/en

A00000046508, 1, GB/en
Translation of the original
© 2021 TROX GmbH
TROX GmbH
Heinrich-Trox-Platz
47504 Neukirchen-Vluyn
Germany
Phone: +49 (0) 2845 202-0
Fax: +49 (0) 2845 202-265
E-mail: [email protected]
Internet: http://www.troxtechnik.com
09/2023
RM-O-M Duct smoke detector2

General information
About this manual
This operating and installation manual enables
operating or service personnel to correctly install
the TROX product described below and to use it
safely and efficiently.
This operating and installation manual is intended
for use by fitting and installation companies, in-
house technicians, technical staff, instructed per-
sons, and qualified electricians or air conditioning
technicians.
It is essential that these individuals read and fully
understand this manual before starting any work.
The basic prerequisite for safe working is to comply
with the safety notes and all instructions in this
manual.
The local regulations for health and safety at work
and general safety regulations also apply.
This manual must be given to the system owner
when handing over the system. The system owner
must include the manual with the system documen-
tation. The manual must be kept in a place that is
accessible at all times.
Illustrations in this manual are mainly for informa-
tion and may differ from the actual design.
Copyright
This document, including all illustrations, is pro-
tected by copyright and pertains only to the corre-
sponding product.
Any use without our consent may be an infringe-
ment of copyright, and the violator will be held liable
for any damage.
This applies in particular to:
Publishing content
Copying content
Translating content
Microcopying content
Saving content to electronic systems and
editing it
TROX Technical Support
To ensure that your request is processed as quickly
as possible, please keep the following information
ready:
Product name
TROX order number
Delivery date
Brief description of defect or issue
Online www.trox.de
Phone +49 2845 202-0
General information
RM-O-M Duct smoke detector 3

Limitation of liability
The information in this manual has been compiled
with reference to the applicable standards and
guidelines, the state of the art, and our expertise
and experience of many years.
The manufacturer does not accept any liability for
damages resulting from:
Non-compliance with this manual
Incorrect use
Operation or handling by untrained individuals
Unauthorised modifications
Technical changes
Use of non-approved replacement parts
The actual scope of delivery may differ from the
information in this manual for bespoke construc-
tions, additional order options or as a result of
recent technical changes.
The obligations agreed in the order, the general
terms and conditions, the manufacturer's terms of
delivery, and the legal regulations in effect at the
time the contract is signed shall apply.
We reserve the right to make technical changes.
Warranty claims
The provisions of the respective general delivery
terms apply to warranty claims. For purchase
orders placed with TROX GmbH, these are
the regulations in section "Vl. Warranty claims"
of the Delivery Terms of TROX GmbH, see
www.trox.de/en/.
Safety notes
Symbols are used in this manual to alert readers to
areas of potential hazard. Signal words express the
degree of the hazard.
Comply with all safety instructions and proceed
carefully to avoid accidents, injuries and damage to
property.
DANGER!
Imminently hazardous situation which, if not
avoided, will result in death or serious injury.
WARNING!
Potentially hazardous situation which, if not
avoided, may result in death or serious injury.
CAUTION!
Potentially hazardous situation which, if not
avoided, may result in minor or moderate injury.
NOTICE!
Potentially hazardous situation which, if not
avoided, may result in property damage.
ENVIRONMENT!
Environmental pollution hazard.
Tips and recommendations
Useful tips and recommendations as well as
information for efficient and fault-free operation.
General information
RM-O-M Duct smoke detector4

Safety notes as part of instructions
Safety notes may refer to individual instructions.
In this case, safety notes will be included in
the instructions and hence facilitate following the
instructions. The above listed signal words will be
used.
Example:
1. Loosen the screw.
2.
CAUTION!
Danger of finger entrapment when
closing the lid.
Be careful when closing the lid.
3. Tighten the screw.
Specific safety notes
The following symbols are used in safety notes to
alert you to specific hazards:
Warning signs Type of danger
Warning – danger
zone.
General information
RM-O-M Duct smoke detector 5

1 Safety.......................................................... 7
General safety notes.................................... 7
Correct use.................................................. 7
Qualified staff............................................... 8
Safety signs................................................. 8
2 Technical data............................................ 9
Dimensions.................................................. 9
Duct smoke detector.................................. 10
Sensor head............................................... 11
Type plate................................................... 11
3 Transport and storage............................. 12
4 Parts and function................................... 12
General functional description................... 12
RM-O-M with air guide profile.................... 13
RM-O-M with sensor head in air duct........ 13
Accessories................................................ 14
Operating status displays .......................... 15
5 Installation................................................ 19
General notes on installation..................... 19
Mounting on rectangular air duct............... 21
Mounting on round air duct........................ 23
6 Electrical connection............................... 24
Supply voltage and wiring to the actuator.. 25
Supply voltage 230 V AC,
Spring return actuator 230 V AC................ 25
Supply voltage 230 V AC,
Spring return actuator 24 V DC.................. 26
Supply voltage 24 V DC,
Spring return actuator 24 V DC.................. 26
Connect display module............................. 27
Integration into the central building man-
agement system (BMS)............................. 27
Expansion modules.................................... 28
7 Commissioning / Function test / Reset.. 30
Commissioning.......................................... 30
Airflow monitoring...................................... 30
Functional test............................................ 30
Reset.......................................................... 31
8 Maintenance............................................. 32
General information................................... 32
Repair work................................................ 33
Open / close inspection cover.................... 33
Check seal................................................. 33
Check/replace sensor head....................... 33
9 Accessories and spare parts.................. 38
10 Index.......................................................... 39
Table of contents
RM-O-M Duct smoke detector6

1 Safety
General safety notes
Electrical voltage
DANGER!
Danger of electric shock! Do not touch any live
components! Electrical equipment carries a dan-
gerous electrical voltage.
– Only skilled qualified electricians are allowed
to work on the electrical system.
– Switch off the power supply before working
on any electrical equipment.
Correct use
The smoke detector is used for smoke detec-
tion in ventilation and air-conditioning systems
(AHU).
Fire dampers or smoke protection dampers
can be triggered (closed) by the smoke
detector.
The duct smoke detector can also be used to
switch off the fan in a ventilation system.
The duct smoke detector can be used in
supply and extract air systems.
In public swimming pools, the use is only per-
mitted in pure supply air ducts (without circu-
lating air).
Use in extract air ducts for kitchens or labo-
ratories must be checked on a case-by-case
basis.
Operation is only permitted in accordance with
the installation instructions and the technical
data in these installation and operating instruc-
tions.
Modifying the duct smoke detector or using
replacement parts that have not been
approved by TROX is not permitted.
Only use TROX test gas for the function test.
Incorrect use
WARNING!
Danger due to incorrect use!
Misuse of the duct smoke detector can lead to
dangerous situations.
The duct smoke detector must not be used:
– in areas with potentially explosive atmos-
pheres (EX);
– outdoors without adequate protection
against the effects of weather;
– in areas with direct sunlight
– in atmospheres where chemical reactions,
whether planned or unplanned, may cause
damage to the duct smoke detector or lead
to corrosion
Safety
RM-O-M Duct smoke detector 7

Qualified staff
WARNING!
Danger of injury due to insufficiently qualified
individuals!
Incorrect use may cause considerable injury or
damage to property.
– Only specialist personnel must carry out
work.
Personnel:
Skilled qualified electrician
Trained personnel
Qualified electrician
The qualified electrician is a person who due to his
professional training, knowledge, and experience,
as well as knowledge of applicable standards and
regulations, is capable of executing work on elec-
trical equipment and is capable of autonomously
recognizing and avoiding possible hazards.
The qualified electrician is specially trained for the
work environment where he is active and is familiar
with the relevant standards and regulations.
Skilled qualified electrician
Skilled qualified electricians are individuals who
have sufficient professional or technical training,
knowledge and actual experience to enable them to
work on electrical systems, understand any poten-
tial hazards related to the work under consideration,
and recognise and avoid any risks involved.
Trained personnel
Trained personnel are individuals who have suffi-
cient professional or technical training, knowledge
and actual experience to enable them to carry out
their assigned duties, understand any potential haz-
ards related to the work under consideration, and
recognise and avoid any risks involved.
Safety signs
The following symbols and information signs can be
found on the product.
WARNING!
Danger due to illegible signage!
Over time, labels and signs can become dirty
or otherwise unrecognisable, so that hazards
cannot be recognised and necessary operating
instructions cannot be followed. There is then a
risk of injury.
– Ensure that all of the safety, warning and
operating information is clearly legible.
– Replace illegible signs or labels immediately.
Electrical voltage
Only qualified electricians are allowed to work in
areas marked as having electrical voltage.
Unauthorised persons must not open the marked
areas.
Safety
RM-O-M Duct smoke detector8

2 Technical data
Dimensions
Fig. 1: Dimensions and space required
1for variant with air guide profile: H ≥ Air guide
profile
2Space requirement for connection lines
3for variant with sensor head in duct, opening in
air duct ∅100...105 mm
4for variant with air guide profile, opening in air
duct ∅40...45 mm
Technical data
RM-O-M Duct smoke detector 9

Duct smoke detector
Nominal operating voltage DC 24 V ±10%
Nominal operating voltage AC 230 V AC ±15% 50-60 Hz
Operating voltage range DC 21.6 V DC ... 28.8 V DC ± 3%
Cut-off range DC < 22.3 V DC and > 28.0 V DC
Power consumption without accessories (nominal opera-
tion)
5 VA (at 230 V AC); 3.6 W (at 24 V DC)
Power consumption with display or expansion module
(nominal operation)
6 VA (at 230 V AC); 4.8 W (at 24 V DC)
Current consumption without accessories (nominal opera-
tion)
40 mA (at 230 V AC); 150 mA (at 24 V DC)
Current consumption with display or expansion module
(nominal operation)
50 mA (at 230 V AC); 200 mA (at 24 V DC)
Maximum connected load spring return actuator 10 VA (230 V AC/ 24 V DC)
Internal fuse 500 mA, slow-blow
Maximum connection diameter 2.5 mm²
Relay contact FD Alarm (motherboard) 230 V AC or 24 V DC; 8A
Relay contact Sys Fail (motherboard) 24 V DC; 1A
Relay contact Alarm BMS (EM-RELAY) 24 V DC; 1A
Relay contact Airflow (EM-RELAY) 24 V DC; 1A
Relay contact Pollution (EM-RELAY) 24 V DC; 1A
IP protection level IP42
Protection class 230V AC / 24 V DC II (protective insulation) / III (protective extra-low voltage)
Minimum length air guide profile 90 mm (600 mm in scope of delivery)
permissible airflow velocity 1.0…20 m/s
Alarm threshold for volume flow rate 0.8 m/s
Alarm threshold for increased contamination > 70%
Operating temperature -10…65 °C
Relative humidity 5 %…90 %, no condensation
Storage temperature -20…70 °C
Weight max. 1.1 kg (without air guide profile)
Technical data
RM-O-M Duct smoke detector10
Indice