Vaillant VRT 350 Manuale utente

For the competent person
Installation instructions
VRT 350
VRT 350
GB, IE
Installation instructions

Legal information
Document type: Installation instructions
Product: VRT 350
Target group: Authorised competent person
Language: EN
Document number_version: 0020131957_01
Created on: 24.05.2012
Publisher/manufacturer
Vaillant GmbH
Berghauser Str. 40 D-42859 Remscheid
Telefon +49 21 91 18‑0 Telefax +49 21 91 18‑28 10
[email protected] www.vaillant.de
© Vaillant GmbH 2012
These instructions, or extracts thereof, may only be printed with the written consent of Vaillant GmbH.
All designations of products in these instructions are brand names/trade marks of the companies in question.
We reserve the right to make technical changes.

Contents
0020131957_01 VRT 350 Installation instructions 3
Contents
1 Notes on the documentation .............................. 4
1.1 Symbols and signs used........................................ 4
1.2 Observing other applicable documents ................. 4
1.3 Document storage ................................................. 4
1.4 Applicability of the instructions .............................. 4
2 Safety .................................................................... 5
2.1 Required personnel qualifications ......................... 5
2.2 General safety information .................................... 5
2.3 CE label ................................................................. 6
2.4 Intended use .......................................................... 6
3 Overview of the equipment................................. 8
3.1 Identification plate.................................................. 8
3.2 Scope of delivery ................................................... 8
4 Installation............................................................ 8
4.1 Fitting the controller in the living room................... 8
5 Electrical installation........................................... 9
5.1 Connect the controller to the boiler with a "3-4-
5 Terminal" .......................................................... 10
5.2 Connect the controller to the boiler with a
"24V=RT terminal" ............................................... 11
6 Electrical installation......................................... 12
6.1 Connect the controller to the boiler with a "3-4-
5 Terminal" .......................................................... 12
6.2 Connect the controller to the boiler with a
"24V=RT terminal" ............................................... 13
7 Start-up ............................................................... 14
7.1 Overview of installation assistant set-up
options ................................................................. 15
8 Operating............................................................ 16
8.1 Installer level overview......................................... 17
9 Operating and display functions...................... 20
9.1 Service information.............................................. 20
9.2 System configuration, system.............................. 20
9.3 System configuration, heater............................... 21
9.4 System configuration, heating circuit................... 22
9.5 System configuration, hot water circuit................ 22
9.6 Changing the code for Installer level ................... 23
10 Rectifying faults................................................. 24
10.1 Error messages ................................................... 24
10.2 Faults ................................................................... 24
11 Decommissioning.............................................. 26
11.1 Replacing the controller....................................... 26
11.2 Recycling and disposal........................................ 26
12 Customer service............................................... 26

1 Notes on the documentation
4Installation instructions VRT 350 0020131957_01
1 Notes on the documentation
1.1 Symbols and signs used
Symbols
The following symbols may appear:
Warning symbol
Information symbol
Symbol for a required action.
Symbol for the result of an action.
1.2 Observing other applicable documents
▶During installation, you must observe all the installation
instructions for the assemblies and components of the
system.
These installation instructions are enclosed with the various
system parts and supplementary components.
▶Furthermore, observe all operating instructions enclosed
with components of the system.
1.3 Document storage
Document handover
▶Pass these instructions and all other applicable docu-
ments and, if necessary, any required tools to the system
operator.
Availability of documents
The system operator is responsible for storing the documents
so that they are available when required.
1.4 Applicability of the instructions
These instructions apply for the following only:
Article number
Great Britain 0020124475

Safety 2
0020131957_01 VRT 350 Installation instructions 5
2 Safety
2.1 Required personnel qualifications
This manual is intended for persons with the following quali-
fications.
2.1.1 Authorised competent person
The installation, assembly and removal, start-up, mainten-
ance, repair and decommissioning of Vaillant products and
accessories must only be carried out by authorised compet-
ent persons.
Note
Each competent person is qualified for specific
activities on the basis of their training. They must
only work on units if they have the required quali-
fication.
When working on the units, the competent persons must
observe all applicable directives, standards, laws and other
regulations.
2.2 General safety information
2.2.1 Installation by skilled tradesmen only
The unit must be installed by a qualified, skilled tradesman,
who is responsible for compliance with the applicable re-
quirements, regulations and directives.
▶Read through these installation instructions carefully.
▶Carry out the activities that are described in these install-
ation instructions.
▶During the installation, observe the following safety in-
structions and regulations.
2.2.2 Risk of death from live connections
When working in the electronics box of the boiler, there is
a risk of death from electric shock. Continuous voltage is
present on the mains connection terminals, even if the main
switch is turned off.
▶Switch the main switch off before working on the electron-
ics box of the boiler.
▶Disconnect the boiler from the power mains by discon-
necting the mains plug or by de-energising the boiler via
a partition with a contact opening of at least 3 mm (e. g.
fuses or power switches).
▶Check that the boiler is de-energised.
▶Secure the power supply against being switched on
again.
▶Open the electronics box only when the boiler is discon-
nected from the power supply.
2.2.3 Material damage due to unsuitable
installation room
If you are installing the controller in a moist environment, the
electronics may be damaged by moisture.
▶The controller should only be installed in dry rooms.

2 Safety
6Installation instructions VRT 350 0020131957_01
2.2.4 Danger due to error functions
▶Ensure that the heating system is in a technically perfect
condition.
▶Ensure that no safety or monitoring devices have been
removed, bridged or disabled.
▶Immediately rectify any faults and damage that may affect
safety.
▶Install the controller in a location where it is not covered
by furniture, curtains, or other objects.
▶If thermostatic control is activated, advise the operator
that, in the room where the controller is mounted, all the
radiator valves must be fully open.
▶Do not use the unit's free terminals as supports for other
wiring.
▶At lengths of over 10 m, 230 V supply cables must be laid
separately from sensor or bus lines.
2.3 CE label
CE labelling shows that, based on the type over-
view, the appliances comply with the basic requirements of
the following directives:
–Electromagnetic compatibility directive (Council Directive
2004/108/EC)
–Low voltage directive (Council Directive 2006/95/EC)
2.4 Intended use
State-of-the-art
The controller is a state-of-the-art unit manufactured in ac-
cordance with recognised safety regulations.
Even so, in the event of inappropriate or non-intended use,
damage to the appliance and other property may arise.
The controller controls a heating installation with a Vaillant
heater with eBUS interface in a way that is room-controlled
and time-dependent.
The controller can control the hot water generation of a con-
nected domestic hot water cylinder.
Operation is permissible with the following components and
accessories:
–Domestic hot water cylinder (conventional)
–VR 66 Control Centre
Improper use
Any other use, or use beyond that specified, shall be con-
sidered improper use. Any direct commercial or industrial use
is also deemed to be improper. The manufacturer/supplier is
not liable for any resulting damage. The user alone bears the
risk.
Improper use of any kind is prohibited.
Other applicable documents
Intended use includes the following:

Safety 2
0020131957_01 VRT 350 Installation instructions 7
–observance of accompanying operating, installation and
servicing instructions for the Vaillant product as well as
for other parts and components of the system
–compliance with all inspection and maintenance condi-
tions listed in the instructions.

3 Overview of the equipment
8Installation instructions VRT 350 0020131957_01
3 Overview of the equipment
3.1 Identification plate
The identification plate is located on the rear of the control-
ler's electronics module (PCB) and is no longer accessible
from the outside after it has been installed on a wall in the liv-
ing area.
The identification plate contains the following information:
Information on the identific-
ation plate
Meaning
Serial number For identification
VRT XXX Unit designation
V Operating voltage
mA Current consumption
CE label Unit complies with European
standards and directives
Waste container Proper disposal of the unit
3.2 Scope of delivery
Quant-
ity
Component
1 Controller
1 Fastening material (2 bolts and 2 wall plugs)
1 Operating instructions
Quant-
ity
Component
1 Installation instructions
4 Installation
4.1 Fitting the controller in the living room
1. Fit the controller on an interior wall of the main living
room in such a way that perfect recording of the room
temperature is ensured.
–Height: ≈1.5 m

Electrical installation 5
0020131957_01 VRT 350 Installation instructions 9
43
6
3
2
1
3
4
3
5
1 Controller
2 Wall-mounting base
3 Mounting holes
4 Openings for cable duct
5 Pin header with terminals
for the eBUS line
6 Slot for screwdriver
2. Mark the position on the wall. Take the eBUS line route
into account when doing so.
3. Drill two holes matching the positions of the mounting
holes (3).
–Diameter of mounting hole: 6 mm
4. Insert the eBUS line through one of the cable ducts (4).
5. Insert the wall plugs supplied.
6. Use the screws supplied to secure the wall-mounting
base.
7. Connect the eBUS line to the terminal block.
(→Page 10)
8. Carefully insert the controller in the wall mounting base.
Ensure that the pin header (5) on the wall-mounting
base fits into the controller connector provided.
9. Carefully press the controller into the wall-mounting
base until the locking tabs on the controller are heard
to latch into the sides of the wall-mounting base.
5 Electrical installation
When connecting the eBUS line, there is no need to pay at-
tention to the polarity. If the two connections are switched
around, communication is not affected.
If you want to use a VR 66, observe the installation instruc-
tions for the VR 66 Control Centre.

5 Electrical installation
10 Installation instructions VRT 350 0020131957_01
5.1 Connect the controller to the boiler with a
"3-4-5 Terminal"
1. Disconnect the power supply to the boiler.
2. Disconnect the boiler from the power mains by pulling
out the mains plug or de-energising the boiler using a
partition with a contact opening of at least 3 mm.
3. Secure the power supply to the boiler against being
switched on again.
4. Check that there is no voltage in the boiler.
1
2
1 Controller terminal block 2 Boiler terminal block
5. Check whether the bridge is installed between termin-
als 3 and 4 on the PCB of the electronics box and, if re-
quired, install the bridge between terminals 3 and 4.
6. Connect the eBUS line to the terminal block (1) in the
wall-mounting base of the controller.
Altri manuali per VRT 350
3
Questo manuale è adatto per i seguenti modelli
1
Indice
Altri manuali Vaillant Controllori

Vaillant
Vaillant sensoCOMFORT VRC 720 Manuale utente

Vaillant
Vaillant VAZ CPC Manuale utente

Vaillant
Vaillant sensoHOME VRT 380f Manuale utente

Vaillant
Vaillant VSMART Manuale utente

Vaillant
Vaillant VRT 350 Manuale utente

Vaillant
Vaillant sensoCOMFORT VRC 720f Manuale utente

Vaillant
Vaillant Regler VA 2-WC C Manuale utente

Vaillant
Vaillant auroMATIC VRS 560 Scheda tecnica

Vaillant
Vaillant multiMATIC VRC 700f/4 Manuale utente

Vaillant
Vaillant VRT 350f Manuale utente