Vallox Pureo Manuale utente

Vallox Pureo
Control
Quick guide
Model
Vallox Pureo Control panel
Document
D10799
Valid from
25.06.2021
Updated
20.10.2021
Control panel
MANUAL

2
Vallox Pureo
Control
CONTENTS
INTRODUCTION
INTRODUCTION
INTRODUCTION............................... . 2
Safety ...................................................... 3
Installation ............................................. . . . 3
Warranty.................................................... 3
Intended use ................................................ 3
Disposal of the air handling unit ............................... 4
Safety signs used in the instructions ........................... 4
Compatibility of the Vallox Pureo control panel ................. 4
Control panel buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Control panel symbols ....................................... 6
USING THE UNIT.............................. . .7
Ventilation speed limits....................................... 7
Fan speeds ................................................. 8
Speed control .......................................... . . . 8
Pressure control ........................................ . . . 8
Air volume control ...................................... . . . 9
Temperatures .............................................. 10
Settings ................................................... 10
Fan settings............................................ . . .10
Test run................................................ . . . 11
Alarms................................................. . . . 11
Adjustment charts ...................................... . . .13
Time settings .......................................... . . .13
Week clock ............................................ . . .13
Measurements ......................................... . . .14
Turning the unit o...................................... . . .15

3© Vallox Oy - All rights reserved
Vallox Pureo
Control
SAFETY
Safe and appropriate handling requires knowledge of the basic
safety regulations, and of the intended use of the ventilation
system. Read this manual before operating the ventilation unit.
Please keep the manual for later reference. If you lose the manual,
it can be downloaded from our website.
This user manual contains all the information necessary for safe
operation of the system. All persons who operate and maintain
the ventilation system must follow the instructions provided in this
manual. Furthermore, all local accident prevention regulations must
be observed.
Installation
Installation and setup should only be carried out by a qualified
specialist. Electrical installations and connections must be carried
out only by an electrician and in compliance with local regulations.
WARRANTY
The guarantee and liability exclude damage resulting from:
• Inappropriate use of the ventilation system or the control unit
• Incorrect or inappropriate installation, setup or use
• Neglect of instructions concerning transportation, installation,
use, or maintenance
• Structural or electronic modifications or changes made to the
software
INTENDED USE
All Vallox air handling units have been designed to provide
appropriate and continuous ventilation so as to present no threat to
the health of people and to maintain structures in good condition.
IMPORTANT
In order to ensure that the indoor air presents no harm to
health and remains optimal also for the structures of the
building, ventilation must be kept on without disruptions. It is
recommended that ventilation be left turned on during long
holidays also. This keeps the indoor air fresh and prevents
humidity from condensing in the ventilation ducts and
structures. It also reduces the risk of moisture damage.
WARNING
The unit is not intended
for use by children
under 8 or by persons
with reduced sensory,
physical or mental
capabilities, or whose
lack of knowledge
and experience do not
ensure safe operation
of the unit.
Such persons can
use the unit under
supervision, or
by following the
instructions of someone
who is responsible for
their safety.
Children must be
supervised and not be
allowed to play with the
device.
NOTE
For further information,
go to www.vallox.com
INTRODUCTION

4
Vallox Pureo
Control
DISPOSAL OF THE AIR HANDLING UNIT
Do not dispose of electronic devices with household waste. Follow
local laws and regulations on safe and ecological disposal of the
product.
SAFETY SIGNS USED IN THE INSTRUCTIONS
WARNING
Indicates a hazard that
can result in death or
serious injury if not
avoided.
IMPORTANT
Indicates a hazard that
can result in damage to
property or loss of data
if not avoided.
NOTE
Indicates essential
information about the
product.
INTRODUCTION
COMPATIBILITY OF THE VALLOX PUREO CONTROL PANEL
The control panel is compatible with the Vallox Pureo TX 500, 900, 1300, and 1800 air handling units.

5© Vallox Oy - All rights reserved
Vallox Pureo
Control
INTRODUCTION
BUTTON DESCRIPTION
CONTROL PANEL BUTTONS
NOTE
The Vallox Pureo
Control panel contains
the buttons described
in the adjacent table.
The control panel has a
touch screen.
On/o status button provides more information of the
unusual running status of the unit.
The Back button takes you backwards in the menu.
The Left arrow button takes you leftward in the menu.
The Right arrow button takes you rightward in the menu.
Press the OK button to confirm selection or to acknowledge
active alarms.
Press the Cancel button to cancel selection.
Press the Select button to select the desired option.
The Up arrow button takes you upward in the menu.
The Down arrow button takes you downwards in the menu.
The Menu button takes you from the main display to the
menu.

6
Vallox Pureo
Control
INTRODUCTION
Control panel symbols
The following icons are used in the Vallox Pureo Control panel.
SYMBOL DESCRIPTION
The used running status is slow
The used running status is fast
The week clock is in use
On/o status information of the unusual running status of the unit
Alarm class 1: An alarm that stops the unit has been activated
Alarm class 2: An alarm that does not stop the unit has been activated
Fan speeds
Temperatures
Settings
Alarms
Adjustment chart
Time settings
Week clock
Language
Unit information and measurements
Turn unit o

7© Vallox Oy - All rights reserved
Vallox Pureo
Control
USING THE UNIT
USING THE UNIT
VENTILATION SPEED SETTINGS
Ventilation speed is controlled by pressing the fan symbol on the
display. The available speed options are slow, fast, and week clock.
NOTE
The week clock is activated from the week clock menu; the
week clock icon is not shown on the main display at other times.
Slow Fast Week clock
If the running status of the unit deviates from the setting shown on the
control panel, the on/o status information icon will appear in the right
top corner of the control panel. The on/o status options are:
• Starting up
• Stopping
• Stopped
• Outdoor air eciency limit restricts the operating speed
• Supply air eciency limit restricts the operating speed
• Extra time switch controls the speed
• Night cooling controls the speed

8
Vallox Pureo
Control
USING THE UNIT
FAN SPEEDS
The fan speeds menu enables setting the control method to speed
control, pressure control, or air volume control and the running status
to either slow or fast, as required by the control method, or setting the
maximum boost speed.
NOTE
The fan settings menu shows and enables editing the settings
of the selected control method of the fan. The control method is
selected from the fan settings and boost menu.
Speed control

9© Vallox Oy - All rights reserved
Vallox Pureo
Control
USING THE UNIT
Pressure control
Air volume control
IMPORTANT
Pressure control
requires external duct
pressure sensors.

10
Vallox Pureo
Control
USING THE UNIT
TEMPERATURES
The Temperaturesmenu is used to set either supply air control or extract
air control as the temperature control method and to set the temperature.
SETTINGS
The settings menu is used to modify the fan, heating/cooling,
frost prevention, and eciency limit settings and to start a
test run.
Fan settings
The Fan settings menu is used to select speed control,
pressure control, or air volume control as the control method
and to specify the K factors of the fans and the boost
settings.
IMPORTANT
K factors must be set
based on the type of
the air handling unit.
K factors
K FACTORS
Vallox Pureo TX 500 60
Vallox Pureo TX 900 121
Vallox Pureo TX 1300 154
Vallox Pureo TX 1800 197
Indice
Altri manuali Vallox Pannello di controllo