PROBA 5 Doc.nr: 190356 Version: 1.0
Page 8
2 hArdwAre speCifiCAtions
Type :PROBA 5 Compact
VDH part number :907.000401
Power supply :12Vdc
Power consumption :less than 20 Watts
Safety precautions :Mount an external switch and fuse as close as possible to the PROBA 5 Compact in order to interrupt the voltage.
Housing dimensions :Approx 208x191X186mm (WxHxD)
Housing material :Aluminium
Housing finish :Anodised aluminum
Front panel :Anodised aluminum with imprint
Mounting method :DIN rail
Weight :
Operation
temperature
:0 / +40˚C
Storage temperature :-20 / +60˚C
Operation RH :10 / 90 %RH non condensing
Operation :•Ethernet LAN connection using a PC
(full access with VASP software)
•RS 485 connection using a remote control (limited access).
Input/Output signals :•4x Pt1000 Temperature sensors
(2 wire shielded with shield connected to earth-strip)
A.. Signal line
B.. Common 0V line
:•3x Analog inputs for 2 or 3-wire shielded sensors
(with shield to earth-strip)
Individual configurable
++12Vdc sensor supply output, Imax. per output 100mAdc
(Imax. total 400mA)
SInput signal selectable by webpage:
0 .. 1 Vdc Ri > 50 KOhm (Umax. = 5Vdc)
0 .. 10 Vdc Ri > 10 KOhm (Umax. = 24Vdc)
4 .. 20 mA Ri = 50 Ohm (Imax. = 40mA)
-0V common (for 2 and 3-wire sensors)
•8x Analog outputs
(2-wire shielded with shield to earth-strip)
Individual configurable
+Output signal selectable by webpage:
0 .. 1 Vdc (Imax. 10 mA)
0 .. 10 Vdc
4 .. 20 mA (Rload max. 450 Ohm)
-0V common
•8x Digital contact
(use shielded cable with shield to earth-strip)
Contact current (closed) 5 mAdc
Contact voltage (open) 5 Vdc