TECHNICAL DATA
The unit is designed for indoor application with the ambient temperature ranging from +1 °C up to +40 °C and relative humidity up to
60 % without condensation. In cold, damp rooms, there is a possibility of freezing or condensation inside and outside the casing.
In order to prevent condensation on the internal walls of the unit, it is necessary that the surface temperature of the casing is 2-3 °C above
the dew point temperature of the transported air.
The unit should be operated continuously, and in cases where ventilation is not necessary, reduce the air flow of the fans to a minimum
(20%). This will ensure a favorable indoor climate and reduce the amount of condensation inside the unit, which can damage electronic
components. Never use the unit for dehumidification, for example, of new buildings.
The unit is rated as a Class I electrical appliance.
Hazardous parts access and water ingress protection rating:
IP22 for the unit connected to the air ducts
IP44 for the unit motors
The unit design is constantly being improved, thus some models may be slightly different from those described in this manual.
Parameter VUE 100 P3 VUE 200 P3 VUE 300 P3 VUE 450 P3
Unit supply voltage, 50 Hz [V] 1~ 230
Maximum unit power [W] 76 141 193 354
Maximum unit current [A] 0.33 0.63 0.84 1.54
Maximum flow rate [m3/h] 160 280 340 500
RPM [min-1]2750 2840 2720 2870
Sound pressure level at 3 m distance [dBA] 47 49 52 57
Transported air temperature [°С] -15...+40
Casing material Painted steel
Insulation Foamed rubber, 5 and 10 mm
Extract filter G4
Supply filters G4 + F8 (PM2.5 93 %)
Connected air duct diameter [mm] 100 100 150 150
Heat recovery efficiency [%] 75-7 72-87 66-87 71-87
Humidity recovery efficiency [%] 32-47 27-47 22-47 23-40
Heat exchanger type Cross-flow enthalpy
Weight [kg] 17 24 27 39
SEC class D D E E