Vents RS TA Series Manuale utente

SPEED CONTROLLER
User’s manual RS-...-TA
EN

2
EN
PURPOSE
The device is intended for use in ventilation systems for switching on/off and controlling rotation speed of single-phase
electric motors in power-controlled fans.
It is possible to control several fans if the total current consumption does not exceed the maximum allowable value of the
controller current.
DELIVERY SET
Speed controller 1 pc.
User’s manual 1 pc.
Packaging 1 pc.
Purpose..................................................................................................................................................................................................................................................... 2
Delivery set............................................................................................................................................................................................................................................. 2
Technical data....................................................................................................................................................................................................................................... 3
Design and operating principle ................................................................................................................................................................................................ 8
Mounting and set-up....................................................................................................................................................................................................................... 8
Troubleshooting.................................................................................................................................................................................................................................. 18
Storage and transportation regulations............................................................................................................................................................................... 19
CONTENTS

3
EN
TECHNICAL DATA
Main technical parameters RS-3/0-TA RS-6/0-TA RS-10/0-TA
Supply voltage [V/50 (60) Hz] ~220240
Minimum current [A] 0,3 0,5 1
Maximum current [A] 3 6 10
Fuse rating [A] F 5,0 A
H 250 VAC
F 10,0 A
H 250 VAC
F 16,0 A
H 250 VAC
Maximum ambient temperature [°С] -20 ... 40 °C at < 95% relative humidity
(without condensation)
Casing material Plastic R-ABS
Ingress Protection Rating IP54
Weight [kg] 0,84 1,0 1,08
Technical data
Analog input:
• voltage: 0-10 VDC / 10-0 VDC;
• current: 0-20 mA / 20-0 mA.
Analog input modes: acceleration or deceleration.
Analog input functionality:
Normal mode / Logic mode.
Remote control input:
Timer or Normal mode.
Adjustable output: 30–100 % Us.
Max. output load: depends on the version.
Unregulated output, L1: 230 VAC (50 / 60 Hz) / max. 2 A.
Min. output voltage, Umin: 30-70% Us (69-161 VAC),
selectable via trimmer or via Modbus.
Max. output voltage, Umax: 75-100 % Us (175-230 VAC),
selectable via trimmer or via Modbus.
The shutdown level is regulated by the trimmer:
• 0–4 VDC / 0–8 mA for the acceleration mode;
• 10-6 VDC / 20-12 mA for the deceleration mode.
Fast Start or Normal Start mode.
Low voltage output: +12 VDC / 1 mA for external
potentiometer.
Modbus RTU
Indication of operation:
• continuous green: normal operating mode;
• flashing green: in standby mode.
Excess voltage and overload protection.

4
EN
OPERATION DIAGRAM
Normal / remote operation modes
Acceleration mode Deceleration mode
Fast start of switching on
Uout, [%]
10 VDC
20 mA
Umax
Umin
0
Ai,
[VDC] /
[mA]
100
75
70
30
Umax
range
Umax
range
Uout, [%]
10 VDC
20 mA
Umax
Umin
0
100
75
70
30
Umax
range
Umax
range
Ai,
[VDC] /
[mA]
Calculation
formula for
acceleration
mode
Uout=Umin+ (Umax-min)
Ai
Aimax
Calculation
formula for
deceleration
mode
Uout=Umax- (Umax-min)
Ai
Aimax
Umax
Umin
0
Ai,
[VDC] /
[mA]
4 VDC
8 mA
U, [%] out
100
75
70
30
10 VDC
20 mA
Umax
range
Umax
range
Shutdown
level
Shutdown level
Umax
Umin
0
Ai,
[VDC] /
[mA]
10 VDC
20 mA
6 VDC
12 mA
U, [%] out
100
75
70
30
Umax
range
Umax
range
Shutdown level
The range of the
shutdown level
Smooth start of power on
Calculation
formula for
acceleration
mode
Ai-Off level
Aimax-Off level
Uout=Umin+ (Umax-min)
Calculation
formula for
deceleration
mode
Ai-Off level
Aimax-Off level
Uout=Umax- (Umax-min)

5
EN
Normal / remote operation modes
Acceleration mode Deceleration mode
Smooth start and activated
shutdown level
t, [s]
Umax
Umin
0
Uout, [%]
100
75
70
30
Umax
range
Umin
range
Duration of fast start t, [s]
Umax
Umin
0
Uout, [%]
100
75
70
30
Umax
range
Umin
range
Duration of fast start
t [s]
Umax
Umin
0
Uout, [%]
100
75
70
30
Umax
range
Umin
range
Duration of smooth start
Shutdown level
t [s]
Umax
Umin
Uout, [%]
100
75
70
30
10 VDC /
20 mA
Umax
range
Umin
range
Duration of smooth start
Shutdown level
Fast mode and activated
shutdown level

6
EN
Normal / remote operation modes
Acceleration mode Deceleration mode
Smooth start and activated level o
t [s]
Umax
Umin
0
100
75
70
30
Umax
range
Duration of smooth start
Shutdown level
Umin
range
t [s]
Umax
Umin
100
75
70
30
10 VDC /
20 mA
U
max
range
Umin
range
Duration of smooth start
Shutdown level
t, [s]
Umax
Umin
0
Uout, [%]
100
75
70
30
Duration of fast start
Umin
range
Umax
range
Ai,10 VDC / 20 mA
t, [s]
Umax
Umin
0
Uout, [%]
100
75
70
30
Umax
range
Umin
range
Duration of fast start
Fast mode and activated level o

7
EN
Timer mode Logic mode
Ai,10 VDC / 20 mA
t, [s]
Umax
Umin
0
Uout, [%]
100
75
70
30
U
max
range
U
min
range
Duration of fast start
Switch signal
0
t [s]
5 VDC
2,5 VDC
Remote
switch
VDC
Standby mode Operation
Voltage
amplitude
range
Fast start is enabled
Smooth start is enabled
t
t
t
t
SW
ONON
Holding
register
18
Holding
register
21
Duration
of soft start
Duration
of soft start
Start
Оutput
Umax
Timer
Soft start
Stop
StartStop
Timer
mode
Work time
Holding
register
18
OFF OFF
Switch signal
t
t
t
t
Ai >2,4 VDC
ON ON
Holding
register
18
Holding
register
21
Holding
register
21
Duration
of soft start
Duration
of soft start
Start
Оutput
Umax
Timer
Soft start
Start
Stop
Timer
mode
Timer
mode
Holding
register
18
OFF OFF
Ai control signal

8
EN
MOUNTING AND SET-UP
The controller is intended for indoor installation.
When installing the controller ensure unobstructed recirculation of air for cooling its internal elements.
Do not install the controller above heating equipment or in areas with insufficient air convection.
ATTENTION! After transporting or storing the product at sub-zero temperatures the controller must be kept
under the specied operating conditions for at least 4 hours prior to turning it on.
Inspect the product visually to confirm absence of any damage to the controller casing.
An automatic switch built into the stationary power supply network must be installed on the external input.
Note: To disable the ON / OFF function (3.0 A version only!) connect 230 VAC supply voltage to the unregulated output (L1).
In this case, do not connect the power supply unit to L.
DESIGN AND OPERATING PRINCIPLE
Controller casing is made of non-flammable thermoplastic.
The controller is equipped with an on/off button with backlight and an operation status indicator.
Output power change from 30 to 100% is made proportionally to the control signal 0...10 V or 4-20 mA in the selected range
during configuring the controller.
The control signal type 0...10 V or 4-20 mA is selected by a switch in the controller casing.
Controlling is possible with the use of a remote control panel, e.g. the R-1/010 controller.
The minimum rotation speed value is set by a variable resistor on the control circuit board inside the controller.
The controller has an additional terminal (230 V) for connecting and controlling external equipment (for example, air damper
drives).
The input circuit of the controller is protected from voltage and current overload by a fuse.

9
EN
INSTALLATION INSTRUCTIONS
Find a flat surface for mounting (wall, panel, etc.).
Follow these steps:
1. Turn off the power.
2. Remove the front cover by removing the self-tapping screws and secure the controller to the wall or panel using screws
through holes located in the back wall of the device. Observe the correct mounting position and dimensions of the device.
(See Fig. 1: Mounting dimensions and Fig. 2: Mounting position.)
Fig. 1. Dimensions [mm] Fig. 2. Mounting position
140
102
4x
Ø
4,50
92
124
205

10
EN
3. Connect the motor / fan. The connection is made using screw terminals on the controller circuit board.
4. Connect L1 output for three-wire connection, adjustable valve, etc. (if necessary). See Fig. 3.
Figure 3. Electrical circuit diagram
Power supply
230 VAC, 50-60 Hz
Unregulated
output
230 VAC/ max 2 A
Remote
controller
Modbus
RTU
Analog output
0-10 VDC / 0-20 mA
Output power
supply
+ 12 VDC / 1mA
V
WIRING AND CONNECTING
L Supply voltage [230 VAC/50(60) Hz]
N Neutral
PE Ground terminal
L1 Unregulated output (230 V/max. 2 A)
U1, U2 Adjustable output for motor connection
SW Remote switch/timer switch
A Modbus RTU (RS485), signal A
/B Modbus RTU (RS485), /B signal
+V Power supply output +12 VDC/1 mA
Ai Analog input 0-10 V/0-20 mA (10-0 V/20-0 mA) / input in Logic mode (timer function)
GND Grounding