Verdant VX Series Manuale utente

V
VX Series Thermostat
with an Occupancy Sensor
INSTALLATION MANUAL
V.5 MAY 31, 2016


3
Table of Contents
Introduction .................................................................................................5
Before You Begin ..........................................................................................8
Programming a Thermostat with a Network Programmer .........................9
Thermostat Installation ............................................................................. 10
Thermostat Configuration .......................................................................... 11
Setting the thermostat clock ...................................................................... 12
Entering the room number ......................................................................... 13
Configuring the Equipment Settings - Compressor Type ...........................14
Configuring the Equipment Settings - Electric Heat ..................................15
Configuring the Equipment Settings - Reversing Valve .............................16
Configuring the Energy Saving Settings .................................................... 17
Testing the thermostat ...............................................................................18
Accessing the Thermostat Settings ............................................................19
Custom Energy Savings Settings ................................................................19
Using the Thermostat Settings Screens .................................................... 20
01 – FAN CONTROL MODE .......................................................................... 21
02 – 1ST STAGE DIFFERENTIAL - HEAT ..........................................................22
03 – 2ND STAGE DIFFERENTIAL - HEAT .........................................................23
04 – 1ST STAGE DIFFERENTIAL - COOL ....................................................... 24
05 – INCIDENTAL OCCUPANCY THRESHOLD ............................................. 25
06 – NIGHT OCCUPANCY THRESHOLD ...................................................... 26
07 – FORCED 2ND STAGE HEATING .............................................................27
08 – NIGHT OCCUPANCY START ................................................................ 28
09 – NIGHT OCCUPANCY END ................................................................... 29
10 – TEMPERATURE RECOVERY TIME ........................................................ 30
11 – RECOVERY TEMPERATURE - HEAT ........................................................31
12 – TEMPERATURE SETBACK DELAY - HEAT ...............................................32
13 – MINIMUM SETBACK TEMPERATURE .................................................. 33
14 – TEMPERATURE SETBACK DELAY - COOL ............................................. 34
15 – MAXIMUM SETBACK TEMPERATURE .................................................. 35
16 – RECOVERY TEMPERATURE - COOL ..................................................... 36
17 – MINIMUM SET POINT ...........................................................................37

4
Table of Contents
18 – MAXIMUM SET POINT ......................................................................... 38
19 – TEMPERATURE CONTROL MODE ........................................................ 39
20 – AUTO CHANGEOVER SET POINT OFFSET ...........................................40
21 – SETBACK SET POINTS / AUTO-RESTORE ..............................................41
22 – AUTOMATIC HUMIDITY CONTROL† ..............................................................................................42
22 – TEMPERATURE CALIBRATION ............................................................. 43
Relay Options .............................................................................................44
ACCESSING RELAY OPTIONS ...................................................................... 44
1 – REVERSE RELAY OPERATION ................................................................ 45
2 – COOLING ONLY “SPDT” VALVE CONTROL ............................................. 46
3 – HEAT PUMP RELAY MODE .....................................................................47
Troubleshooting .........................................................................................48
Error Codes ................................................................................................. 48
APPENDIX 1 - Energy Saving Presets ..........................................................49
APPENDIX 2 - Glossary ................................................................................50
Warranty Information .................................................................................51
Technical Specifications ............................................................................. 52

5
Introduction
Verdant VX Series Energy Management Thermostats for the hospitality
industry deliver unprecedented energy savings without compromising
guest comfort.
Integrated occupancy sensor uses a combination of motion and thermal
sensing technologies for accurate occupancy detection. Reliable
occupancy detection allows saving energy when rooms are unoccupied.
Energy saving presets eliminate the guesswork and make it easy to
adjust the energy saving settings. (Patent Pending)
Fully configurable energy saving settings allow customizing the
thermostat energy saving settings to fit any situation.
Comprehensive configuration options ensure full compatibility with
virtually any existing or emerging hospitality HVAC system with up to 2
heat and 1 cool stages.
Built-in wireless mesh-networking enables optional remote management.

6

7
NOTICE
FOR INSTALLATION OF NETWORKING THERMOSTATS WITH
REMOTE MANAGEMENT, REFER TO THE “VX-TR NETWORK
INSTALLATION” MANUAL.
LOGIN TO THE REMOTE MANAGEMENT WEBSITE TO CONFIRM
THE SERVER IS CONNECTED TO THE INTERNET BEFORE
INSTALLING THERMOSTATS.
DO NOT INSTALL THERMOSTATS IF THE SERVER IS NOT
CONNECTED TO THE INTERNET. STOP THE INSTALLATION AND
CONTACT VERDANT TECHNICAL SUPPORT.
START BY FIRST INSTALLING A THERMOSTAT IN THE ROOM
CLOSEST TO THE SERVER.
LOG IN TO VERDANT’S REMOTE MANAGEMENT WEBSITE
TO CONFIRM THAT THE THERMOSTAT IS ON THE REMOTE
MANAGEMENT WEBSITE WITH THE CORRECT ROOM NUMBER.
CONTINUE BY INSTALLING ADDITIONAL THERMOSTATS IN
ADJACENT ROOMS ONLY AFTER CONFIRMING THAT INSTALLED
THERMOSTAT(S) HAVE CONNECTED TO THE WIRELESS NETWORK
AND THE REMOTE MANAGEMENT WEBSITE .
IF INSTALLED THERMOSTAT(S) ARE NOT CONNECTING TO THE
NETWORK AND DO NOT APPEAR ON THE VERDANT’S REMOTE
MANAGEMENT WEBSITE WITH THE CORRECT ROOM NUMBER,
STOP THE INSTALLATION AND CONTACT VERDANT TECHNICAL
SUPPORT
THE ROOMS FURTHEST AWAY FROM THE SERVER SHOULD BE
INSTALLED LAST.

8
Before You Begin
➤Determine the appropriate installation location for the thermostat.
➤Set the HVAC unit to “External Thermostat” (Class 2) mode. Consult
the HVAC unit documentation to determine how to set the HVAC
unit to “External Thermostat” mode.
THERMOSTAT SHOULD FACE THE BED AREA OF THE ROOM.
THERMOSTAT MUST NOT BE INSTALLED NEAR OR ON METAL
STRUCTURES OR SURFACES INCLUDING METAL AIR DUCTING
THAT MAY BE IN THE WALL.
METAL STRUCTURES AND SURFACES SIGNIFICANTLY REDUCE
THE RANGE OF THE WIRELESS SIGNAL.

9
Programming a Thermostat with a Network Programmer
In case of Network Installation with Remote Management, the
thermostat must be programmed with a Network Programmer
specific to the property before the installation.
Thermostat must not be powered during the programming procedure..
➤Plug one programmer connector into the thermostat;
➤Push the black button on the programmer. The red light on the
programmer should turn on and remain steadily lit;
If the red light on the programmer is blinking or is not steadily lit,
unplug the programmer from the thermostat and repeat the steps
above.
➤Unplug the programmer from the thermostat;
Before You Begin

10
Thermostat Installation
Mounting the thermostat to the wall
➤Power of the HVAC unit;
➤Remove the thermostat cover;
➤Connect the thermostat wires to the supplied Wiring Harness - refer
to the Wiring Table to determine proper connections;
➤Plug in the Wiring Harness into to the thermostat;
➤Use the supplied wall anchors and mounting screws to secure the
thermostat to the wall;
➤Follow the “Thermostat Configuration” instructions;
➤Replace the thermostat cover and screw in the locking screw;
➤Power on the HVAC unit.
NOTE: If the PTAC unit has only one (1) fan speed, connect both fan
control wires – Green and Purple – to the fan terminal (G).
Wiring Table - 24V AC
Wire
Color Terminal
Letter Terminal
Connection
Black C Common
Red R 24V
Yellow Y Compressor
White W Heat
Orange O or B Reverse Valve
Green GH Fan High
Purple GL Fan Low
Wiring Table - 24V DC
Wire
Color Terminal
Letter Terminal
Connection
Black R 24V
Red C Common
Yellow Y Compressor
White W Heat
Orange O or B Reverse Valve
Green GH Fan High
Purple GL Fan Low
Altri manuali per VX Series
3
Indice
Altri manuali Verdant Termostato

Verdant
Verdant Wireless Manuale utente

Verdant
Verdant VX-TR Istruzioni di installazione e manutenzione

Verdant
Verdant VX Series Manuale utente

Verdant
Verdant VX-TW Manuale utente

Verdant
Verdant V8-BB-7S Manuale utente

Verdant
Verdant VX Series Manuale utente

Verdant
Verdant VX-TW Istruzioni di installazione e manutenzione

Verdant
Verdant VX Series Istruzioni operative e di manutenzione