Viega ProPress Manuale utente

Installation Manual
Viega ProPress®

Table of Contents
2 of 38IM-PP 724607 1218 ProPress
Table of Contents
1 About this Document ______________________________________ 5
1.1 Disclaimer ____________________________________________ 5
1.2 Symbols Used _________________________________________ 5
2 Product Information _______________________________________ 6
2.1 ProPress Systems ______________________________________ 6
2.2 Safety ________________________________________________ 6
2.2.1 Drinking Water Installation ________________________ 6
2.3 Areas of Use __________________________________________ 7
2.3.1 Commercial and Residential ______________________ 8
2.3.2 Industrial and Plant Operations ____________________ 8
2.3.3 Fire Protection Systems __________________________ 8
2.3.4 Design Services _________________________________ 8
2.4 Product Description ____________________________________ 8
2.4.1 Overview _______________________________________ 8
2.4.2 Listings and Certications_________________________ 9
2.4.3 Codes and Standards ____________________________ 9
2.4.4 Copper Tubing _________________________________ 10
2.4.5 Press Fittings __________________________________ 10
2.4.5.1 Viega ProPress Fittings ___________________ 10
2.4.5.2 Viega ProPress XL-C Fittings ______________ 10
2.4.5.3 EPDM Sealing Element ___________________ 10
2.4.5.4 Cylindrical Guides _______________________ 11
2.4.5.5 Fitting Markings _________________________ 11
2.4.5.6 Viega Smart Connect Technology __________ 12
2.5 General Installation Requirements ________________________ 12
2.5.1 Required Tools _________________________________ 12
2.5.2 Expansion _____________________________________ 13
2.5.3 Electrical Bonding ______________________________ 13
2.5.4 Exposure to Freezing Temperatures _______________ 14
2.5.5 Underground Installations ________________________ 14
2.5.6 Corrosion Protection ____________________________ 14
2.5.6.1 Mixed Installations _______________________ 14
2.5.7 Pressure Surges _______________________________ 15
2.5.8 Rotating a Pressed Fitting _______________________ 15
2.5.9 Deection _____________________________________ 15
2.5.9.1 Controlling Deection ____________________ 16
3 Handling Instructions _____________________________________ 17
3.1 Transport ____________________________________________ 17
3.2 Storage ______________________________________________ 17

Table of Contents
3 of 38IM-PP 724607 1218 ProPress
4 Installation Instructions ___________________________________ 18
4.1 Check System Components ____________________________ 18
4.1.1 Replacing the Sealing Element ___________________ 18
4.2 Installing and Mounting the Tube ________________________ 19
4.2.1 Pipe Hangers and Supports ______________________ 19
4.3 Space Requirements and Intervals _______________________ 19
4.3.1 Transition Fittings _______________________________ 20
4.3.1.1 Threaded Connections ___________________ 20
4.3.1.2 Flange Connections ______________________ 20
4.3.2 Minimum Distance between Fittings _______________ 20
4.3.3 ProPress Jaws Clearance Requirements ___________ 20
4.3.4 ProPress Rings Clearance Requirements ___________ 22
4.4 Soldering or Brazing ___________________________________ 24
4.4.1 Using ProPress Near Existing Fittings ______________ 24
4.4.2 Soldering or Brazing Near Existing ProPress Fitting __ 24
4.5 Welding _____________________________________________ 25
4.5.1 Welding Adjacent to a Fitting _____________________ 25
4.5.2 Welding In Line with a Fitting _____________________ 25
4.6 Cutting the Tube ______________________________________ 26
4.7 Deburring the Tube ____________________________________ 26
4.8 Pressing the Fitting ____________________________________ 27
4.8.1 Viega ProPress Installation _______________________ 27
4.8.2 Viega ProPress XL-C Installation __________________ 30
4.9 Pressure Testing ______________________________________ 33
4.10 Disposal _____________________________________________ 33
5 Limited Warranty _________________________________________ 34
5.1 Limited Warranty for ProPress Fittings and Valves __________ 34
5.2 Limited Warranty for Industrial Application _________________ 35
5.3 Limited Warranty for Marine Application ___________________ 36

Table of Contents
4 of 38IM-PP 724607 1218 ProPress
List of Tables
Table 1 Fluids and water approved for use with ProPress systems ____ 7
Table 2 Gases approved for use with ProPress systems ____________ 7
Table 3 Minimum distance between press ttings _________________ 20
Table 4 ProPress standard jaws clearance requirements ___________ 21
Table 5 ProPress standard jaws clearance requirements between
tube, wall, and oor ___________________________________ 21
Table 6 ProPress compact jaws clearance requirements ___________ 21
Table 7 ProPress compact jaws clearance requirements between
tube, wall, and oor ___________________________________ 21
Table 8 ProPress rings dimensions _____________________________ 22
Table 9 ProPress rings with V1 Actuator clearance requirements ____ 22
Table 10 ProPress rings with V2 Actuator clearance requirements ____ 22
Table 11 ProPress rings with V1 Actuator clearance requirements
between tube, wall, and oor ___________________________ 22
Table 12 ProPress rings with V2 Actuator clearance requirements
between tube, wall, and oor ___________________________ 23
Table 13 ProPress rings with C1 Actuator clearance requirements
between tube, wall, and oor ___________________________ 23
Table 14 ProPress XL-C rings dimensions ________________________ 23
Table 15 ProPress XL-C rings clearance requirements ______________ 23
Table 16 ProPress XL-C rings clearance requirements between tube,
wall, and oor ________________________________________ 23
Table 17 Minimum distance between existing soldered or brazed tting
and ProPress tting ___________________________________ 24
Table 18 Minimum distance between existing ProPress tting and soldered
or brazed tting _______________________________________ 25
Table 19 Minimum insertion depths for ProPress ___________________ 27
Table 20 Insertion depths for ProPress non-stop couplings __________ 28
Table 21 Insertion depths for ProPress extended non-stop couplings _ 28
Table 22 Minimum insertion depths ProPress XL-C _________________ 31
Table 23 Insertion depths for ProPress XL-C non-stop couplings _____ 31

About this Document
5 of 38
IM-PP 724607 1218 ProPress
1 About this Document
DANGER!
This symbol warns of possible life-threatening injury.
WARNING!
This symbol warns of possible serious injury.
CAUTION!
This symbol warns of possible injury.
NOTICE!
This symbol warns of possible damage to property.
Notes give additional helpful tips.
1.1 Disclaimer
1.2 Symbols Used
The following symbols may be used within this document:
Viega products are designed to be installed by licensed and
trained plumbing and mechanical professionals who are
familiar with Viega products and their installation. Installation
by non-professionals may void Viega LLC’s warranty.
This document is subject to updates. For the most current
Viega technical literature please visit www.viega.us.

Product Information
6 of 38
IM-PP 724607 1218 ProPress
Please read and understand the instructions before beginning installation
to eliminate safety concerns and reduce risks associated with use and
handling of Viega products.
Viega ProPress systems are state-of-the-art press tting systems
that provide economical and reliable installations for the commercial,
industrial, and residential markets.
Viega ProPress are copper and zero lead bronze ttings and valves in
copper tube size (CTS) ranging from ½ inch to 2 inches for ProPress
ttings and 2½ inches to 4 inches for ProPress XL-C® (Copper) ttings.
The ttings require no soldering or brazing and are installed with electro-
hydraulic press tools (battery-powered or corded press tools).
The ttings feature a green dot representing Smart Connect® technology
with an EPDM sealing element suitable for many applications. Viega’s
unique, patented Smart Connect technology helps installers ensure that
they have pressed all connections.
2 Product Information
2.1 ProPress Systems
2.2 Safety
2.2.1 Drinking Water Installation
Standard engineering practices must be observed for planning,
installation, operation, and maintenance of drinking water installations.
Only EPDM sealing elements are approved in drinking water installations.
The use of other sealing elements is not permitted.

Product Information
7 of 38
IM-PP 724607 1218 ProPress
The use of the system for applications other than those
listed or outside of these parameters must be approved by
the Viega Technical Services Department.
2.3 Areas of Use
Type of Service Comments Pressure Temperature
Hot and cold potable water 200 psi 32° to 250°F
Rainwater / gray water 200 psi 32° to 250°F
Fire sprinklers Listed with UL and FM 175 psi 32° to 250°F
Chilled water Ethylene glycol /
propylene glycol 200 psi 0° to 250°F
Hydronic heating Ethylene glycol /
propylene glycol 200 psi 0° to 250°F
Cooling water Up to 50% ethylene
glycol or propylene
glycol solution
200 psi 0° to 250°F
Low-pressure steam ≤ 15 psi max 250°F
Ethanol Pure grain alcohol 200 psi Ambient
Table 1: Fluids and water approved for use with ProPress systems
Type of Service Comments Pressure Temperature
Compressed air Oil concentrate
< 25 mg/m3200 psi 0° to 140˚F
Oxygen - O2 (nonmedical) Keep oil and fat free
/ non-liquid O2
140 psi 0° to 140˚F
Nitrogen - N2200 psi 0° to 140˚F
Carbon dioxide - CO2200 psi 0° to 140˚F
Argon Welding use 200 psi 0° to 140˚F
Hydrogen - H2125 psi 0˚ to 140˚F
Vacuum 29.2" of Hg 0° to 160˚F
Table 2: Gases approved for use with ProPress systems
It is recommended that all systems be clearly labeled with the uid or gas
being conveyed. In the absence of local requirements, systems should be
identied in accordance with ANSI/ASME A13.1.

Product Information
8 of 38
IM-PP 724607 1218 ProPress
2.3.1 Commercial and Residential
ProPress systems are approved for numerous applications in commercial
and residential markets including potable water. “Zero Lead” identies
products meeting the lead-free requirements of NSF 61 through testing
under NSF/ANSI 372 (0.25% or less maximum weighted average lead
content).
2.3.2 Industrial and Plant Operations
ProPress systems are also suitable for use in industrial and plant
processes. Primary areas of application include:
■ Utility systems
■ Process piping
■ Cooling water
■ Potable water
■ Fire sprinkler systems
2.3.3 Fire Protection Systems
The system components may be installed in NFPA 13, 13R, and 13D
re sprinkler systems. They are certied for use in “wet” and “dry” re
protection systems in accordance with UL and FM certications:
■ UL/ANSI 213: Standard for Rubber Gasketed Fittings for Fire-
Protection Services.
■ ULC ORD-C213: Canadian Standard for Rubber Gasketed Fittings for
Fire-Protection Services.
■ FM Class 1920: Pipe Couplings and Fittings for Aboveground Fire
Protection Systems.
2.3.4 Design Services
Consult Viega’s Technical Services Department for information on applications
not listed or applications outside listed temperature and pressure ranges.
■ Viega Technical Services Department: T[email protected]
■ Design Service: For more information on re protection system design,
radiant system design, and plumbing design services: [email protected]
2.4 Product Description
2.4.1 Overview
ProPress systems consists of copper and Zero Lead bronze press ttings
for copper tubes and the corresponding press tools.

Product Information
9 of 38
IM-PP 724607 1218 ProPress
2.4.2 Listings and Certications
The ttings have the following listings and certications:
■ ABS: American Bureau of Shipping Type Approval
■ ASME B16.51: Copper and Copper Alloy Press-Connect Pressure Fittings
■ ASME B31.1: Power Piping
■ ASME B31.3: Process Piping
■ ASME B31.9: Building Service Piping
■ BV: Bureau Veritas Type Approval
■ Canadian Registration Number (CRN): 0A14541.5 A/B/C
■ CSA Low Lead Content
■ DNV GL: Det Norske Veritas Germanischer Lloyd Type Approval
■ FM Class 1920: Pipe Couplings and Fittings for Aboveground Fire
Protection Systems
■ IAPMO PS-117: Press and Nail Connections
■ ICC-ES LC1002: Copper and Copper Alloy Press-Connect Pressure Fittings
■ LR: Lloyd’s Register Type Approval
■ NFPA 13: Standard for the Installation of Sprinkler Systems
■ NFPA 13D: Standard for the Installation of Sprinkler Systems in One-
and Two-Family Dwellings and Manufactured Homes
■ NFPA 13R: Standard for the Installation of Sprinkler Systems in Low-
Rise Residential Occupancies
■ NKK: Nippon Kaija Kyokai Type Approval
■ NSF/ANSI 61: Drinking Water System Components – Health Eects
■ NSF/ANSI 372: Drinking Water System Components – Lead Content
■ UL/ANSI 213: Standard for Rubber Gasketed Fittings for Fire-
Protection Service
■ ULC/ANSI ORD-C213: Canadian Standard for Rubber Gasketed
Fittings for Fire-Protection Service
2.4.3 Codes and Standards
ProPress ttings comply with the following codes and standards:
■ ASME B31: Code for Pressure Piping
■ ASTM B88: Standard Specication for Seamless Copper Water Tube
■ IAPMO California Plumbing Code (CPC)
■ IAPMO National Standard Plumbing Code (NSPC)
■ IAPMO Uniform Mechanical Code (UMC)
■ IAPMO Uniform Plumbing Code (UPC)
■ ICC International Mechanical Code (IMC)
■ ICC International Plumbing Code (IPC)
■ ICC International Residential Code (IRC)
■ National Building Code of Canada (NBCC)
■ National Plumbing Code of Canada (NPCC)
It is the responsibility of the installer or any other parties
to adhere to all applicable local rules and regulations
governing the nature of the installation.

Product Information
10 of 38
IM-PP 724607 1218 ProPress
2.4.4 Press Fittings
2.4.4.1 Viega ProPress Fittings
1 Each tting contains an application specic sealing element. A green
dot on a Viega ProPress tting indicates the presence of Smart
Connect technology and an EPDM sealing element.
2 Viega’s distinctive hexagonal pressing pattern bonds tting and tube
and provides the mechanical strength for the connection.
3 Color coded dots indicate the presence of Viega’s unique, patented
Smart Connect technology which helps installers ensure that they
have pressed all connections.
4 Cylindrical guides ensure the proper insertion of the tube and protects
the sealing element.
2.4.4.2 Viega ProPress XL-C Fittings
Viega ProPress ttings are manufactured with a high-quality, shiny black
EPDM (Ethylene Propylene Diene Monomer) sealing element installed at
the factory. The molded sealing lips also seal tube surfaces with slightly
uneven surfaces. Sealing elements are inserted into the tting using a H1
food grade lubricant registered with NSF and the USDA, and is approved
for use under FDA 21 CFR.
The EPDM sealing element possesses excellent resistance to aging,
ozone, sunlight, weathering, environmental inuences, and most alkaline
solutions and chemicals used in a broad range of applications.
The operating temperature of the EPDM sealing element is 0° to 250°F
(-18° to 120°C).
2.4.4.3 EPDM Sealing Element
1 The 420 stainless steel grip ring's teeth cut into the tube and lock the
tting securely in place.
2 A PBT (Polybutylene Terephthalate) separator ring protects the sealing
element from damage by creating a positive physical separation during
installation and later during pressing.
3 The EPDM sealing element ensures water-tight or air-tight connections.
ProPress XL-C ttings are designed to be pressed with ProPress XL-C press
rings and V2 actuator to produce a non-detachable, secure connection.
2.4.5 Copper Tubing
Copper and copper alloy ttings are compatible with ½ inch to 1¼ inches soft
copper tubing and ½ inch to 4 inches hard copper tubing types K, L, and M. All
copper tubing that is to be used must comply with ASTM B88 standards.
Copper tubing must be free of surface imperfections,
including metal stamped print lines, before a ProPress
tting is installed.
Indice
Altri manuali Viega Utensili elettrici

Viega
Viega Pressgun 6 Manuale utente

Viega
Viega Picco 6 Manuale utente

Viega
Viega MegaPress XL Manuale utente

Viega
Viega Picco 6 Manuale utente

Viega
Viega Pressgun 6 Manuale utente

Viega
Viega MegaPress XL PressBooster 4896.2XL Manuale utente

Viega
Viega Eco Plus Manuale utente

Viega
Viega Pressgun Press Booster PT2 Manuale utente

Viega
Viega Pressgun 6B Manuale utente

Viega
Viega 4296.2XL Manuale utente