Viessmann VITOTROL 200 RF Guida rapida

Installation and service
instructions
for contractors
VIESMANN
Wireless base station
For connecting a Vitotrol 200 RF and outside temperature sensor RF
to a Vitotronic control unit
For applicability, see the last page
Wireless base station
5692 915 GB 6/2011 Please keep safe.

2
Please follow these safety instructions closely to prevent accidents and mate-
rial losses.
Safety instructions explained
Danger
This symbol warns against the
risk of injury.
!Please note
This symbol warns against the
risk of material losses and envi-
ronmental pollution.
Note
Details identified by the word "Note" con-
tain additional information.
Target group
These instructions are exclusively
designed for qualified personnel.
■ Work on gas equipment must only be
carried out by a qualified gas fitter.
■ Work on electrical equipment must
only be carried out by a qualified elec-
trician.
■ The system must be commissioned by
the system installer or a qualified per-
son authorised by the installer.
Regulations
Observe the following when working on
this system
■ all legal instructions regarding the pre-
vention of accidents,
■ all legal instructions regarding envi-
ronmental protection,
■ the Code of Practice of relevant trade
associations,
■ all current safety regulations as
defined by DIN, EN, DVGW, TRGI,
TRF, VDE and all locally applicable
standards,
■ Gas Safety (Installation & Use) Regu-
lations
– the appropriate Building Regulation
either the Building regulations, the
Building Regulation (Scotland),
Building Regulations (Northern Ire-
land),
– the Water Fittings Regulation or
Water Bylaws in Scotland,
– the current I.E.E. Wiring Regula-
tions.
If you smell gas
Danger
Escaping gas can lead to explo-
sions which may result in serious
injury.
■ Never smoke. Prevent naked
flames and sparks. Never
switch lights or electrical appli-
ances ON or OFF.
■ Close the gas shut-off valve.
■ Open windows and doors.
■ Remove all people from the
danger zone.
■ Notify your gas or electricity
supplier from outside the build-
ing.
■ Shut off the electricity supply to
the building from a safe place
(outside the building).
Safety instructions
Safety instructions
5692 915 GB

3
If you smell flue gas
Danger
Flue gas can lead to life-threat-
ening poisoning.
■ Shut down the heating system.
■ Ventilate the boiler room.
■ Close all doors leading to the
living space.
Working on the system
■ When using gas as fuel, also close the
main gas shut-off valve and safeguard
against unauthorised reopening.
■ Isolate the system from the power sup-
ply and check that it is no longer 'live',
e.g. by removing a separate fuse or by
means of a main isolator.
■ Safeguard the system against unau-
thorised reconnection.
!Please note
Electronic modules can be dam-
aged by electro-static dis-
charges.
Touch earthed objects, such as
heating or water pipes, to dis-
charge static loads.
Repair work
!Please note
Repairing components which ful-
fil a safety function can compro-
mise the safe operation of your
heating system.
Replace faulty components only
with original Viessmann spare
parts.
Ancillary components, spare and
wearing parts
!Please note
Spare and wearing parts which
have not been tested together
with the heating system can com-
promise its function. Installing
non-authorised components and
non-approved modifications/con-
version can compromise safety
and may invalidate our warranty.
For replacements, use only orig-
inal spare parts from Viessmann
or those which are approved by
Viessmann.
Safety instructions
Safety instructions (cont.)
5692 915 GB

4
Installation instructions
Installation sequence
Installation location............................................................................................... 5
Connecting the wireless base station to the control unit...................................... 6
Logging the wireless components on at the wireless base station...................... 7
Fitting the wireless repeater................................................................................. 10
Checking the transmission and reception quality of the Vitotrol 200 RF.............. 10
Fitting the wall mounting base of the wireless base station................................. 11
Inserting and removing the wireless base station................................................ 11
Fitting the outside temperature sensor RF........................................................... 13
Service instructions
Diagnosis
Diagnosis on the Vitotrol 200 RF.......................................................................... 15
Diagnosis at the wireless base station................................................................. 15
Specification
Specification, wireless base station...................................................................... 16
Specification, outside temperature sensor RF..................................................... 16
Specification, wireless repeater............................................................................ 16
Parts list.............................................................................................................. 17
Index
Index
5692 915 GB

5
Connecting several remote control units
Up to three Vitotrol RF and one outside
temperature sensor RF can be connec-
ted to a single wireless base station at
any one time.
Wireless connection
Select the installation location of the
wireless base station and the other wire-
less components so that the radio sig-
nals are beamed as vertically as possible
onto walls and furnishings.
C
B
B
DC
A
F
E
AWireless base station
BOutside temperature sensor RF
CVitotrol RF
DWireless repeater
EHeat source
FKM BUS
Installation sequence
Installation location
5692 915 GB
Installation

6
Install the wireless base station as cen-
trally as possible inside the building. Site
wireless components at least 0.5 m away
from other transmitters (e.g. GSM,
DECT, wireless LAN) and other HF sour-
ces of potential interference (computers
etc.).
Note
Conducting metallic materials have a
strong negative effect on reception.
Prior to the final fitting at the chosen
installation location, commission all wire-
less components and check the trans-
mission and reception quality at the
installation location.
If adequate transmission and reception
quality cannot be achieved, install a wire-
less repeater (accessory).
Preparing the outside temperature sensor RF for commissioning
Remove the outside temperature sensor
RF from its packaging and position it fac-
ing a light source to enable the internal
power supply to build up. This takes
approx. 15 min.
Connecting the wireless base station to the control unit
Note
Initially, make a provisional connection
for the wireless base station to allow a
different location to be selected later if
the transmission and reception quality
needs to be improved.
Installation sequence
Installation location (cont.)
5692 915 GB

7
A
B
4 3 2 1
3 2 17 6 5 4
X3X4 C
145
1 2
3 2 12 1 5 4
X3X4 D
145
AWireless base station
BPlug aVG to the control unit or to the
KM BUS distributor
CControl unit with terminals X3
DControl unit with plug-in connection
aVG
Logging the wireless components on at the wireless base sta-
tion
Note
If a wireless repeater is used, log all com-
ponents on via the wireless repeater.
Should a wireless repeater become nec-
essary later, log all components off and
then log them on again via the wireless
repeater (see page 14).
1. Make a note here of the 3-digit PIN on
the protective foil on the front of the
wireless base station: ___ ___ ___.
Installation sequence
Connecting the wireless base station to the… (cont.)
5692 915 GB
Installation

8
2. Place all components near the wire-
less base station.
Position the wireless base station at
least 1 m away from the wireless
repeater (if installed).
A
3. Press A on the wireless base sta-
tion:
■ Operation without wireless
repeater: 4 s.
LED flashes green in long intervals.
■ Operation with wireless repeater:
8 s.
LED flashes green in short inter-
vals.
Note
If all components are logged on in
sequence, press A on the wireless
base station once for each compo-
nent.
4. Initiate the logging on process at the
relevant component. See the follow-
ing chapter.
Logging on the Vitotrol 200 RF
Vitotrol 200 RF installation and
service instructions
Installation sequence
Logging the wireless components on at the… (cont.)
5692 915 GB

9
Logging on the outside temperature sensor RF
AB
1. Only if the outside temperature sen-
sor is not logged on together with the
other components:
Initiate the logging on process at the
wireless base station (see page 7).
2. Open the casing of the outside tem-
perature sensor.
3. Briefly press A on the outside tem-
perature sensor.
The B LED on the outside temper-
ature sensor flashes briefly red if it
was successfully logged on.
Installation sequence
Logging the wireless components on at the… (cont.)
5692 915 GB
Installation

10
1. Secure the wireless repeater near a
socket.
2. Insert the wireless repeater cable into
the power supply unit.
3. Plug the power supply unit into a
socket.
Note
Logging on process with wireless
repeater (see page 7).
Never adjust the DIP switches on the
back of the unit.
Checking the transmission and reception quality of the Vitotrol
200 RF
To determine the most favourable place
to install a Vitotrol 200 RF, check the
transmission and reception quality at the
intended installation location.
See the diagnosis chapter or the Vitotrol
installation and service instructions.
Installation sequence
Fitting the wireless repeater
5692 915 GB
Altri manuali per VITOTROL 200 RF
4
Indice
Altri manuali Viessmann Accessori

Viessmann
Viessmann KOB 8110-1 Manuale del sistema

Viessmann
Viessmann 5206 Manuale utente

Viessmann
Viessmann 4519 Manuale utente

Viessmann
Viessmann ESS CHP Guida all'installazione

Viessmann
Viessmann ViCare Manuale utente

Viessmann
Viessmann TectoRefrigo WMC1 Manuale utente

Viessmann
Viessmann Wireless base station Istruzioni operative