3.3. CONFIGURATION PARAMETERS
Parameters are available for user configuration through a HART
®
programmer. In addition to the parameters inherent
to the protocol, there are some basic parameters to be configured before starting the converter: the address of the
equipment to be monitored, the codes of the variables to be monitored, units and working ranges for calculating the
currents.
The parameters inherent to the protocol concern the converter itself, basically dealing with its identification (Tag,
Description, Date, Address) and calibration of the currents to be used as output signals of the monitored variables.
For more details on each of these parameters and where to configure them, see section 3.5.
CONFIGURATION WINDOW
VHC10-P normally works as a "master" in order to monitor the "slave" equipment and generate currents proportional
to the monitored variables. So, converter will not receive HART
®
commands from another master, making it
impossible to configure it when in this mode.
To configure it, the user must follow the procedure below.
a. Reset VHC10-P converter
The converter will wait for configuration commands to be received. If no command is sent within 30 seconds", the
"master mode will be enabled automatically.
b. Localize the conversor
Using a HART
®
configurator, poll device at address one (1) – or at the address modified by user user.
c. Change mode to Configuration
In the "Settings" directory, change the converter mode to "Configuration". From this moment on, the user will be able
to make any configuration with peace of mind, without the converter going back to the "master" mode.
d. Configure addresses, variables and ranges
User must verify that the address of the "slave" equipment, the codes of the variables to be monitored, working
ranges and units are correct.
The variables to be monitored can be chosen among the dynamic variables (PV, SV, TV or QV) or by a variable-
specific code index (check the indexes available in the monitored product manual).
e. Change mode to Monitoring
In the "Settings" directory, change the converter mode to "Monitoring" (or "Enable Master Mode", according to the
configurator used). From this moment on, the user will no longer be able to configure the converter and it will work in
"master" mode.
As VHC10-P converter will be connected on the same HART
®
line as the equipment monitored, its default
address is one (1). Therefore, when using the HART
®
configurator for configuration, this address must be
entered by the user in the 'Polling Address' field.
If the converter enters monitoring mode and the user wants to change any configuration, the procedure
must be restarted.
Vivace configuration tools such as VMT-HART and converter DTM already send this command