Voltacon ESS12100 Manuale utente

ESS12V100Ah LFP Battery User Manual
Rechargeable Li-ion Battery
ESS12100 User Manual
Information Version: 1.0
20ESS-SV0801

This manual introduces ESS12100 from Voltacon. Please read this manual
before installing the battery and follow the instruction carefully during the
installation process. Any questions, please contact Voltacon immediately
for advice and clarification.
Content
1 Product introduction...........................................................................................1
1.1 Product features.............................................................................................1
1.2 Scope and purpose of application.............................................................. 1
2 Product parameters.............................................................................................2
2.1Battery module technical parameters..........................................................2
3 Installation Environment.......................................................................................7
4 Transportation and storage requirements.......................................................8
4.1 Product transportation requirements.......................................................... 8
4.2 Product storage requirements..................................................................... 8

1
1 Product introduction
1.1 Product features
Voltacon Lithium Iron Phosphate Battery is perfect for deep-cycle
applications including electric vehicles, solar/wind energy systems, UPS
battery backup, telecommunication systems, medical equipment, and more..
Voltage platform: 12V
High C rate: the output power reaches sustained 1C
High safety: lithium iron phosphate battery is safe and reliable
High reliability: interactive cooperative guarantee mechanism is
adopted to improve system reliability
Minimalist design: bolt design of positive and negative terminals
with strong adaptability
Battery status information display, SOC display
Ultra-long cycle life: 3000 cycles
Can be connected in parallel to 4 batteries
1.2 Scope and purpose of application
This battery is mainly used for lead-acid battery replacement.

2 Product parameters
2.1Battery module technical parameters
Table 4 -Technical parameters of battery module
NO
Item
Value
1
Nominal capacity
100 Ah
2
Nominal voltage
12.8Vdc
3
Voltage range
DC 10V ~14.8V
4
Continuous charging current
DC 50A
5
Continuous discharging current
DC 100A
6
Working temperature
-20℃~50℃
7
Humidity
5~95%
8
Cooling
Natural cooling
9
Dimension
300mm*173mm*220mm
10
Weight
≤15kg
11
IP rate
IP20
12
Communication
Optional

13
Parallel Connection
supported
2.2 Panel definition
Battery switch:
Press the Power Button for “1S” and the battery is on.
In order to save energy ,after 30s,all the indicator light will shut down.
If customers want to see the battery status, please press the power button 1s
again.
Long press the Power Button “3S” to turn off the battery.
Self-check lamp status:When the initial self-check is completed, all lights will
be turn on for a while and then return to the normal display state.
Please refer to the table below for normal display state:
Indicator light description:

Alarm
★
According to Soc state
The
State
Soc
Status
SOC
Remark
●★Ru
n
●★
ALM
SOC4
SOC3
SOC2
SOC1
Turn off
All off
Idle
0%-25%
●
●
All SOC
Light is solid
26%-50
%
●
●
51%-75
%
●
●
●
76%-10
0%
●
●
●
●
Charge
0%-25%
●
★
The SOC
top one is
flashing,oth
ers are solid
26%-50
%
★
●
51%-75
%
★
●
●
76%-10
0%
★
●
●
●
discharg
e
100%-7
6%
★
●
●
●
●
The Run
light is
flashing
75%-51
%
●
●
●
50%-26
%
●
●
25%-0%
●
Protect
Protect
Hardware
damaged

Alarm
protected
state can be
released
upon
reaching the
recovery
condition
Protect
Protect
●
Hardware
damaged
●:Green light solid
★:Green light flashing (2S flashing)
★★:Green light flashing (4S flashing)
●:Red light solid
★:Red light flashing (2S flashing)
★★:Red light flashing (4S flashing)
2.3 System wiring
2.3.1 Parallel connection
Before wiring the battery model, make sure all batteries are turned off .Follow
the steps shown below for wiring, with all positive poles together and all
negative poles together. Then press any battery’ Power button and the other
batteries will turn on automatically.

Notice:
1、The number of parallel connections is limited to 4 pcs.
2、Ensure that the voltage difference between the batteries should not exceed
0.5V before connection.
3、Each set of the battery external cables should have the same wire
diameter and length. This keeps the current flow of each battery consistent
during operation.
4、When 2~4 battery are connected in parallel, the charge-discharge current
shall not exceed 0.5C of the Total current.
2.3.2 Series Connection
Before wiring the battery model, Make sure all batteries are turned off .Follow
the steps shown below for wiring.Then press any battery’ Power button one by
one.
Notice:

1、The number of series connections is limited to 2 pcs,24V.
2、Each battery should have the same capacity and the same voltage.
Otherwise it will affect subsequent use.If not, please first connect the battery in
parallel to internal balance and then use it in series.
3、If one battery goes into protective mode, the whole system will shutdown.
4、Each set of the battery external cables should have the same wire diameter
and length. This keeps the current flow of each battery consistent during
operation.
3 Installation Environment
Battery operating environment requirements are as follows:
Working temperature:0℃- 50℃
Humidity:5% - 95%
Altitude:<4000m
The site environment:Away from heat, no corrosive gas, no explosive gas, no
damaging gas, no damaging insulation Conductive dust.

4 Transportation and storage requirements
4.1 Product transportation requirements
Battery in the process of transportation should prevent violent vibration, impact
or extrusion, to prevent the sun and rain, can use cars, trains, ships, aircraft
and other means of transportation.
In the process of loading and unloading, the battery should be handled gently
to prevent throwing, rolling and weight.
4.2 Product storage requirements
Batteries should be stored in clean, dry and ventilated rooms where the
ambient temperature is -20℃~ 60℃and the relative humidity is no more than
85%.
Battery should avoid contact with corrosive substances, should be far away
from the source of fire and heat.
Battery storage SOC: 40% ~ 50%.
Long-term storage: before storage, the SOC should be more than 80%, and
the battery should be recharged every six months.The charging amount should
exceed 80% of the capacity