Series 733/734
Watlow Controls, 1241 Bundy Blvd., P.O. BOX 5580, Winona, MN 55987-5580, Phone: 507/454-5300, Fax: 507/452-4507
Service Manual

2WATLOW Series 733/734 Service Manual Install & Wire, Chapter 1
This manual is a supplement to the Series 733/734 Program Manual. It is for
configuring, servicing and calibrating your control. Use this manual in conjunc-
tion with the Series 733/734 Program Manual and Data Communications manual.
Contents
Technical Assistance
If you encounter a problem with your Series 733/734
control, review all of your configuration information to
verify that your selections are consistent with your
application... Inputs, Outputs, Alarms, Limits, etc. If the
problem persists after checking the above, you can get
technical assistance by dialing: 1-507-454-5300
An Application Engineer will discuss your problem with
you. Please have the following information available:
• Complete model number • Revision number
• All configuration information • User's manual
The model and serial numbers can be found on the
outside of the case.
Your Feedback
Your comments or suggestions on the manual are
welcome, please send them to: Technical Writer, Watlow
Controls, 1241 Bundy Blvd., P.O. Box 5580, Winona, MN
55987-5580, or phone 507/454-5300. The Watlow Series
733/734 Service Manual and integral software are
copyrighted by Watlow Winona, Inc., © 1995, with all
rights reserved.
PageItem
Chapter 1
3 Install and Wire the Series 733/734
3 Dimensions
3 Panel Cutout
4 How to Wire the Series 733/734
5 Power Wiring
5 Input Wiring
8 Output 1 Wiring
9 Output 2 Wiring
10 Event Input Wiring
10 Event Output Wiring
10 Alarm Wiring
11 System Wiring Examples
Chapter 2
12 The Setup Mode
12 Advancing Through the Setup Mode
12 Select or Change Setup Data Within the Mode
13 Setup Parameters
16 Setup ModeTable
Notes
˜
Informational notes alert you to important details.
When you see a note icon, look for an explanation in
the margin.
Safety Information
Boldface safety information protects both you and
your equipment. Please be attentive to them. Here
are explanations:
ç
The CAUTION symbol (exclamation point) in the wide
text column alerts you to a "CAUTION," a safety or
functional hazard which could affect
your equipment
or
its performance. A full explanation is in the narrow
column on the outside of the page.
∫
The WARNING symbol (lightning bolt) in the wide text
column alerts you to a "WARNING," a safety hazard
which could affect
you and the equipment
. A full
explanation is in the narrow column on the outside of
the page.
Chapter 3
16 The Service Mode
17 Service Parameters
18 Service Mode Table
Chapter 4
20 Auto-Tuning
21 Manual Tuning
Chapter 5
22 The Calibration Mode
23 Calibration Parameters
24 Calibration Procedures
Appendix
30 Glossary
32 Index
33 Warranty/Returns
34 Specifications
35 Ordering Information
36 CE Declaration of Conformity
37 Notes
38 Notes

3
WATLOW Series 733/734 Service Manual
Install & Wire, Chapter 1
Install
Chapter 1
Install and Wire the Series 733/734
Front panel mounting for ease of installation and service.
Series 734
Figure 1 -
Series 733 and 734
Dimensions.
˜
NOTE:
For Series 734
orientation (verti-
cal), rotate the panel
cutout 90°.
Figure 2 -
Panel Cutout.
1.975
(50 mm)
Series 733
Panel Cutout ˜
SERIES 733
TL
W
W
A
81012
1 3 5
2 4 6 7 9 11
EVENT LOAD 1READY
MENUS
10.625"
(270 mm)
3.25"
(83 mm)
SERIES 734
1
10
7
4
2
11
8
5
3
12
9
6
EVENT READY LOAD 1
MENUS
TL
W
W
A
10.625"
(270 mm)
3.25"
(83 mm)
9.78"
(248 mm)
3.13"
(80 mm)
0.27" Dia.
(7 mm)
2.75"
(70 mm)
Use four #6-32 screws
with nutserts
(customer supplied)
10.13"
(257 mm)
R 0.125"
(3 mm) Max.
Use four #6-32 screws
with press-in-nuts
(customer supplied)
1. Make a panel cutout per the dimensions given above.
2. Drill four 0.265 (7mm) diameter holes per the dimensions given above..
See Figure 2.
3. Mount the Series 733 or 734 with four #6-32 screws using press-in-nuts,
weld nuts, or equivalent…

4WATLOW Series 733/734 Service Manual Install & Wire, Chapter 1
Wiring
Figure 6 -
Series 733/734
Rear View.
9-pin
Event Input/
Output
Connector
12-pin
Output Wiring
Connector
Input/
Communications
Connector
How to Wire the Series 733/734
The Series 733/734 wiring is illustrated by model number option. Check the
terminal designation sticker on the control and compare your model number to
those shown here and also the model number breakdown on the inside back
cover of this manual.
When you apply power without sensor inputs on the terminal strip, the Series
733/734 display alternates parameter data and Er07 at a 3 second rate.
This error indicates an open sensor or A/D error. Remove power to the control
and connect the sensor properly. All wiring and fusing must conform to the
National Electric Code and to any locally applicable codes as well.
Use Figure 6 as a location reference when wiring your unit.

5
WATLOW Series 733/734 Service Manual
Install & Wire, Chapter 1
Wiring
Figure 8 -
Input Wiring Con-
nector.
Figure 7 -
24VÅÅ
ÅÅ
Å(VAC) Power
Wiring.
∫
WARNING:
To avoid potential
electric shock, use
National Electric
Code (NEC) safety
practices when
wiring and connect-
ing this unit to a
power source and to
electrical sensors or
peripheral devices.
12345678910 11 12
1
2
3
4
5
6
7
8
9
10
11
12
Fuse
L2
L1
Power Wiring
Input Wiring
Use this wiring connector as a reference for terminal orientation. Each indi-
vidual wiring breakdown will only show the terminals used. This connector
only applies to input wiring and communications wiring.
´ç
CAUTION:
Input power limited
to 15 watts maxi-
mum. All compo-
nents are rated for a
maximum of 15
watts.

6WATLOW Series 733/734 Service Manual Install & Wire, Chapter 1
Input Wiring
Figure 10 -
2 or 3 Wire RTD
Wiring.
Figure 9 -
Thermocouple
Wiring.
˜
NOTE:
Dual-zone thermo-
couple units require
at least one un-
grounded
thermocouple.
1
2
3
+
-
4
5
6
+
-
Thermocouple Input
73XX-1XXX-XXXX ˜(Dual Zone Only)
73XX-4XXX-XXXX
73XX-6XXX-XXXX 73XX-4XXX-XXXX
Zone 1 Zone 2
3 Wire RTD
2 Wire RTD
1
2
3
1
2
3
3 Wire RTD
2 Wire RTD
4
5
6
4
5
6
RTD Input
(Dual Zone Only)
73XX-2XXX-XXXX
73XX-5XXX-XXXX 73XX-5XXX-XXXX
Zone 1 Zone 2

7
WATLOW Series 733/734 Service Manual
Install & Wire, Chapter 1
Input Wiring
Figure 11 -
0-5VDC or 0-10VDC
Process Input
Wiring.
Figure 12 -
0-20mA or 4-20mA
Process Input
Wiring.
4
5
6+
-
DC
I
4
5
6
+
-
Zone 2
Zone 2
0-5VDC or 0-10VDC Process Input
Model # 73XX-6XXX-XXXX (Dual Zone Only)
0-20mA or 4-20mA Process Input
Model # 73XX-6XXX-XXXX (Dual Zone Only)

8WATLOW Series 733/734 Service Manual Install & Wire, Chapter 1
Output 1 Wiring
Figure 14 -
DC Output 1 Wiring.
Figure 13 -
AC Output 1 Wiring.
1
2
3
4
5
6
7
8
9
10
11
12
-
External
Load
+
-
+
1
2
3
4
5
6
7
8
9
10
11
12
External
Load
COM L1
L2
Fuse
AC Output Wiring - Zone 1
Solid State Relay
with
Mechanical Relay
with
Contact Suppression Contact Suppression
Form A, 0.4 Amps Form A, 1 Amp
Off state impedance: 20K max. Off state impedance: 20K min.
73XX-XBXX-XXXX 73XX-XDXX-XXXX
Solid State Relay
without
Solid State Relay
without
Contact Suppression Contact Suppression
Form A, 0.4Amps Form A, 1 Amp
Off state impedance: 31M max. Off state impedance: 20k max.
73XX-XKXX-XXXX 73XX-XEXX-XXXX
DC Output Wiring - Zone 1
Switched DC
(Open Collector) 4-20mA Process Output
Non-isolated Non-isolated
Minimum load resistance: 500 Load impedance: 600 max.
73XX-XCXX-XXXX 73XX-XFXX-XXXX
0-5VÅÅ
ÅÅ
Å(VDC) Process Output
Non-isolated
Load impedance: 10K min.
73XX-XHXX-XXXX

9
WATLOW Series 733/734 Service Manual
Install & Wire, Chapter 1
Output 2 Wiring
Figure 16 -
DC Output 2 Wiring.
Figure 15 -
AC Output 2 Wiring.
1
2
3
4
5
6
7
8
9
10
11
12
External
Load
+
-
-
+
1
2
3
4
5
6
7
8
9
10
11
12
External
Load
COM L1
L2
Fuse
NO
AC Output Wiring - Zone 2
Solid State Relay
with
Mechanical Relay
with
Contact Suppression Contact Suppression
Form A, 0.4 Amps Form A, 1 Amp
Off state impedance: 20K max. Off state impedance: 20K min.
73XX-XXBX-XXXX 73XX-XXDX-XXXX
Solid State Relay
without
Contact Suppression
Form A, 04 Amps
Off state impedance: 31M max.
73XX-XXKX-XXXX
DC Output Wiring - Zone 2
Switched DC
(Open Collector) 4-20mA Process Output
Non-isolated Non-isolated
Minimum load resistance: 500 Load impedance: 600 max.
73XX-XXCX-XXXX 73XX-XXFX-XXXX
0-5VÎÎ
ÎÎ
Î(VDC) Process Output
Non-isolated
Load impedance: 10K min.
73XX-XXHX-XXXX

10 WATLOW Series 733/734 Service Manual Install & Wire, Chapter 1
Optional Wiring
Figure 18 -
Event Output
Wiring.
Figure 19 -
Alarm Wiring.
˜
NOTE:
Event Input is not
available on stan-
dard Series 733/734
controls. Consult
factory for more
information.
Figure 17 -
Event Input Wiring.
1
23
4
5
6
7
89
Event Input 2
Common
Event Input 1
1
2
3
4
5
6
7
8
9
10
11
12
External
Load
COM L1
L2
Fuse
Event Input Wiring
2 Event Inputs
Non-isolated
73XX-XXX1-XXXX
Event Output Wiring
4 Event Outputs
Open Collector, Non-isolated
5mA Maximum Per Event
73XX-XXX1-XXXX
Alarm Wiring
Single Alarm
Mechanical Relay with
Contact Suppression
Form A, 1 Amp
73XX-XXXX-DXXX
1
23
4
5
6
7
89
Event 1
Event 2
Event 3
Event 4
-
-
-
-
+
Internal +5 Volt
SSR
Customer Supplied
+
+
+
SSR
SSR
SSR
Alarm
+
-