Overview of the steps to be taken
and maintenance report
Overview of the steps to be taken and maintenance report
No.
Step Report item Report item Report item
1Switch OFF the boiler, emergency stop switch is OFF
2Close the gas supply valve
3Remove the casing and the combustion chamber housing
4Unplug the electrical connections from the fan, sensors and
electrodes
5Remove the combustion chamber lid upwards
6Clean the burner, if required OOO
7Clean the heating water heat exchanger OOO
8Clean the condensate pan OOO
9Clean the mixing chamber, if required OOO
10 Check the combustion chamber insulation for damage OOO
11 Check gaskets, and if required, replace them and
lubricate with silicone grease OOO
12 Rell granulate, if a neutralising system is installed OOO
13 Check the protective anode every two years on enamelled
cylinders OOO
14 Assemble the equipment
15 Clean and ll the siphon, install and check for tight t OOO
16 Descale the DHW heat exchanger, if required OOO
17 Clean the DHW strainer OOO
18 Check the expansion vessel in case of water loss OOO
19 Open the gas supply valve and start the boiler
20 Gas leak test OOO
21 Flue gas leak test OOO
22 Check the ignition OOO
23 Check the interaction with control accessories OOO
24 Flue gas test in emissions test mode OOO
25 Gross ue gas temperature °C °C °C
26 Ventilation air temperature °C °C °C
27 Net ue gas temperature °C °C °C
28 Carbon dioxide content (CO2)%%%
29 or oxygen content (O2)%%%
30 Carbon monoxide content (CO) %%%
31 Flue gas loss %%%
Conrm maintenance (company stamp, signature)