ZOTECH Z920K-RS485 Guida

WWW.ZOTECH.COM.TW
Lasted update 2019/08/30
INTRODUCTION
Hereunder the description includes the package, and operation guides. Before start operating, please kindly read it for quick and correct
installation.
GENERRAL
Package
1. Z920K-RS485 or RS232
Device
x1
2. Antenna
x1
3. Power Adaptor 100-240Vac /24V[email protected] x1
4. Micro-USB Cable
x1
5. Magnetic Adsorptor x1
6. Din-Rail Adaptor (purchase separably) x1
Z920K
-
RS485/Z920K
-
RS232
Getting Start Guide
Micro-USBCable
Z920K
-
RS485
Z920K
-
RS232
PowerAdaptor
Din-RailAdaptor(PurchaseSeparately)
MagneticAdsorptor
SleeveAntenna
V+ (Red )
V- (Black)

2
Z920K
-
RS485
Serial Port Setting
• Protocol Modbus RTU/ASCII code
• Port Type I-RS485-2W D+/D-/GND
Note: D+ (red cord)/D- (black cord) of power adaptor
• Data indicators TX/Green, RX/Yellow
• SW2 RS485 D+/D- resistors and Terminal Resistor setting for impedance match.
Note:“120 ohm” Terminal Res. is recommended to avoid a noise bounding.
• Port Type II -RS232 DB9
DB9 pin definition
Pin 1 2 3 4 5 6 7 8 9
Definition DCD RX TX DTR GND DSR RTS CTS RI
Power
• DC
In (V+/V-)
Unregulated
10-48Vdc or 8-24Vac in
• DC Out (Vo/GND) 12Vdc out (The adaptor has to be used.)
LED indicators:
• LINK:
Link: Solid Green
Traffic: 1 Hz blinking
Link Fail: 1Hz Red Blinking
• PWR
Power ON ready: Solid green
Bootup fail: Solid red
• Network
Normal state (Mesh network ready): Solid Green
Z920K-RS232
1 2 3 4 5
6 7 8 9
ThetopviewofZ920K

3
Data transmission: Green (10Hz blinking)
Stop pairing: Green/Red 1Hz blinking simultaneously
No light: Network unable to join or escape network
• RSSI indication
3 LEDs have those 7 modes to indicate the different RSSI strength as the figure.
SW1 Communication Switch
Baud Rate (DIP5/DIP6/DIP7)
2400/4800/9600/19200/38400/57600/115200
Parity (DIP4)
。 Hi: Even
。 Lo: None
Stop Bit (DIP3)
。 Hi: 2-bit
。 Lo: 1-bit
HW Flow Control (DIP2)
。 Hi: Enable
。 Lo: Disable
Button/Connector
• Reset
Click in seconds: SW Reboot
Hold on more than 10 seconds: Z920K will be recovered as the default factory setting.
• PWR Switch Power switch on/off
• ANT SMA antenna header
• USB Micro-USB connector to plug in USB cable for console configuration
• MODE If the MOD button is asserted for 3 seconds or more, the LED display is cleared.
• PAIR
For an advanced Z920K version, the BLE pairing is active if the PAIR button is asserted for 3 seconds.
The BLE pairing is reset, if the PAIR button is asserted for 10 seconds..
TherearviewofZ920K
1 2 3 4 5 6 7
H
L
9600
57600
19200
115200
2400
38400
4800
H
i
L
APP setting
Baud Rate
DIP 5
/
6
/
7
Even
Parity
None
DIP
4
2-bit
Stop Bit
1-bit
DIP
3
Enable
HW Flow Control
Disable
DIP
2
stronger than -55 dBm
-56 dBm ~ -65dBm
-66 dBm ~ -75dBm
-76 dBm ~ -85dBm
-86 dBm ~ -90dBm
-91 dBm ~ -103dBm
weaker than -103dBm
RSSIindication

4
Accessory
• Magnetic Adsorptor
• Din-Rail Adaptor
Magnetic Adsorptor
DIN-Rail Adaptor
Z920K Bottom View
Magnetic Adsorptor Assembly
Combination with a Din-Rail adaptor
Din-Rail Adaptor Assembly

5
CONSOLE UTILITY
To register on the download website https://www.zotech.com.tw/contact-information for agreement to download Console Utility
1. Please install console utility on Window PC
2. To plug the micro-USB cable into Z920K device’s USB connector on the rear panel, and plug the other end of the USB cable into the
maintenance console PC’s USB port.
3. To launch the console utility and follow up the user guide step by step
Start Up
1. After installing the console utility, please click the icon “MH920 Console International” to startup
2. To select the right COM port and set it

6
Configuration
。
.To select Parent (Coordinator) or Child (Router) correctly to setup
。
。 To click “Module setup” for configuration
。
To click “Connect” to start up and “Load from Module” to check the current configuration
Parent Configuration
Child Node Configuration

7
Configuration File
•
Load Configuration
Load the configuration file into Z920K device
• Save Configuration
Save the present configuration file to PC
• Load Default
Recover default setting
•
Save Default
Save the present setting as the default
Mesh Network set up
。 Make sure the following parameters of all of the Parent (coordinator) and Child node (router) to be the same for the same group.
1. PAN ID (group name)
2. Radio channel number
3. Network Name
4. Encryption key
。 Short Address for all of Child nodes ID must be different each other.

8
Communication Configuration
The bit rate means the communication speed between Parent and Child. Please keep at the high speed 115200 bps. Don’t change any
parameters on this page.
Protocol Setup
RS485 Modbus/RTU configuation
Make sure the protocol type as “Modbus (RTU)”
1. “Station number analysis” is an option if Child nodes are connected with Modbus sensors

9
2. A “Station no. list” has to be set with the sensors ID (Station number) corresponding to the short address of Child node and
“Save to module”.
For example:
。 Sensor Modbus ID1/ID2 are connected with Child node short address 0001
。 Sensor Modbus ID3/ID4/ID5 are connected with Child node short address 0002
。 Sensor Modbus ID6 is connected with Child node short address 0003
RS232 ASCII set up
RS232 (1-to-1) set up
Configuration:
1. Select “No” for “Station number analysis” on Parent device.
2. Make sure packet filtering is set at “Yes (notification type)” for Parent and Child devices.

10
RS232 (1-to-N) set up
Parent configuration:
1. The station number analysis needs to enable and setup the station no. table as the description on the page 7/8.
2. Please select “Other(ASCII)” as protocol type
3. “Start character code 1” and “Start character code 2” can be set by demand; The initial start character code1 setting is "25".
4. “Station number start position after character code” is to specify the number of bytes that follow the start position
character code.
5. “Station number store area”: Select the number of bytes (1 to 4) for the area where the station number is stored.
6. “Station number size”: Select the number of digits from the end of the station number (1 to 4)
7. “Station number type”: The format of (Decimal ASCII/Hexadecimal ASCII) can be selected for the station number.
8. “Delete the beginning of transmitted data”: While transmitting the data to the child node, can be set to delete the specified
number of bytes (0 to 15 bytes) from the beginning of the receive data by child nodes,
Questo manuale è adatto per i seguenti modelli
1
Indice

















