ABB RET620 Manuale utente

Relion® 620 series
Transformer Protection and Control
RET620
Product Guide

Contents
1. Description.....................................................................3
2. Default configurations.....................................................3
3. Protections functions......................................................9
4. Application...................................................................10
5. Supported ABB solutions.............................................11
6. Control.........................................................................12
7. Measurement...............................................................13
8. Disturbance recorder....................................................13
9. Event log......................................................................13
10. Recorded data............................................................13
11. Trip-circuit supervision.................................................13
12. Self-supervision...........................................................13
13. Access control............................................................13
14. Inputs and outputs......................................................14
15. Station communication................................................14
16. Technical data.............................................................18
17. Local HMI....................................................................48
18. Mounting methods......................................................48
19. IED case and IED plug-in unit......................................49
20. Selection and ordering data.........................................50
21. Accessories and ordering data....................................52
22. Tools...........................................................................52
23. Connection diagrams..................................................54
24. References..................................................................56
25. Functions, codes and symbols....................................57
26. Document revision history...........................................61
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any
errors that may appear in this document.
© Copyright 2013 ABB.
All rights reserved.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
Transformer Protection and Control 1MRS757846 A
RET620
Product version: 2.0
2 ABB

1. Description
RET620 is a dedicated transformer IED perfectly aligned for
the protection, control, measurement and supervision of both
power and step-up transformers, including power generator-
transformer blocks, in utility and industrial power distribution
systems. RET620 is a member of ABB’s Relion® protection
and control product family and its 620 series. The 620 series
IEDs are characterized by their functional scalability and
withdrawable-unit design.
The 620 series has been designed to unleash the full potential
of the IEC 61850 standard for communication and
interoperability of substation automation devices.
2. Default configurations
The 620 series IEDs are configured with default
configurations, which can be used as examples of the 620
series engineering with different function blocks. The default
configurations are not aimed to be used as real end-user
applications. The end-users always need to create their own
application configuration with the configuration tool. However,
the default configuration can be used as a starting point by
modifying it according to the requirements.
RET620 is available with one default configuration. The
default signal configuration can be altered by means of the
graphical signal matrix or the graphical application
functionality of the Protection and Control IED Manager
PCM600. Furthermore, the application configuration
functionality of PCM600 supports the creation of multi-layer
logic functions utilizing various logical elements including
timers and flip-flops. By combining protection functions with
logic function blocks the IED configuration can be adapted to
user specific application requirements.
Transformer Protection and Control 1MRS757846 A
RET620
Product version: 2.0 Issued: 2013-05-07
Revision: A
ABB 3

3×
REMARKS
Optional
function
No. of
instances
Alternative
function to be
defined when
ordering
OR
Io/Uo
Calculated
value
3×
10100011001100
101100101110010
1100111011010
10110110110100
1010001100110010100011001100
101100101110010
1100111011010
10110110110100
Analog interface types 1)
Current transformer
Voltage transformer
1) Conventional transformer inputs
MEASUREMENT
COMMUNICATION
Protocols:
IEC 61850-8-1
Modbus®
IEC 60870-5-103
DNP3
Interfaces:
Ethernet: TX (RJ-45), FX (LC)
Serial: Serial glass fiber (ST),
RS-485, RS-232/485
D-sub 9, IRIG-B
Redundant protocols:
HSR
PRP
RSTP
ALSO AVAILABLE
- 16× prog. push-buttons on LHMI
- Disturbance and fault recorders
- Event log and recorded data
- High-Speed Output module (optional)
- IED self-supervision
- Local/Remote push-button on LHMI
- Sequence event recorder
- User management
- Web HMI
OR
AND
CONTROL AND INDICATION 1)
LOCAL HMI
Object Ctrl 2) Ind 3)
CB
DC
ES
1) Check availability of binary inputs/outputs
from technical documentation
2) Control and indication function for
primary object
3) Status indication function for
primary object
2-
4 4
2 2
CONDITION MONITORING
AND SUPERVISION
TRANSFORMER PROTECTION AND CONTROL IED
PROTECTION
EXAMPLE
CONFIGURATION
Version 2.0
RET620
SYNC
25
Master trip
Lockout relay
94/86
Master trip
Lockout relay
94/86
3×
Uo>
59G
COLTC
90V
I2>
46
3I>>>
50P/51P
3I>/Io>BF
51BF/51NBF
3I<
37F
Io>>
51N-2
Io>
51N-1
dIoLo>
87NL
3I>
51P-1
3I>>
51P-2
3I>>>
50P/51P
3I>/Io>BF
51BF/51NBF
Io>>
51N-2
I2>
46
3Ith>T
49T
3I<
37F
Io>
51N-1
3I (HV)
3I (LV)
UL1UL2UL3
UL1UL2UL3
U0
N
FUSEF
60
MCS 3I
MCS 3I
MCS 3I
MCS 3I
MCS 3I, I2
MCS 3I, I2
TPOSM
84M
6×
UFLS/R
81LSH
U12
U12b
U12
8xRTD
3xmA
3I>
51P-1
3×
ARC
50L/50NL
dIoLo>
87NL
3I>>
51P-2
3I2f>
68
3I>>→
67-2
3I>→
67-1
Io>>→
67N-2
2×
Io>→
67N-1
dIoHi>
87NH
dIoHi>
87NH
3dI>T
87T
2×
U1<
47U+
2×
U2>
47O-
3×
f>/f<,
df/dt
81
Io (HV)
Io (LV)
Io
- HV: I, U, Io, Uo
- LV: I, Io
- P, Q, E, pf, f
- Symmetrical components
- Limit value supervision
- Load profile
8
6
R
L
ClearESC
I
O
U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A
A
Io
2×
TCS
TCM
2×
CBCM
CBCM
12×
MAP12
MAP12
3×
3U<
27
2×
U/f>
24
3×
3U>
59
GUID-BFA69E71-CDBB-4333-A91F-001F2A8A1E6B V1 EN
Figure 1. Functionality overview
Transformer Protection and Control 1MRS757846 A
RET620
Product version: 2.0
4 ABB

Table 1. Supported functions
Functionality CTs & VTs
Protection
Three-phase non-directional overcurrent protection, low stage, instance 1 ●1)
Three-phase non-directional overcurrent protection, low stage, instance 2 ●2)
Three-phase non-directional overcurrent protection, high stage, instance 1 ●1)
Three-phase non-directional overcurrent protection, high stage, instance 2 ●2)
Three-phase non-directional overcurrent protection, instantaneous stage, instance 1 ●1)
Three-phase non-directional overcurrent protection, instantaneous stage, instance 2 ●2)
Three-phase directional overcurrent protection, low stage, instance 1 ●1)
Three-phase directional overcurrent protection, high stage, instance 1 ●1)
Non-directional earth-fault protection, low stage, instance 1 ●3)
Non-directional earth-fault protection, low stage, instance 2 ●4)
Non-directional earth-fault protection, high stage, instance 1 ●3)
Non-directional earth-fault protection, high stage, instance 2 ●4)
Directional earth-fault protection, low stage, instance 1 ●3)
Directional earth-fault protection, low stage, instance 2 ●3)
Directional earth-fault protection, high stage, instance 1 ●3)
Negative-sequence overcurrent protection, instance 1 ●1)
Negative-sequence overcurrent protection, instance 2 ●2)
Residual overvoltage protection, instance 1 ●1)
Residual overvoltage protection, instance 2 ●1)
Residual overvoltage protection, instance 3 ●1)
Three-phase undervoltage protection, instance 1 ●1)
Three-phase undervoltage protection, instance 2 ●1)
Three-phase undervoltage protection, instance 3 ●1)
Three-phase overvoltage protection, instance 1 ●1)
Three-phase overvoltage protection, instance 2 ●1)
Three-phase overvoltage protection, instance 3 ●1)
Positive-sequence undervoltage protection, instance 1 ●1)
Positive-sequence undervoltage protection, instance 2 ●1)
Negative-sequence overvoltage protection, instance 1 ●1)
Negative-sequence overvoltage protection, instance 2 ●1)
Frequency protection, instance 1 ●1)
Frequency protection, instance 2 ●1)
Frequency protection, instance 3 ●1)
Voltage per hertz protection, instance 1 ●1)
Voltage per hertz protection, instance 2 ●1)
Transformer Protection and Control 1MRS757846 A
RET620
Product version: 2.0
ABB 5

Table 1. Supported functions, continued
Functionality CTs & VTs
Three-phase thermal overload protection for power transformers, two time constants ●1)
Loss of phase (undercurrent), instance 1 ●1)
Loss of phase (undercurrent), instance 2 ●2)
Stabilized and instantaneous differential protection for 2-winding transformers ●
Numerical stabilized low impedance restricted earth-fault protection, instance 1 ●1)
Numerical stabilized low impedance restricted earth-fault protection, instance 2 ●2)
High impedance based restricted earth-fault protection, instance 1 ●1)
High impedance based restricted earth-fault protection, instance 2 ●2)
Circuit breaker failure protection, instance 1 ●1)
Circuit breaker failure protection, instance 2 ●2)
Three-phase inrush detector ●1)
Master trip, instance 1 ●
Master trip, instance 2 ●
Arc protection, instance 1 ○5)
Arc protection, instance 2 ○5)
Arc protection, instance 3 ○5)
Multipurpose analog protection, instance 1 ●
Multipurpose analog protection, instance 2 ●
Multipurpose analog protection, instance 3 ●
Multipurpose analog protection, instance 4 ●
Multipurpose analog protection, instance 5 ●
Multipurpose analog protection, instance 6 ●
Multipurpose analog protection, instance 7 ●
Multipurpose analog protection, instance 8 ●
Multipurpose analog protection, instance 9 ●
Multipurpose analog protection, instance 10 ●
Multipurpose analog protection, instance 11 ●
Multipurpose analog protection, instance 12 ●
Control
Circuit-breaker control, instance 1 ●1)
Circuit-breaker control, instance 2 ●2)
Disconnector control, instance 1 ●1)
Disconnector control, instance 2 ●1)
Earthing switch control, instance 1 ●1)
Disconnector control, instance 3 ●2)
Disconnector control, instance 4 ●2)
Earthing switch control, instance 2 ●2)
Transformer Protection and Control 1MRS757846 A
RET620
Product version: 2.0
6 ABB

Table 1. Supported functions, continued
Functionality CTs & VTs
Disconnector position indication, instance 1 ●1)
Disconnector position indication, instance 2 ●1)
Earthing switch position indication, instance 1 ●1)
Disconnector position indication, instance 3 ●2)
Disconnector position indication, instance 4 ●2)
Earthing switch position indication, instance 2 ●2)
Synchronism and energizing check ●1)
Tap changer position indication ●
Tap changer control with voltage regulator ○2)
Load shedding and restoration, instance 1 ●1)
Load shedding and restoration, instance 2 ●1)
Load shedding and restoration, instance 3 ●1)
Load shedding and restoration, instance 4 ●1)
Load shedding and restoration, instance 5 ●1)
Load shedding and restoration, instance 6 ●1)
Condition monitoring
Circuit-breaker condition monitoring, instance 1 ●1)
Circuit-breaker condition monitoring, instance 2 ●2)
Trip circuit supervision, instance 1 ●1)
Trip circuit supervision, instance 2 ●2)
Current circuit supervision, instance 1 ●1)
Current circuit supervision, instance 2 ●2)
Advanced current circuit supervision for transformers ●
Fuse failure supervision ●1)
Measurement
Three-phase current measurement, instance 1 ●1)
Three-phase current measurement, instance 2 ●2)
Sequence current measurement, instance 1 ●1)
Sequence current measurement, instance 2 ●2)
Residual current measurement, instance 1 ●1)
Residual current measurement, instance 2 ●2)
Three-phase voltage measurement ●1)
Residual voltage measurement ●1)
Sequence voltage measurement ●1)
Three-phase power and energy measurement ●1)
Frequency measurement ●1)
Transformer Protection and Control 1MRS757846 A
RET620
Product version: 2.0
ABB 7

Table 1. Supported functions, continued
Functionality CTs & VTs
Other
Minimum pulse timer (2 pcs), instance 1 ●
Minimum pulse timer (2 pcs), instance 2 ●
Minimum pulse timer (2 pcs), instance 3 ●
Minimum pulse timer (2 pcs), instance 4 ●
Minimum pulse timer (2 pcs, second resolution), instance 1 ●
Minimum pulse timer (2 pcs, second resolution), instance 2 ●
Minimum pulse timer (2 pcs, minute resolution), instance 1 ●
Minimum pulse timer (2 pcs, minute resolution), instance 2 ●
Pulse timer (8 pcs), instance 1 ●
Pulse timer (8 pcs), instance 2 ●
Time delay off (8 pcs), instance 1 ●
Time delay off (8 pcs), instance 2 ●
Time delay off (8 pcs), instance 3 ●
Time delay off (8 pcs), instance 4 ●
Time delay on (8 pcs), instance 1 ●
Time delay on (8 pcs), instance 2 ●
Time delay on (8 pcs), instance 3 ●
Time delay on (8 pcs), instance 4 ●
Set reset (8 pcs), instance 1 ●
Set reset (8 pcs), instance 2 ●
Set reset (8 pcs), instance 3 ●
Set reset (8 pcs), instance 4 ●
Move (8 pcs), instance 1 ●
Move (8 pcs), instance 2 ●
Move (8 pcs), instance 3 ●
Move (8 pcs), instance 4 ●
Generic control points, instance 1 ●
Generic control points, instance 2 ●
Generic control points, instance 3 ●
Remote generic control points ●
Local generic control points ●
Generic up-down counters, instance 1 ●
Generic up-down counters, instance 2 ●
Generic up-down counters, instance 3 ●
Generic up-down counters, instance 4 ●
Generic up-down counters, instance 5 ●
Generic up-down counters, instance 6 ●
Transformer Protection and Control 1MRS757846 A
RET620
Product version: 2.0
8 ABB

Table 1. Supported functions, continued
Functionality CTs & VTs
Generic up-down counters, instance 7 ●
Generic up-down counters, instance 8 ●
Generic up-down counters, instance 9 ●
Generic up-down counters, instance 10 ●
Generic up-down counters, instance 11 ●
Generic up-down counters, instance 12 ●
Programmable buttons (16 buttons) ●
Logging functions
Disturbance recorder ●
Fault recorder ●
Sequence event recorder ●
Load profile ●
● = Included,○ = Optional at the time of the order
1) The function is to be used on high voltage winding side in the application
2) The function is to be used on low voltage winding side in the application
3) The function is to be used on high voltage winding side in the application,and uses calculated Io when HREF and varistor connection used
4) The function is to be used on low voltage winding side in the applicationand,and uses calculated Io when HREF and varistor connection used
5) Calculated Io is used for the residual current criteria
3. Protections functions
The IED features a three-phase, multi-slope stabilized (biased)
stage transformer differential protection and an instantaneous
stage to provide fast and selective protection for phase-to-
phase short circuit, winding interturn fault and bushing flash-
over protection. Besides the second harmonic restraint, an
advanced waveform-based blocking algorithm ensures
stability at transformer energization and the fifth harmonic
restraint function ensures good protection stability at
moderate overexcitation of power transformers. The restricted
earth-fault protection (REF) completes the overall differential
protection providing detection of even single phase-to-earth
faults close to the neutral earthing point of the transformer.
Either the conventional high-impedance scheme or the
numerical low-impedance scheme can be selected for
protection of the transformer windings. When the low-
impedance REF protection is used, neither stabilizing
resistors nor varistors are needed and, as a further benefit,
the transforming ratio of the neutral earthing CTs can differ
from that of the phase current transformers. Due to its unit
protection character and absolute selectivity, REF does not
need to be time-graded with other protection schemes, and
therefore a high-speed fault clearance can be achieved.
The IED also incorporates a thermal overload protection
function that supervises the thermal stress of the transformer
windings to prevent the premature aging of the insulation of
the windings. Multiple stages of short circuit, phase-
overcurrent, negative-phase-sequence and earth-fault backup
protection are separately available for both sides of the power
transformer. An earth-fault protection based on the measured
or calculated residual voltage is also available. The IED also
features three-phase overvoltage protection, three-phase
undervoltage protection and residual overvoltage protection.
Furthermore, the IED also offers circuit breaker failure
protection.
Enhanced with optional hardware and software, the IED also
features three light detection point-to-point lens sensors for
arc fault protection of the circuit breaker, busbar and cable
compartment of metal-enclosed indoor switchgear.
The arc fault protection sensor interface is available on the
optional communication module. Fast tripping increases staff
safety and security and limits material damage in an arc fault
situation. Optional high speed outputs help to minimize the
arc impacts.
Transformer Protection and Control 1MRS757846 A
RET620
Product version: 2.0
ABB 9

4. Application
RET620 has been designed to be the main protection for two-
winding power transformers and power generator-transformer
blocks. RET620 also includes an optional voltage regulation
function.
RET620 can be used with either single- or double-busbar
configurations with either one or two breakers, and with
numerous switching device configurations. It supports a
substantial number of both manually and motor-operated
disconnectors and earthing switches, and it is capable of
running large configurations. The number of controllable
devices depends on the number of inputs and outputs left
free from other application needs. The number of available I/
Os can be increased with the RIO600 Remote I/O device.
RET620 offers extensive possibilities to tailor the
configurations to end application requirements. The tool suite
for all Relion IEDs is Protection and control IED manager
PCM600, which contains all the necessary tools for
configuring the device, including functionality,
parameterization, the HMI and communication.
RET620 provides both transformer protection and control and
voltage regulator control at the same time. Voltage regulation
capability is targeted for automatic and manual voltage
regulation of power transformers equipped with a motor-
driven on-load tap changer. An automatic voltage regulation
can be applied both with a single transformer as well as with
up to four transformers running in parallel. The IED also
supports both traditional resistor connection-based and
numerically calculated high-impedance earth-fault protection.
To further improve the arc fault protection and minimize the
effects of an arc fault, the 620 series IEDs ordered with the
arc fault protection option can be equipped with an I/O card
featuring high-speed outputs.
Io HV
Io LV
3I HV
3I LV
3U
U12
U12b
Uo
RTD
RET620
Example conf.
ANSI IEC
N
25
50L/50NL
50P/51P
51P/51N
67/67N
84M
87T
90V
MAP
49T
87NH
87NL
87NH
87NL
SYNC
ARC
3I>>>
3I/Io
3I→/Io→
TPOSM
3dI>T
COLTC
MAP
3Ith>T
dIoHi>
dIoLo>
dIoHi>
dIoLo>
HV
side
LV
side
GUID-A758C254-7907-4965-9389-113BCBD77B75 V1 EN
Figure 2. The protection of HV/MV, or an MV/MV transformer with low-impedance EF on both sides of trafo
Transformer Protection and Control 1MRS757846 A
RET620
Product version: 2.0
10 ABB
Indice
Altri manuali ABB Altro

ABB
ABB REG650 ANSI Manuale utente

ABB
ABB REF 542plus Manuale del prodotto

ABB
ABB REC650 ANSI Manuale utente

ABB
ABB VD4 Series Manuale utente

ABB
ABB EP010 Guida rapida

ABB
ABB REX 521 Manuale per l'uso e la cura

ABB
ABB SACE Tmax XT UL Manuale utente

ABB
ABB VD4 12 Guida rapida

ABB
ABB MREL-01 Manuale utente

ABB
ABB SACE Tmax XT2 Manuale utente

ABB
ABB RELION REF610 Manuale del prodotto

ABB
ABB REX 521 Manuale per l'uso e la cura

ABB
ABB SPAA 341 C /E351 Manuale utente

ABB
ABB SACE Emax E1.2 Guida rapida

ABB
ABB REM 610 Manuale utente

ABB
ABB Tmax T7 Manuale utente

ABB
ABB Relion RER615 Manuale utente

ABB
ABB REM 610 Manuale utente

ABB
ABB REM 610 Manuale del prodotto

ABB
ABB REM 610 Manuale utente