The DNP31 devcie allows the connection of the Universal Motor
Controller UMC100.3 to a DeviceNet network.
DNP31.0
DeviceNet Interface
Technical description

- 2 -
DNP31.0 Data sheet Issue: 09.2015
Please note the following
Target group
This description is intended for the use of trained specialists in electrical installation and control and automation engi-
neering, who are familiar with the applicable national standards.
Safety requirements
The responsible staff must ensure that the application or use of the products described satisfy all the requirements for
safety, including all the relevant laws, regulations, guidelines and standards.
Using this Handbook
Symbols
This technical document contains sentinels to point the reader to important information, potential risks and precaution
information. The following symbols are used:
Sign to indicate a potential dangerous situation that can cause damage of the
connected devices or the environment.
Sign to indicate important information and conditions.
Sign that indicates a potential dangerous situation that can cause human injuries.
Terms and Abbreviations
SMK Single Mounting Kit for the fieldbus interfaces
UMC100.3 Universal Motor Controller
Related Documents
Technical Documentation Document No.

- 3 - Data sheet DNP31.0
Issue: 09.2015
Content
Overview...................................................................................................................................................5
Mechanical Installation.............................................................................................................................6
Mounting the DNP31 on the UMC100.3.............................................................................................6
Mounting the DNP31 remotely from the UMC100.3...........................................................................7
Demounting the DNP31......................................................................................................................8
Electrical installation.................................................................................................................................9
DeviceNet Connection........................................................................................................................9
DeviceNet line with DNP31 directly connected to UMC100.3 in a drawout system........................10
DeviceNet line with DNP31 mounted outside a drawer using single mounting kit (SMK3.0)...........11
Diagnosis................................................................................................................................................12
Diagnosis and behaviour in case of an error ....................................................................................12
Checklist ...........................................................................................................................................12
DeviceNet information about the properties of the DNP31....................................................................13
General information ..........................................................................................................................13
Class Code 001 (0x01): Identity Object ............................................................................................14
Class Code 002 (0x02): Message Router Object .............................................................................14
Class Code 004 (0x04): Assembly Object ........................................................................................15
Class Code 005 (0x05): Connection Object .....................................................................................16
Class Code 043 (0x2B): Acknowledge Handler Object ....................................................................19
Class Code 100 (0x64): ABB Discrete Input Object .........................................................................19
Class Code 101 (0x65): ABB Discrete Output Object ......................................................................20
Class Code 102 (0x66): ABB Analog Input Object ...........................................................................20
Class Code 103 (0x67): ABB Analog Output Object ........................................................................21
Class Code 105 (0x69): ABB Parameter Object...............................................................................21
Class Code 112 (0x70): ABB Parameter Modular Object.................................................................22
Class Code 118 (0x76): ABB Any Data Class...................................................................................22
Class Code 128 (0x80): ABB Query Object......................................................................................22
Technical data ........................................................................................................................................23
Dimensions.............................................................................................................................................24
Connection Cables.................................................................................................................................24

- 4 -
DNP31.0 Data sheet Issue: 09.2015
Document History

- 5 - Data sheet DNP31.0
Issue: 09.2015
Overview
This chapter contains a short description of the DeviceNet standard and the DNP31 DeviceNet Interface module.
DeviceNet Standard
The DeviceNet network has a linear bus topology. Terminating resistors are required on each end of the trunk line. Drop lines
as long as 6 metres (20 feet) each are permitted, allowing one or more nodes to be attached. DeviceNet allows branching
structures only on drop lines.
The DeviceNet Communication Interface
The DNP31 communication interface is an optional device for the UMC100.3 which enables the connection of the
UMC100.3 to a DeviceNet system. The UMC100.3 is considered as a slave in the DeviceNet network.
• Use UMC100.3 to set bus address and baud rate (or autobaud) of the DeviceNet communication. Once the address
is set, it is stored in the DNP31, even in case of supply voltage breakdown.
Through the DNP31 DeviceNet communication interface it is possible to:
• give control commands to the drive (Start, Stop etc.)
• read status information and actual values from the drive
• read and write UMC100.3 parameter values
• reset a UMC100.3 trip.
The DNP31 acts as a Class 2 only slave with predefined master-slave connection set services. These include the
Explicit Messaging, the Poll-Response service and the Change of State/Cyclic service. The DeviceNet commands and
services supported by the DNP31 DeviceNet communication interface are discussed in chapter Communication.
NS MS
DNP31
X3:
DeviceNet
Connector
Dual colour
LEDs for
status display
X3:
DeviceNet Connector
From Top From Side
X1: Interface to
UMC100.3

- 6 -
DNP31.0 Data sheet Issue: 09.2015
Power
DNP31
NS MS
Mechanical Installation
The DeviceNet adapter module DNP31 can be mounted either on the UMC100.3 itself or separately from the UMC100.3 using
the single mounting kit (SMK3.0).
Mounting the DNP31 on the UMC100.3
When the module is installed directly on the UMC100.3 the UMC100.3 with DNP31 acts like a device with integrated DeviceNet
communication. No additional accessories are needed.
Move down DNP31 until
snapped-in to fix DNP31
on UMC100.3
Image shows UMC100.3 DC

- 7 - Data sheet DNP31.0
Issue: 09.2015
(1)
(2)
(2)
(1)
Mounting the DNP31 remotely from the UMC100.3
When the communication interface is installed remotely from the UMC100.3 - e. g. in the cable chamber of a motor control
center - the DNP31 must be separately supplied. This makes it possible to keep the DNP31 online even in the case when the
drawer is removed. Ready made cables are available. But it is also possible to use own cables.
For more details see section „Using DNP31 in a Drawout System“.
Mounting the Single Mounting Kit
The single mounting kit (SMK3.0) can be either mounted on a DIN rail hat or fixed with screws on a fitting panel.
Mounting the DNP31 on the Single Mounting Kit
Step 1:
Plug in the communication
connectors.
Step 3:
Move down the DNP31 until
snapped in
Step 2:
Move down the DNP31
Move down
Step 4:
Fix cable with cable ties
Assembly Disassembly

- 8 -
DNP31.0 Data sheet Issue: 09.2015
DNP31
NS MS
Demounting the DNP31
Follow the shown procedure for demounting the DNP31 from UMC100.3 or SMK.3.
For demounting slightly rotate
screw driver and move the DNP31
upwards to loosen snap-in
connection.

- 9 - Data sheet DNP31.0
Issue: 09.2015
Electrical installation
DeviceNet Connection
Connect DeviceNet to X3.
General cabling instructions
– Arrange the bus cables as far away from the motor cables as possible.
– Avoid parallel runs
– Use bushings at cable entries
Bus termination
Bus termination is required to prevent signal reflections from the bus cable ends. The DNP31 DeviceNet interface module is not
equipped with internal bus termination
The DeviceNet network should be terminated at both ends of the trunk cable with a 121 ohm,
¼ W, 1% Metal Film resistor. Connect this resistor between the two signal wires (CAN_H,
CAN_L) on the DeviceNet cable.
Setting the Communication Parameters
The DeviceNet interface module does not provide means to adjust the DeviceNet slave address and baud rate (incl. autobaud).
The DeviceNet slave address, baud rate and communication timeout can be set in the UMC100.3 and are copied to the
DeviceNet interface module during initial connection between UMC and DNP31. When changing communication parameters later
on perform a power cycle. The baudrate is set to 'autobaud' by default.
Network and Baudrates
The maximum length of trunk cable depends on the data rate and on the type of the cable used.
• DeviceNet Cables: YR-29790 (Thick DeviceNet Cable) or YR-29832 (Thin DeviceNet Cable)
• Maximum Bus Length: 1200 m
• Topology: Multi-drop
• Serial Communication Type: Asynchronous, half Duplex
• Transfer Rate: 125, 250 or 500 kbit/s

- 10 -
DNP31.0 Data sheet Issue: 09.2015
DeviceNet line with DNP31 directly connected to UMC100.3 in a drawout system
The following figure shows a simplified diagram on how to connect the UMC100.3 to a DeviceNet network. Required grounding
of the DeviceNet cable is not shown in this figure.
UMC100.3 and DNP31
mounted in drawer
Termination active
Ground wire and cable shield should be connected to prevent common mode voltage
between the network devices from drifting outside the allowable limits.
DeviceNet
Master
DeviceNet Cable
DeviceNet Cable
Indice
Altri manuali ABB Apparecchiature di registrazione

ABB
ABB IP Touch 7 Manuale utente

ABB
ABB FEN-11 Manuale utente

ABB
ABB FEN-01 Manuale utente

ABB
ABB FEN-01 Manuale utente

ABB
ABB i-bus KNX IPS/S 3.5.1 Manuale utente

ABB
ABB FEN-31 Manuale utente

ABB
ABB FEN-21 Manuale utente

ABB
ABB IPS/S 2.1 Manuale utente

ABB
ABB FEN-21 Manuale utente

ABB
ABB FEN-31 Manuale utente
Manuali Apparecchiature di registrazione popolari di altre marche

Strymon
Strymon NIGHTSKY Manuale utente

Mitsubishi Electric
Mitsubishi Electric 16CH DIGITAL RECORDER DX-TL5000U Manuale utente

Tews Technologies
Tews Technologies TPMC465 Manuale utente

Honeywell
Honeywell Excel 50 Manuale utente

SeaLevel
SeaLevel COMM+8.LPCI Manuale utente

Arturia
Arturia AUDIOFUSE STUDIO Manuale utente