ABB RELION RET670 Manuale utente

Relion® 670 series
Transformer protection RET670 9-2 LE
Customized
Product Guide

Contents
1. Application.....................................................................3
2. Available functions..........................................................8
3. Differential protection....................................................11
4. Impedance protection..................................................12
5. Current protection........................................................13
6. Voltage protection........................................................14
7. Secondary system supervision.....................................15
8. Control.........................................................................15
9. Logic............................................................................16
10. Monitoring...................................................................16
11. Metering......................................................................17
12. Basic IED functions.....................................................17
13. Human machine interface............................................18
14. Station communication ...............................................18
15. Hardware description..................................................18
16. Connection diagrams..................................................21
17. Technical data.............................................................26
18. Ordering......................................................................59
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any
errors that may appear in this document.
© Copyright 2012 ABB.
All rights reserved.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
Transformer protection RET670 9-2 LE
1MRK504119-BEN B
Customized
Product version: 1.2
2 ABB

1. Application
A very fast differential protection function with settable CT
ratio matching and vector group compensation makes this
IED the ideal solution even for the most demanding
applications. Since RET670 has very low requirements on the
main CTs, no interposing CTs are required.It is suitable for
differential applications with multi-breaker arrangements with
up to six restraint CT inputs. The differential protection
function is provided with 2nd harmonic and wave-block
restraint features to avoid tripping for magnetizing inrush
current, and 5th harmonic restraint to avoid tripping for
overexcitation.
The differential function offers a high sensitivity for low-level
internal faults. The unique and innovative sensitive differential
protection feature of the RET670 provides the best possible
coverage for winding internal turn-to-turn faults, based on the
theory of symmetrical components .
A low impedance restricted earth-fault protection function is
available as a complimentary sensitive and fast main
protection against winding earth faults. This function includes
a directional zero-sequence current criterion for additional
security.
Tripping from pressure relief/Buchholz and temperature
devices can be done through the transformer IED where
pulsing, lock-out contact output and so on, is performed. The
binary inputs are heavily stabilized against disturbance to
prevent incorrect operations at for example dc system
capacitive discharges or DC earth faults.
The binary inputs are heavily stabilized against disturbances
to prevent incorrect operations during for example during DC
system capacitive discharges or DC earth faults.
Distance protection functionality for phase-to-phase and/or
phase-to-earth faults is available as back-up protection for
faults within the transformer and in the connected power
system.
Versatile phase, earth, positive and zero sequence
overcurrent functions, which can optionally be made
directional and/or voltage controlled, provide further
alternative backup protection. Thermal overload with two time-
constants, volts per hertz, over/under voltage are also
available.
A built-in disturbance and event recorder provides valuable
data to the user about status and operation for post-fault
disturbance analysis.
Breaker failure protection allows high speed back-up tripping
of surrounding breakers.
The transformer IED provided with Synchrocheck function to
allow integration of the main and/or a local back-up control.
RET670 can be used in applications with the IEC
61850-9-2LE process bus with up to two Merging Units (MU).
Each MU has eight analogue channels, normally four current
and four voltages. Conventional and Merging Unit channels
can be mixed freely in your application.
The advanced logic capability, where user logic is prepared
with a graphical tool, allows special applications such as
automatic opening of disconnectors in multi-breaker
arrangements, closing of breaker rings, load transfer logic
and so on. The graphical configuration tool ensures simple
and fast testing and commissioning.
Transformer protection RET670 9-2 LE
1MRK504119-BEN B
Customized
Product version: 1.2 Issued: February 2015
Revision: B
ABB 3

IN>
4
4
3U>
2
2
3U<
2
2
I->O
51/67
51N/67N
59
27
94/86
87T
3Id/I>
IdN/I>
87N
IdN/I>
87N
3I>
50BF
3I>
4
4
IN>
4
4
51N/67N
SC/VC
25
51/67
3I>
50BF
3I>
4
4
I->O
94/86
TRIP BUSBAR
TRIP BUSBAR
CB2
TRIP CB2
CB1
TRIP CB1
IEC08000205-2-en.vsd
Merging
unit
MU1
1-ph 1-ph
1-ph
IEC08000205 V2 EN
Figure 1. A typical protection application for a two winding transformer in single breaker arrangements is shown on the figure. The system
earthing principle and connection group will vary which gives different detailed arrangements for each application. Breaker failure
function is here provided for secondary side breaker. Merging unit/s can be used for voltage and or current as required and freely
mixed with conventional analogue inputs.
Transformer protection RET670 9-2 LE
1MRK504119-BEN B
Customized
Product version: 1.2
4 ABB

IN>
4
4
3U>
2
2
3U<
2
2
I->O
51/67
51N/67N
59
27
94/86
87T
3Id/I>
IdN/I>
87N
IdN/I>
87N
3I>
4
4
IN>
4
4
51N/67N
SC/VC
25
51/67
3I>
50BF
3I>
4
4
I->O
94/86
TRIP BUSBAR
&CB1/2
CB3
TRIP CB3
CB1
TRIP CB1
CB2
S
I->O
94/86
TRIP CB2
IEC08000203-2-en.vsd
Merging
unit
Merging
unit
IEC08000203 V2 EN
Figure 2. A typical protection application for a two winding transformer in multi breaker arrangements is shown on the figure. The system
earthing principle and connection group will vary which gives different detailed arrangements for each application. Breaker failure
function is here provided for secondary side breaker. Merging unit/s can be used for voltage and or current as required and freely
mixed with conventional analogue inputs.
Transformer protection RET670 9-2 LE
1MRK504119-BEN B
Customized
Product version: 1.2
ABB 5

IN>
4
4
3U>
2
2
3U<
2
2
I->O
51/67
51N/67N
59
27
94/86
87T
3Id/I>
IdN/I>
87N
IdN/I>
87N
3I>
4
4
IN>
4
4
51N/67N
SC/
VC
25
51/67
3I>
50BF
3I>
4
4
I->O
94/86
TRIP BUSBAR
&CB1/2/3
CB2
TRIP CB2
CB1
TRIP CB1
CB3
3I>
4
4
3I>
50BF
TRIP BUSBAR
&CB1/2
UN>
2
2
59N
t2
TRIP
I->O
94/86
IEC08000206-2-en.vsd
Merging
unit
IEC08000206 V2 EN
Figure 3. A typical protection application for a three winding transformer in single breaker arrangements is shown on the figure. The system
earthing principle and connection group will vary which gives different detailed arrangements for each application. Breaker failure
function is here provided for secondary and tertiary side breaker. Merging unit/s can be used for voltage and or current as
required and freely mixed with conventional analogue inputs.
Transformer protection RET670 9-2 LE
1MRK504119-BEN B
Customized
Product version: 1.2
6 ABB

IN>
4
4
3U>
2
2
3U<
2
2
I->O
51/67
51N/67N
59
27
94/86
87T
3Id/I>
IdN/I>
87N
IdN/I>
87N
3I>
4
4
IN>
4
4
51N/67N
SC/VC
25
51/67
3I>
50BF
3I>
4
4
I->O
94/86
TRIP BUSBAR
&CB1/2/4
CB3
TRIP CB3
CB1
TRIP CB1
CB2
S
I->O
94/86
TRIP CB2
CB4
3I>
4
4
3I>
50BF
TRIP BUSBAR
&CB1/2/3
TRIP
UN>
2
2
59N
t2
I->O
94/86
IEC08000204-2-en.vsd
Merging
unit MU2
Merging
unit
MU1
IEC08000204 V2 EN
Figure 4. A typical protection application for a three winding transformer in multi breaker arrangements is shown on the figure. The system
earthing principle and connection group will vary which gives different detailed arrangements for each application. Breaker failure
function is here provided for secondary and tertiary side breaker. Merging unit/s can be used for voltage and or current as
required and freely mixed with conventional analogue inputs.
Transformer protection RET670 9-2 LE
1MRK504119-BEN B
Customized
Product version: 1.2
ABB 7

2. Available functions
Main protection functions
2 = number of basic instances
IEC 61850 ANSI Function description Transformer
RET670 V1
RET670 V2
Differential protection
T2WPDIF 87T Transformer differential protection, two winding 1
T3WPDIF 87T Transformer differential protection, three winding 1
REFPDIF 87N Restricted earth fault protection, low impedance 2
Impedance protection
ZMCPDIS,
ZMCAPDIS
21 Distance characteristic for series compensated lines 4
ZDSRDIR 21D Directional impedance quadrilateral, including series compensation 2
FDPSPDIS 21 Phase selection, quadrilateral characteristic with fixed angle 2
Back-up protection functions
IEC 61850 ANSI Function description Transformer
RET670 V1
RET670 V2
Current protection
PHPIOC 50 Instantaneous phase overcurrent protection 1
OC4PTOC 51_67 Four step phase overcurrent protection 2 1
EFPIOC 50N Instantaneous residual overcurrent protection 1
EF4PTOC 51N_67
N
Four step residual overcurrent protection 2 1
TRPTTR 49 Thermal overload protection, two time constant 1 1
CCRBRF 50BF Breaker failure protection 1 1
BRCPTOC 46 Broken conductor check 1 1
Voltage protection
UV2PTUV 27 Two step undervoltage protection 1
OV2PTOV 59 Two step overvoltage protection 1
ROV2PTOV 59N Two step residual overvoltage protection 1
OEXPVPH 24 Overexcitation protection 1 1
LOVPTUV 27 Loss of voltage check 1 1
Transformer protection RET670 9-2 LE
1MRK504119-BEN B
Customized
Product version: 1.2
8 ABB

Control and monitoring functions
IEC 61850 ANSI Function description Transformer
RET670 V1
RET670 V2
Control
SESRSYN 25 Synchrocheck, energizing check and synchronizing 1
QCBAY Apparatus control 1 1
LOCREM Handling of LRswitch positions 1 1
LOCREMCTR
L
LHMI control of PSTO 1 1
SLGGIO Logic rotating switch for function selection and LHMI presentation 15 15
VSGGIO Selector mini switch 20 20
DPGGIO IEC61850 generic communication I/O functions 16 16
SPC8GGIO Single pole generic control 8 signals 5 5
AutomationBits AutomationBits, command function for DNP3.0 3 3
SingleComma
nd16Signals
Single command, 16 signals 4 4
VCTRSend Horizonal communication via GOOSE for VCTR 1 1
VCTR
Receive
Horizontal communication via GOOSE for VCTR 7 7
Secondary system supervision
SDDRFUF Fuse failure supervision 2
Logic
SMPPTRC 94 Tripping logic 5 5
TMAGGIO Trip matrix logic 12 12
Configuration logic blocks 40-280 40-280
FixedSignals Fixed signal function block 1 1
B16I Boolean 16 to Integer conversion 16 16
B16IFCVI Boolean 16 to Integer conversion with Logic Node representation 16 16
IB16 Integer to Boolean 16 conversion 16 16
IB16FCVB Integer to Boolean 16 conversion with Logic Node representation 16 16
Monitoring
CVMMXN Measurements 6 6
EVENT Event function 20 20
DRPRDRE Disturbance report 1 1
SPGGIO IEC61850 generic communication I/O functions 64 64
SP16GGIO IEC61850 generic communication I/O functions 16 inputs 16 16
MVGGIO IEC61850 generic communication I/O functions 24 24
Transformer protection RET670 9-2 LE
1MRK504119-BEN B
Customized
Product version: 1.2
ABB 9

IEC 61850 ANSI Function description Transformer
RET670 V1
RET670 V2
BSStatReport Logical signal status report 3 3
RANGE_XP Measured value expander block 66 66
Metering
PCGGIO Pulse-counter logic 16 16
ETPMMTR Function for energy calculation and demand handling 6 6
Designed to communicate
IEC 61850 ANSI Function description Transformer
RET670 V1
RET670 V2
Station communication
SPA communication protocol 1 1
LON communication protocol 1 1
IEC60870-5-103 communication protocol 20/1 20/1
Operation selection between SPA and IEC60870-5-103 for SLM 1 1
DNP3.0 for TCP/IP and EIA-485 communication protocol 1 1
DNP3.0 fault records for TCP/IP and EIA-485 communication protocol 1 1
Parameter setting function for IEC61850 1 1
IntlReceive Horizontal communication via GOOSE for interlocking 59 59
Goose binary receive 10 10
Multiple command and transmit 60/10 60/10
Ethernet configuration of links 1 1
Process bus communication IEC61850-9-2LE 2 2
Remote communication
Binary signal transfer receive/transmit 6/36 6/36
Transmission of analog data from LDCM 1 1
Receive binary status from remote LDCM 6/3/3 6/3/3
Transformer protection RET670 9-2 LE
1MRK504119-BEN B
Customized
Product version: 1.2
10 ABB
Altri manuali per RELION RET670
11
Indice
Altri manuali ABB Trasformatore

ABB
ABB FLM 1000 Manuale utente

ABB
ABB TPU Series Manuale elenco delle parti

ABB
ABB GSB 800 Manuale del prodotto

ABB
ABB ILUJ000004-BLE Manuale utente

ABB
ABB ELK Series Manuale elenco delle parti

ABB
ABB Relion 615 series Manuale utente

ABB
ABB TDO 6 Manuale elenco delle parti

ABB
ABB VT Guard Pro Manuale elenco delle parti

ABB
ABB ELK-CT0 Series Manuale elenco delle parti

ABB
ABB KOKM Series Manuale elenco delle parti