ACP-02 Addressable Manual Call Point Flush Mount Item Number: 4255-0250
Installation guide
1
Description
The Ampac ACP-02 double action re-settable Manual
Call Point (MCP) eliminates the possibility of accidental
operation and the cost and labour of replacement of
frangible elements.
Features
•Testing of operation without removal of front cover
•Resettable operation
•LED indication
•Suits standard mounting control wall box
Installation
Observe anti-static precautions at all times
Flush Mounting
1. Remove the securing screw from the front of MCP
while at the same time pulling the top of the facia
away from the backing plate
2. Set the address of the MCP (See Figure 2)
3. Place the spacer to the back of the MCP as shown
above and terminate the cables (See Figure 1)
4. Fix the backing plate and spacer to the wall box
using two (2) appropriately sized fixing screws
5. Set the address of the MCP (See Figure 2)
6. Remove the two (2) thread protection plugs from
the mounting box and fix the backing plate to it
using the two (2) fixing screws supplied
7. Replace the facia by inserting the two (2) bottom
locating pegs of the facia up into the bottom of the
locating holes of the backing plate, close at the top,
tighten the retaining screw then insert the key (as
shown) to reset the operation element
8. Testing of MCP Operation
1. Isolate the FACP from calling the fire brigade
2. Press on the clear ABS operation element in the
location indicated, PUSH HERE to drop the
element down
3. Operate the switch, the MCP LED should illuminate
and an alarm at the FACP should be indicated
4. To reset the operation element firmly push the key
up into the slot in the bottom of the facia
Note 1:
Set the device type in FireFinder
ConfigManager to S90 MCP
Note 2:
To ensure line monitoring integrity always use
one (1) set of terminals for “IN” and one (1) set for
“OUT”.