ascon M1 line Manuale utente

Temperature
Controller
1/16 DIN - 48 x 48
M1 line cc
User manual • M.I.U.M1-5/09.05 • Cod. J30-478-1AM1 IE
M1UK.ed5 14-05-2009 14:56 Pagina 1
ISO 9001
Certified
Ascon Tecnologic srl
via Indipendenza 56,
27029 Vigevano (PV)
Tel.: +39-0381 69 871
Fax: +39-0381 69 8730
Internet site:
www.ascontecnologic.com
E-Mail address:

Temperature
Controller
1/16 DIN - 48 x 48
M1 line cc
1
2
AT
M1UK.ed5 14-05-2009 14:56 Pagina 1

2
information
cc
NOTES
ON ELECTRIC
SAFETY AND
ELECTROMAGNETIC
COMPATIBILITY
Please, read carefully these instructions before proceeding with
the installation of the controller.
Class II instrument, rear panel mounting.
This controller has been designed with compliance to:
Regulations on electrical apparatus (appliance, systems and installa-
tions) according to the European Community directive 73/23/EEC amend-
ed by the European Comunity directive 93/68/EEC and the Regulations
on the essential protection requirements in electrical apparatus EN61010-
1 : 93 + A2:95.
Regulations on Electromagnetic Compatibility according to the
European Community directive n089/336/EEC, amended by the European
Community directive no. 92/31/EEC, 93/68/EEC, 98/13/EEC
and the following regulations:
Regulations on RF emissions
EN61000-6-3 : 2001 residential environments
EN61000-6-4 : 2001 industrial environments
Regulation on RF immunity
EN61000-6-2 : 2001 industrial equipment and system
It is important to understand that it’s responsibility of the installer to ensure
the compliance of the regulations on safety requirements and EMC.
The device has no user serviceable parts and requires special equipment
and specialised engineers. Therefore, a repair can be hardly carried on
directly by the user. For this purpose, the manufacturer provides techni-
cal assistance and the repair service for its Customers.
Please, contact your nearest Agent for further information.
All the information and warnings about safety and electromagnetic
compatibility are marked with the Bsign, at the side of the note.
M1UK.ed5 14-05-2009 14:56 Pagina 2

3
Table of contents
TABLE OF CONTENTS 1INSTALLATION ...........................................................................................................................Page 4
2ELECTRICAL CONNECTIONS.....................................................................................Page 8
3PRODUCT CODING..............................................................................................................Page 14
4OPERATIONS..............................................................................................................................Page 18
5AUTOMATIC TUNE...............................................................................................................Page 28
6TECHNICAL SPECIFICATIONS...................................................................................Page 29
Main universal input
Control Alarms Retransmission
Resources
OP1
PV
OP2
OP4
(option)
Setpoint
Operating mode
PV
M1
1Single OP1 OP2 OP4
action
2Single OP2 OP1 OP4
action
0Indication OP1 OP2 OP4
only
Modbus RS485
Parameterisation
Supervision
Fuzzy tuning
with automatic selection
One shot
Auto tuning One shot
Natural frequency
Special functions
M1UK.ed5 14-05-2009 14:56 Pagina 3

4
1 - Installation
1INSTALLATION
Installation must only be carried
out by qualified personnel.
Before proceeding with the instal-
lation of this controller, follow the
instructions illustrated in this man-
ual and, particularly the installation
precautions marked with the B
symbol, related to the European
Community directive on electrical
protection and electromagnetic
compatibility.
B
To prevent hands or metal touch-
ing parts that may be electrically
live, the controllers must be
installed in an enclosure and/or in
a cubicle.
1.1 GENERAL DESCRIPTION
IP20 Terminal block
EN61010 - 1 (IEC1010 - 1)
Product code label
Sealing front panel gasket
Mounting clamps
Panel surface
Front panel
IP65 protection
EN 650529 (IEC 529)
M1UK.ed5 14-05-2009 14:56 Pagina 4

5
1 - Installation
1.2 DIMENSIONAL DETAILS
48 mm
1.89 in
120 mm
4.72 in
48 mm
1.89 in
20 mm max.
0.79 in max.
1.3 PANEL CUT-OUT
65 mm min.
2.56 in min.
45+0.6 mm
1.78+0.023 in
45+0.6 mm
1.78+0.023 in
65 mm min.
2.56 in min.
M1UK.ed5 14-05-2009 14:56 Pagina 5

6
1 - Installation
Special conditions
MAltitude > 2000 m
TTemperature >50°C
%Rh Humidity > 95 %
PConducting atmosphere Use filter
Warm up
Use forced air ventilation
Use 24Vac supply version
Suggestions
Forbidden Conditions D
CCorrosive atmosphere
EExplosive atmosphere
Operating conditions
MAltitude up to 2000 m
TTemperature 0…50°C [1]
%Rh Relative humidity 5…95% non-condensing
1.4 ENVIRONMENTAL RATINGS B
UL note
[1] Operating surrounding
temperature 0…50°C
M1UK.ed5 14-05-2009 14:56 Pagina 6

7
1 - Installation
1.5.1 INSERT THE INSTRUMENT
1Prepare panel cut-out
2Check front panel gasket posi-
tion
3Insert the instrument through
the cut-out
1.5.2 INSTALLATION SECURING
1Position the mounting clamps
2Push the mounting clamps
towards the panel surface to
secure the instrument
1
3
2
1.5.3 CLAMPS REMOVING
1Insert the screwdriver in the clips
of the clamps
2Rotate the screwdriver
1
2
1.5.4 INSTRUMENT UNPLUGGING B
1Push and
2pull to remove the instrument
Electrostatic discharges can
damage the instrument
Before removing the instrument the
operator must
discharge him-
self to ground
1
1
1
2
1
2
1
1MΩ
1.5 PANEL MOUNTING [1]
UL note
[1] For Use on a Flat Surface
of a Type 2 and Type 3
‘raintight’ Enclosure.
M1UK.ed5 14-05-2009 14:56 Pagina 7

8
2 - Electrical connections
2ELECTRICAL CONNECTIONS
2.1 TERMINAL BLOCK [1] B
Pin connector
q1.4 mm
0.055 in max.
Ø
Fork-shape
AMP 165004
Ø 5.5 mm - 0.21 in
Stripped wire
L 5.5 mm - 0.21 in
Terminals
L
0,5
Nm
6
5
4
3
2
1
12
11
10
9
8
7
16
15
Rear
terminal
cover
Wire size 1 mm2
(18 AWG Solid/
Stranded) [2]
5.7 mm
0.22 in
14 screw terminals
Option terminals
Tightening torque
0.5 Nm
Pillips screwdriver
PH1
Flat blade screwdriver
0.8 x 4 mm
1
TC
mA
mV
OP1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
b
B
A
RTD
L
N
NO
C
RS485
(OP4)
OP2 - L 18V—
OUT
N/C
N/C
N/C
N/C
NO
C
F50-
474 1A1M1
OP2 - R
UL notes
[1] Use 60/70 °C copper (Cu)
conductor only.
[2] Wire size 1mm2(18 AWG
Solid/Stranded)
M1UK.ed5 14-05-2009 14:56 Pagina 8

9
2 - Electrical wirings
PRECAUTIONS B
Despite the fact that the instrument
has been designed to work in an
harsh and noisy environmental
(level IV of the industrial standard
IEC 801-4), it is strongly recom-
mended to follow the following
suggestions.
A
All the wiring must comply with the
local regulations.
The supply wiring should be rout-
ed away from the power cables.
Avoid to use electromagnetic con-
tactors, power relays and high
power motors nearby.
Avoid power units nearby, espe-
cially if controlled in phase angle
Keep the low level sensor input
wires away from the power lines
and the output cables.
If this is not achievable, use shield-
ed cables on the sensor input, with
the shield connected to earth.
2.2 PRECAUTIONS AND ADVISED CONDUCTOR COURSE B
Conduit for supply and output cables
Conduit for low level sensor cables
A= Supply
B= Outputs
C= Analog inputs
D= Analogue output
Serial
communications
E= SSR drive output
BB
6
5
4
3
2
1
12
11
10
9
8
7
L
N
A
CED
16
15
B B
6
5
4
3
2
1
12
11
10
9
8
7
L
N
A
CED
16
15
B
M1UK.ed5 14-05-2009 14:56 Pagina 9