Beijer Electronics BoX2 extreme Manuale utente

Installation Manual
BoX2 extreme
MAEN276
2023-09

Foreword
All BoX2 devices are developed to satisfy the demands of human-machine communication.
Configuration is carried out on a PC using iX Developer software. The project can then be transferred
and stored in the device itself. Various types of automation equipment such as PLCs, servos or
drives can be connected to the device. In this manual, the term “the controller” refers to the
connected equipment. This manual explains how to install the device. Please refer to the iX
Developer reference manual for further information.
Copyright © 2023 Beijer Electronics AB. All rights reserved.
The information in this document is subject to change without notice and is provided as availa-
ble at the time of printing. Beijer Electronics AB, including all its group companies, reserves
the right to change any information without updating this publication. Beijer Electronics AB, in-
cluding all its group companies, assumes no responsibility for any errors that may appear in this
document. Read the entire installation manual prior to installing and using this equipment. Only
qualified personnel may install, operate or repair this equipment. Beijer Electronics AB, includ-
ing all its group companies, are not responsible for modified, altered or renovated equipment.
Because the equipment has a wide range of applications, users must acquire the appropriate
knowledge to use the equipment properly in their specific applications. Persons responsible
for the application and the equipment must themselves ensure that each application is in
compliance with all relevant requirements, standards and legislation in respect to configuration
and safety. Only parts and accessories manufactured according to specifications set by Beijer
Electronics AB, including all its group companies, may be used.
BEIJER ELECTRONICS AB, INCLUDING ALL ITS GROUP COMPANIES, SHALL NOT BE LIABLE TO
ANYONE FOR ANY DIRECT, INDIRECT, SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULT-
ING FROM THE INSTALLATION, USE OR REPAIR OF THIS EQUIPMENT, WHETHER ARISING IN TORT,
CONTRACT, OR OTHERWISE. BUYER'S SOLE REMEDY SHALL BE THE REPAIR, REPLACEMENT, OR
REFUND OF PURCHASE PRICE, AND THE CHOICE OF THE APPLICABLE REMEDY SHALL BE AT THE
SOLE DISCRETION OF BEIJER ELECTRONICS AB, INCLUDING ALL ITS GROUP COMPANIES.
Head Office
Beijer Electronics AB
Box 426
201 24 Malmö, Sweden
www.beijerelectronics.com / +46 40 358600

Table of Contents
1. Safety Precautions ........................................................................................ 5
1.1. General ............................................................................................ 5
1.2. Hazardous Materials ............................................................................. 5
1.3. Disposal Requirements Under WEEE Regulations ............................................ 5
1.4. UL and cUL Installation .......................................................................... 6
1.5. During Installation ................................................................................ 6
1.6. During Use ......................................................................................... 7
1.7. Service and Maintenance ........................................................................ 7
1.8. Dismantling and Scrapping ...................................................................... 7
2. Installation ................................................................................................. 8
2.1. Installation Process .............................................................................. 8
2.1.1. Protective Connector Shield Installation Process .................................. 11
2.1.2. Connections to the Controller ........................................................ 12
2.1.3. Other Connections and Peripherals .................................................. 12
3. Technical Data ............................................................................................ 13
3.1. Compass Safe Distance ......................................................................... 14
4. Chemical Resistance ..................................................................................... 15
4.1. Metal Casing ...................................................................................... 15
5. Device Drawings .......................................................................................... 16
5.1. Connectors ....................................................................................... 16
5.2. Connectors ....................................................................................... 16
5.2.1. Power Supply ............................................................................ 16
5.2.2. Communication Ports .................................................................. 17
5.3. Device Outline ................................................................................... 19
6. Additional Installation Tips ............................................................................. 20
6.1. Grounding the Device ........................................................................... 20
6.2. To Achieve Better EMC Protection ............................................................ 21
6.3. Safety ............................................................................................. 22
6.4. Galvanic Isolation ............................................................................... 23
6.5. Cable and Bus Termination RS-485 ........................................................... 24
6.6. CAN Interface .................................................................................... 24
6.6.1. Cable Recommendations .............................................................. 24
6.6.2. Termination ............................................................................. 24
6.6.3. Restrictions and Recommendations .................................................. 25
6.7. USB Flash Drive .................................................................................. 25
Beijer Electronics, MAEN276 3 2023-09

4

1. Safety Precautions
Both the installer and users of the BoX2 device must read and understand this manual.
1.1. General
• Read the safety precautions carefully.
• Check the delivery for transportation damage. If damage is found, notify the supplier as soon as
possible.
• Do not use the device in an environment with high explosive hazards.
• The supplier is not responsible for modified, altered, or reconstructed equipment.
• Use only parts and accessories manufactured according to specifications of the supplier.
• Read the installation and operating instructions carefully before installing, using, or repairing the
device.
• Never allow fluids, metal filings or wiring debris to enter any openings in the device. This may
cause fire or electrical shock.
• Only qualified personnel may operate the device.
• This is an OPEN-TYPE device and should therefore be installed in an enclosure to prevent
unqualified personnel from operating it.
• The figures in this manual serve an illustrative purpose. Because of the many variables associated
with any particular installation, the supplier cannot assume responsibility for actual use based on
the figures.
• The supplier neither guarantees that the device is suitable for your particular application, nor
assumes responsibility for your product design, installation or operation.
1.2. Hazardous Materials
Part description
零件描述
Toxic and hazardous materials or elements
有毒和有害的材料或元素
PCB and electronic components
PCB 和电子元件
Pb Hg Cd Cr6+ PBB PBDE
X O O O O O
O: Indicates that this toxic or hazardous substance contained in all of the homogenous materials for
this part is below the limit requirement in SJ/T 11363–2014.
O: 表示该有害物质在该部件所有均质材料中的含量均在 SJ/T 11363–2014 规定的限量要求以下
X: Indicates that this toxic or hazardous substance contained in at least one of the homogenous
materials for this part is above the limit requirement in SJ/T 11363–2014.
X: 表明该有害物质至少在部件的某一均质材料中的含量超出 SJ/T 11363–2014 规定的限量要求。
1.3. Disposal Requirements Under WEEE Regulations
For professional users in the European Union: If you wish to discard electrical and electronic
equipment (EEE), please contact your dealer or supplier for further information.
For disposal in countries outside of the European Union: If you wish to discard this product please
contact your local authorities or dealer and ask for the correct method of disposal.
Safety Precautions
Beijer Electronics, MAEN276 5 2023-09

1.4. UL and cUL Installation
• All devices have to be supplied by a Class 2 power supply.
WARNING
• Do not separate when energized.
AVERTISSEMENT, NE PAS SEPARER SOUS TENSION.
• Do not open when an explosive atmosphere is present.
NE PAS OUVRIR SI UNE ATMOSPHERE EXPLOSIVE EST PRÉSENT.
• Battery may explode if mistreated. Do not recharge, disassemble or dispose of in
fire. This product contains a battery that is not user replaceable.
LA BATTERIE PEUT EXPLOSER EN CAS DE MAUVAISE MANIPULATION. NE LA
RECHARGEZ PAS, NE LA DÉMONTEZ PAS ET NE LA JETEZ PAS DANS LE FEU.
CE PRODUIT CONTIENT UNE PILE QUI NE PEUT PAS ÊTRE REMPLACÉE PAR
L'UTILISATEUR.
• Potential electrostatic charging hazard, see instructions. To avoid electrostatic
charge build-up, it must not be rubbed or cleaned with solvents or a dry cloth
when installed or used within a potentially explosive atmosphere.
POTENTIEL ÉLECTROSTATIQUE RISQUE DE CHARGEMENT, VOIR INSTRUCTIONS.
• Explosion hazard! Substitution of components may impair suitability for Class I,
Division 2.
RISQUE D'EXPLOSION! LA SUBSTITUTION DE COMPOSANTS PEUT NUIRE À LA
CONFORMITÉ DE CLASSE I, DIVISION 2.
CAUTION
• Temperature code xT4 IEC/EN60079x-0, IEC/EN60079-7, IEC/EN60079-15 and IEC/
EN60079-31. Protection string Ex ec nC IIC T4Gc and Ex tc IIIC T82 °C Dc.
CODES DE TEMPÉRATURE T4 IEC/EN60079-0, IEC/EN60079-7, IEC/EN60079-15 et
IEC/EN60079-31. CHAîNE DE PROTECTION Ex ec nC IIC T4Gc et Ex tc IIIC T82 °C Dc.
1.5. During Installation
• Install the device according to the accompanying installation instructions.
• Ground the device according to the accompanying installation instructions.
• Only qualified personnel may install the device.
• Separate the high voltage, signal, and supply cables.
• Make sure that the voltage and polarity of the power source is correct before connecting the
device to the power outlet.
• Peripheral equipment must be appropriate for the application and location.
• Use only UL certified and approved M12 cables or M12 connector with cable gland. See section
Installation Process for installation details. See step 3 in the process for UL approved M12 cables
sets and M12 connector with cable gland.
Safety Precautions
2023-09 6 Beijer Electronics, MAEN276

1.6. During Use
• Keep the device clean.
• Emergency stop and other safety functions may not be controlled from the device.
1.7. Service and Maintenance
• Only qualified personnel should carry out repairs.
• The agreed warranty applies.
• Before carrying out any cleaning or maintenance operations, disconnect the equipment from the
electrical supply.
• The battery must be replaced by an authorized Beijer Electronics service center.
WARNING
On versions with Codesys runtime included, do not replace the battery before a
backup of the Codesys retain variables and content has been made!
For more information contact our local support team or look in help online.
1.8. Dismantling and Scrapping
• Recycle the device and parts of it according to local regulations.
• The following components contain substances that might be hazardous to health and the
environment: lithium battery and electrolytic capacitor.
Safety Precautions
Beijer Electronics, MAEN276 7 2023-09

2. Installation
2.1. Installation Process
71.7
M4 x 0.7
178.4
6 mm min. (4x)
20
6 mm min. (4x)M3 x 0.5
34
163.2
D
C
Installation
2023-09 8 Beijer Electronics, MAEN276

The following is needed:
• A Phillips screwdriver for installation of the M12 protection bracket
• Four M5 × 0.8 screws conforming to the table above
• Installation tool for mounting screws
Do the following:
1. Unpack and check the delivery. If damage is found, notify the supplier.
NOTE
Place the BoX2 device on a stable surface during installation. Dropping the
device or letting it fall may cause damage.
2. Attach UL certified and approved cables\connectors to the BoX2 device. Special precaution must
be followed to ensure approved cable\connector sets are installed according to the environment
and application where the device will be located. The unit is certified to be installed in the
following hazardous environments:
• C1D2, Type 4X
• ATEX\IECEx Zone 2
NOTE
Please refer to the following tables for information on which connectors \ cables
are to be used in each of these two environments.
NOTE
For information, see table ATEX \ IECEx Zone 2 Environment (M12 cables sets)
and Type 4X, C1D2 Environments (M12 connector with cable gland) below.
NOTE
M12 connector with cable gland torque: 3 Nm.
3. Drill the correct hole pattern in device outlined above or install unit on VESA compliant mounting
bracket.
Installation
Beijer Electronics, MAEN276 9 2023-09

• Connect cable A to the terminal, using 14-20 AWG (2.08–0.52 mm2), 180–220 N-cm torque.
NOTE
Use minimum 85°C copper conductors only.
ATEX \ IECEx Zone 2 Environment (M12 cables sets)
Manufacturer Beijer Part
Number
Manufacturer Model No. Description
Binder 100-1025 77-3529-0000-50708-0300 M12 male 8p to blank 3 meter
(COM)
100-1151 77-3529-0000-50708-1000 M12 male 8p to blank 10 meter
(COM)
Binder 100-1024 77-4529-0000-34704-0300 M12 male 4p to blank 3 meter
(LAN)
100-1152 77-4529-0000-34704-1000 M12 male 4p to blank 10 meter
(LAN)
Binder 100-1023 77-3430-0000-50004-0300 M12 female 4p to blank 3 meter
(power)
100-1153 77-3430-0000-50004-1000 M12 female 4p to blank 10
meter (power)
Type 4X, C1D2 Environments (M12 connector with cable gland)
Manufacturer Beijer
Part
Number
Manufacturer
Model No.
Description Cable Ratings
Binder 100-1148 99-1487-992-08 X2 extreme
Connector, M12
SS 8p male 5.5 -
7.5 mm Gland
(COM)
CMX cable rated 300V,
2 4AWG, 8 conductor,
5.5 - 7.5 mm OD, -30°
C to 70° C
PLTC cable rated 300V,
22AWG, 4 conductor,
5.5 mm – 7.5 mm OD,
-30° C to 70° C
Installation
2023-09 10 Beijer Electronics, MAEN276
Altri manuali per BoX2 extreme
2
Questo manuale è adatto per i seguenti modelli
1
Indice
Altri manuali Beijer Electronics Convertitore multimediale

Beijer Electronics
Beijer Electronics 100-0973 Manuale utente

Beijer Electronics
Beijer Electronics BoX2 pro Manuale utente

Beijer Electronics
Beijer Electronics BoX2 base v2 Foglio di istruzioni

Beijer Electronics
Beijer Electronics BoX2 extreme Manuale utente

Beijer Electronics
Beijer Electronics JetCon 1701GP-U Manuale utente