Bluezone PK-220 Guida all'installazione

Document #: BPI-PM013-00
1
IMPORTANT SAFEGUARDS
READ AND SAVE THESE INSTRUCTIONS
Safety
This manual contains important instructions
and safety information about the Bluezone Air
Purification System. Observe the following
dangers, warnings, cautions and notices
when installing, operating and servicing the
Bluezone PK-220.
Electrical System
Energized electrical circuits present a
potentially life-threatening hazard.
Ensure the unit’s power cord is unplugged
before performing any installation or service
work.
Do Not Operate unit with a damaged cord or
plug. Discard the cord and reorder a new
cord from an authorized Bluezone dealer.
Follow all lockout/tagout procedures for all
electrical circuits.
Refer to the product asset tag and confirm the
PK-220 electrical requirements before
energizing the unit.
System Operation
The appliance is not to be used by persons
(including children) with reduced physical,
sensory or mental capabilities, or lack of
experience and knowledge, unless they have
been given supervision or instruction.
Children being supervised should not play
with the appliance.
For Indoor Agricultural Applications:
Do not operate the Bluezone PK-220 while
fogging with chlorine bleach or other
disinfectant solutions. Turn off the Bluezone
Units if disinfectant fogging or cleaning is
underway.
•Turn Bluezone units back on after
disinfectants have dissipated.
Never hose down the Bluezone PK-220 or
clean with a water jet.
Turn off Bluezone units and cover with plastic
if the room is being hosed with water or
steam.
System Maintenance
The Bluezone PK-220 contains 4 germicidal
ultra-violet (UV-C) light bulbs; the UV light is
completely contained inside the unit during
operation.
The Bluezone PK-220 has multiple safety
systems to ensure that you cannot view the
UV bulbs while they are operating.
Do NOT attempt to override the cover switch
to allow the bulbs to operate when the cover
is off.
Skin or eye damage may result from directly
viewing the light produced by the lamp in this
apparatus. Always disconnect power before
relamping or servicing.
Replace lamps using Lamp Replacement Kit
Model No. 005-000008, manufactured by

Document #: BPI-PM013-00
2
Bluezone Products Inc. and sold by an
Authorized Bluezone Partner.
The UV-C bulbs contain small amounts of
mercury. If you break a bulb follow the clean-
up instructions at the end of this manual.
Description
The Bluezone® PK-220 is an air purification
device that draws in air containing viruses,
old, spores or fungus, and discharges air with
a highly reduced concentration of these
infectious impurities. The unit is completely
self-contained. The facility, equipment, and
personnel have no contact with the process
that is cleaning the air.
The Bluezone unit’s operation is controlled by
a microprocessor-based controller that alerts
the user to any system faults.
Specifications
The specifications of the Bluezone PK-220 are shown in Table 1. Please note that the 120V and
230V models of the PK-220 are different units and can only be used at the voltage listed on the
asset tag.
Table 1: Bluezone PK-220 Specifications
Imperial / US Installation
Metric / OUS Installation
Size
24 X 48 X 9 in
61 X 122 X 23 cm
Weight
38 lbs.
17 kg
Electrical Current
2A
1.1A
Input Voltage
120V
230-240V~
Power
250 Watts
250 Watts
Flow Rate
220 CFM
380 m3/hr
Mounting Options
Floor, wall, or drop ceiling
Noise
High Speed: 46 dBA
Low Speed: <40 dBA
High Speed: 46 dBA
Low Speed: <40 dBA
Capacity
1600 sf @ 1 ACH
800 sf @ 2 ACH
550 sf @ 3 ACH
150 m2sf @ 1 ACH
75 m2sf @ 2 ACH
50 m2sf @ 3 ACH
Maintenance
Bulb change once every 1-3 years*, no filters to replace
*Bulb life is 8800 hours:
Typical office application is 10 hours per day, 5 days per week, or >3
years between bulb change out. 24 hour/day operation requires an
annual bulb change.

Document #: BPI-PM013-00
3
Key Components
Figure 1: Bluezone PK-220 Key Components

Document #: BPI-PM013-00
5
Installation Guidelines
The Bluezone PK-220 offers variable
installation options with no additional
cabinetry required. Units can be mounted to
the floor, mounted to the wall, or installed in
2’ X 4’ drop ceiling grid. A mounting cleat is
provided and must be used in all floor and
wall applications to prevent tip.
The number of PK-220s used in the space
depends on the size of the room and the
desired number of additional air changes
per hour (ACH) to be provided by air
cleaning.
For an additional 1 ACH, use one PK-220
for every 1600 square feet of floor space.
For an additional 2 ACH, use one PK-220
for every 800 square feet of floor space.
For an additional 3 ACH, use one PK-220
for every 550 square feet of floor space.
If multiple Bluezone PK-220 units are being
installed in a room, the following are
recommended guidelines for the placement
of the Bluezone units:
1. Distribute the units relatively evenly
throughout the space.
2. Units placed on the floor should be
positioned against a wall to protect
against tipping.
3. If installing in drop ceiling tiles, ensure at
least one ceiling tile between the
Bluezone PK-220 and either a HVAC
diffuser or a light fixture.

Document #: BPI-PM013-00
6
Installation
Bluezone PK-220 can be mounted to the floor, mounted to the wall, or installed into a 2’ X 4’
drop ceiling opening.
Floor/Wall Mounting:
Overview
The Bluezone PK-220 unit can be mounted the floor or mounted to a wall with the cleat
provided. A wall mounting bracket is integral to the unit.
Figure 3: PK-220 Wall Mounting Bracket

Document #: BPI-PM013-00
7
Preparation
Unpack the Bluezone PK-220 and locate the included wall mounting cleat. See arrows in Figure
4 for recommended fastener install locations.
Figure 4: PK-220 Wall Mounting Cleat
Securely fasten the mounting cleat to the wall using the recommended fasteners shown in Table
2. If installing to metal or wood studs the bracket must be secured to 2 studs. It is the installers
responsibility to determine fasteners. All fasteners must be rated for 120lbs or greater.
For floor placement, mount the cleat 41 ½” off the floor. The installation of the wall mounting
cleat is required to prevent the PK-220 from tipping. Failure to secure the PK-220 with the
mounting cleat can result in injury.
Figure 5: Cleat Mounting Height for Floor Placement of the PK-220

Document #: BPI-PM013-00
8
For wall mounting, Bluezone recommends mounting the cleat at 46” or greater off the floor for 4”
or greater of clearance from the base of the PK-220 to the floor. Provide a minimum distance of
6 in from the top of cleat to the ceiling.
Figure 6: Cleat Mount to Wall for Wall Mounting the PK-220
Securely fasten the mounting cleat to the wall using the recommended fasteners shown in Table
2. If installing the cleat onto a stud wall (wood or metal) locate the studs and fasten directly to
them. Follow anchor manufacturer specifications for selecting screws.
Table 2: Recommended Fasteners
Wall type
Fasteners Recommended
Wood studs
4X #8 cabinet screws
Metal studs
4X ¼-20 toggle-style anchors
Concrete
6X M4 expansion shield anchors
with hex bolts
½” Drywall
6X toggle-style anchors

Document #: BPI-PM013-00
9
Hang the PK-220 mounting bracket on the wall mounting cleat. Adjust the Bluezone PK-220 to
center it onto the mounting cleat.
Figure 7: Hang the PK-220 Mounting Bracket on the Mounting Cleat