8| GB312 Applications Manual
Logano plus GB312 applications manual | 04.2008
Technical specifications are subject to change without prior notice
Connection ST (B-kit) TPN"1TPN"¾
Diameter GAS TPN"¼1TPN"1
Boiler size (output - no. of heat exchanger
sections) Model 90 - 4 120 - 4 160 - 5 200 - 6 240 - 7 280 - 8
Tab. 1 Dimensions and connection sizes
1.2.2 Specifications
Observe all standards and guidelines appli-
cable to the installation and operation of the
heating system in your country. The informa-
tion on the boiler rating plate is denitive and
it is imperative that it is observed.
Boiler size (output - no. of heat exchanger sec-
tions) Model 90 - 4 120 - 4 160 - 5 200 - 6 240 - 7 280 - 8
Natural gas
I-B-R Input max. load Btu/hr
328,300 440,500 588,300 732,600 880,700 1,028,800
min. load Btu/hr
132,150 132,000 176,000 220,000 264,000 309,000
I-B-R gross output 180/80 ° F max. load Btu/hr
305,000 409,000 544,000 676,000 810,000 944,000
I-B-R net rating 180/80 ° F max. load Btu/hr
265,000 356,000 473,000 588,000 704,000 821,000
Rated heat input 122/86 ° F max. load Btu/hr
307,090 409,460 545,940 682,430 818,910 955,400
(50/30 ° C) min. load Btu/hr 128,050 127,390 171,190 212,310 255,220 298,140
Flue gas mass ow rate 180/80 ° F max. load lb/min 4.85 6.53 9.14 11.40 13.88 16.15
Flue gas mass ow rate 122/86 ° F max. load lb/min 5.05 7.12 9.29 11.61 14.02 16.65
Flue gas temperature 180/80 ° F max. load ° F 83 90 127 138 140 134
Flue gas temperature 122/86 ° F max. load ° F 120 133 129 131 131 135
CO2 content, natural gas max. load %9.1
min. load
Available ue pressure in. W.C. 0.4 (100 Pa)
(ue draft + air supply pressure)
Air supply volumetric ow rate cfm 95 95 130 160 190 220
Blower G1G 170
Honeywell gas valve V4730C1071 V4730C1097 V4730C10
63
Gas injector diameter
Natural gas caloric value 1075 BTU/ft3 17.0
Heating water circuit
Boiler water capacity US gal-
lons 4.2 4.2 5.3 6.3 7.1 7.9
Primary pressure drop psi Fig. 4 (graph)
Maximum ow temperature, heating/hot water
mode (at full output) ° F 172/180
High temperature cut-out safety limit (manual
reset high limit setting )° F 200
Permissible operating pressure psi 50
Electrical data
Enclosure class IP 40
Mains power supply V/Hz 120 V / 60 Hz
Power consumption max. load W84 150 190 230 270 370
min. load W40 40 45 50 50 50
Maximum permissible fuse rating A10 (slow blow)
Appliance dimensions and weight
Transport clearance dimensions, width x depth x
height Inches 34x25x60 42x25x60 50x25x60
Weight lbs 455 530 585 665 730
Boiler size (output - no. of heat exchanger sec-
tions) Unit 90 - 4 120 - 4 160 - 5 200 - 6 240 - 7 280 - 8
Tab. 2 Specications
fm
mm