
88
88
8
The rotor displacement angle ϑbetween stator and rotor
is depending of the mechanical moving torque of the
generator shaft. The mechanical shaft power is balanced
with the electrical feeded mains power, and therefore the
synchronous speed keeps constant (Fig. 4.5).
Fig. 4.5: Voltage vectors at mains parallelFig. 4.5: Voltage vectors at mains parallel
Fig. 4.5: Voltage vectors at mains parallelFig. 4.5: Voltage vectors at mains parallel
Fig. 4.5: Voltage vectors at mains parallel
operationoperation
operationoperation
operation
4.6 Vector surge supervision (MRN3-1)
The vector surge supervision protects synchronous
generators in mains parallel operation due to very fast
decoupling in case of mains failure. Very dangerous are
mains auto reclosings for synchronous generators. The
mains voltage returning after 300 ms can hit the
generator in asynchronous position. A very fast
decoupling is also necessary in case of long time mains
failures. Generally there are two different applications:
a) Only mains parallel operation no singleOnly mains parallel operation no single
Only mains parallel operation no singleOnly mains parallel operation no single
Only mains parallel operation no single
operation:operation:
operation:operation:
operation:
In this application the vector surge supervision
protects the generator by tripping the generator
circuit breaker in case of mains failure.
b) Mains parallel operation and singleMains parallel operation and single
Mains parallel operation and singleMains parallel operation and single
Mains parallel operation and single
operation:operation:
operation:operation:
operation:
For this application the vector surge supervision trips
the mains circuit breaker. Here it is insured that the
gen.-set is not blocked when it is required as the
emergency set.
A very fast decoupling in case of mains failures for
synchronous generators is known as very difficult. Voltage
supervision units cannot be used because the synchronous
alternator as well as the consumer impedance support the
decreasing voltage.
For this the mains voltage drops only after some 100 ms
below the pickup threshold of voltage supervision relays
and therefore a safe detection of mains auto reclosings is
not possible with this kind of relay.
Frequency relays are partial unsuitable because only a
highly loaded generator decreases its speed within 100
ms. Current relays detect a fault only when shortcircuit
type currents exist, but cannot avoid their development.
Power relays are able to pickup within 200 ms, but they
cannot prevent power to rise to short-circuit values too.
Since power changes are also caused by sudden loaded
alternators, the use of power relays can be problematic.
Whereas the MRN3-1MRN3-1
MRN3-1MRN3-1
MRN3-1 detects mains failures within 60
ms without the restrictions described above because they
are specially designed for applications where very fast
decoupling from the mains is required.
Adding the operating time of a circuit breaker or contactor,
the total disconnection time remains below 150 ms. Basic
requirement for tripping of the generator/mains monitor
is a change in load of more than 15 - 20 % of the rated
load. Slow changes of the system frequency, for instance
at regulating processes (adjustment of speed regulator) do
not cause the relay to trip.
Trippings can also be caused by short-circuits within the
grid, because a voltage vector surge higher than the
preset value can occur. The magnitude of the voltage
vector surge depends on the distance between the short-
circuit and the generator. This function is also of
advantage to the Power Utility Company because the
mains short-circuit capacity and consequently the energy
feeding the short-circuit is limited.
To prevent a possible false tripping the vector surge
measuring can be blocked at a set low input voltage (refer
to 5.4.7). The undervoltage lockout acts faster then the
vector surge measurement.
Vector surge tripping is blocked by a phase loss so that a
VT fault (e.g. faulty VTs fuse) does not cause false tripping.
When switching on the aux. voltage or measuring voltage,
the vector surge supervision is blocked for 5 s (refer to
chapter 4.8).
Note:Note:
Note:Note:
Note:
In order to avoid any adverse interference voltage effects,
for instance from contactors or relays, which may cause
overfunctions, MRN3-1MRN3-1
MRN3-1MRN3-1
MRN3-1 should be connected separately
to the busbar.
4.6.1 Measuring principle of vector surge
supervision
When a synchronous generator is loaded, a rotor
displacment angle is build between the terminal voltage
(mains voltage U1) and the synchronous internal voltage
(Up). Therefore a voltage difference ΔU is built between
Up and U1 (Fig. 4.4).
Fig. 4.4: Equivalent circuit at synchronousFig. 4.4: Equivalent circuit at synchronous
Fig. 4.4: Equivalent circuit at synchronousFig. 4.4: Equivalent circuit at synchronous
Fig. 4.4: Equivalent circuit at synchronous
generator in parallel with the mainsgenerator in parallel with the mains
generator in parallel with the mainsgenerator in parallel with the mains
generator in parallel with the mains
UP
~
ΔU= .jX
d
I1
U1Z
~
Mains
I2
I1
ΔU= l
1
.jX
d
UP
U
1
Generator Mains / Load