Cansec Zodiac FR100 Manuale utente

Zodiac FR100TM
INSTALLATION MANUAL
June 2014

Zodiac FR100TM Page 2 of 15
Installation Manual June 2014 • Rev. 1.2
Table of Contents
INTRODUCTION ....................................................................................................................... 3
SPECIFICATIONS..................................................................................................................... 4
Diodes............................................................................................................................ 5
Terminal Strips and Cable.............................................................................................. 5
READER LAYOUT.................................................................................................................... 6
READER INSTALLATION......................................................................................................... 7
Mounting Plate ............................................................................................................... 9
Reader Mounting...........................................................................................................10
READER WIRING ....................................................................................................................11
Wiegand Reader –SmartLock Pro Controller................................................................11
Wiegand Reader –H1000 Controller.............................................................................12
Wiegand Reader –3rd Party Access Controller..............................................................13
LOCK OUTPUT RELAY WIRING –STANDALONE READER.................................................14
DC Electric Strikes –Differrent power source................................................................14
DC Electric Strikes –Same power source.....................................................................15

Zodiac FR100TM Page 3 of 15
Installation Manual June 2014 • Rev. 1.2
Introduction
Zodiac FR100™ facial recognition reader is Cansec’s newest addition to its
industry leading line of biometric readers.
The FR100™ leads the way with cutting edge technology and simplicity of use.
Capable of storing 500 user templates, it offers a read response of less than 1
second, sending the user’s Wiegand data to any access control panel to provide
accurate user validation. Alternatively, using its internal relay in stand-alone
mode, it can be used to restrict access to CNC machines, punch presses, or other
equipment which must only be operated by trained personnel.
User enrollment is done quickly and easily at the reader by an administrator in
less than a minute. User templates can be exported and imported via network or
USB connectivity to simplify management of multi-reader installations.

Zodiac FR100TM Page 4 of 15
Installation Manual June 2014 • Rev. 1.2
Specifications
Power Supply and Requirements
Zodiac FR100®Reader: ............................................. 12 VDC, 500 mA
Supplied Plug-in Transformer: ..........................................12 VDC, 1A
User Capacity:
CA-ZODFR100 - 500 Users
Verification Method: .......................................................... Face Recognition
Verification Speed:……………………………..….Less than 1 Second (500 Users)
Keyboard: ....................................................................... 4x4 Touch Keyboard
LCD: .....3.5 “TFT Color Screen, 65000 Bright Color, 320x240 Resolution
Communication Method: ...................Standard TCP/IP, USB Flash Drive
Environment Light:......................................................................... 0-5000Lux
Working Distance: ........................................................................... 30-80cm
Working Temperature: .................................. 0oC - 40oC [32oF - 104oF]
Working Humidity: ...................................................................... 20% - 80%
Installation Method: ................................................................... Wall Mount
Capture Distance: ............................................. 30 cm - 80 cm [11.8" - 31.5"]
Communications Cable (multi-reader configuration)
RJ-45 Cable: .......................................................... Standard RJ-45 cable
On-Board Relay (standalone configuration)
Normally Open Dry Contact Relay: ...................Rated @ 30 VDC, 1A
Wiegand Output
Standard 26-bit
Cansec 37-bit
Reader Cable (required when connected to an access controller)
Wiegand Cable: ....................... 4 conductor (twisted pair not required)
............................................................................22 AWG, overall shield
............................................................... 152 m (500 ft)max total length
Dimensions & Weight
Reader: ............................................200 mm (l) x 95 mm (w) x 115 mm
..........................................................[ 7.87” (l) x 3.74” (w) x 4.53” (h) ]
Weight: .......................................................................... 505 g (1.11 lbs)
Specifications subject to change without notice.

Zodiac FR100TM Page 5 of 15
Installation Manual June 2014 • Rev. 1.2
DIODES
Diodes are required for inductive loads such as electric strikes/locks. Failure
to use appropriate diodes will void the reader warranty.
TERMINAL STRIPS AND CABLE
Use MARR Connectors
If you are bringing in cable that is too large for the terminal
strip, use a MARR connector (wire nut, marrette, thimble
connector, cone connector). Splice the thicker cable to a cable
that is the appropriate thickness, and then run the thinner
cable to the terminal strip on the control panel.
Use Splices for Parallel Wiring
The terminal strips are designed to allow one cable per hole.
If you need to connect multiple cables in a single hole, use a
MARR connector (wire nut, marrette, thimble connector,
cone connector). Splice multiple cables to a single cable, and
then run the single cable to the terminal strip on the control
panel.
NOTE: When determining power supply current requirements, you must consider lock
and reader current draw if using the same supply for these devices.
NOTE:
Installation of magnetic locks is not supported with this reader
.
NOTE: The lock must have a diode installed to prevent “back EMF” from
damaging the reader.

Zodiac FR100TM Page 6 of 15
Installation Manual June 2014 • Rev. 1.2
Reader Layout
1. 3.5 inch TFT Color LCD
2. Navigational keys
3. Cansec label
4. Right camera
5. Left camera
6. LED
7. Confirmation key
8. Escape/Cancel key
9. Alphanumeric key
10. Backspace key
11. Menu key
12. USB port
13. Mounting plate screw
14. Reset button
15. RJ-45 jack
16. 12VDC input jack
17. Terminal blocks
18. SD card slot
19. Mounting plate
20. Speaker
21. Tamper switch
Terminal Block (Pin 6 –10)
Pin 6 & 7 are internally connected. 12VDC
input to pin 6 will also supply 12VDC to pin 7
and vice versa.
Pin 8 & 9 are internally connected. Both pins
have the same ground.
Those extra pins are provided for wiring
convenience, e.g. use pin 6 & 8 to power the
reader and pin 7 & 9 to power other device

Zodiac FR100TM Page 7 of 15
Installation Manual June 2014 • Rev. 1.2
Reader Installation
Do not install the reader in a place subject to direct sunlight, humidity and dust.
Do not install the reader close to a magnet, CRT, TV, monitor or speaker. They
may damage the reader.
Do not to let liquid like water, drinks or chemicals leak inside the device.
Use either supplied transformer OR terminal block for reader power input.
OR
(not both)

Zodiac FR100TM Page 8 of 15
Installation Manual June 2014 • Rev. 1.2
Recommended installation height is 1.2m (47") to read individuals from 155cm
to 193cm (5'1" to 6'4") at a distance of 46cm to 91cm (18" to 36"). Adjust
installation height accordingly for lower or higher height requirements.
Must be mounted away from any direct sunlight.
Ensure the unit is level.
1.20m (47”)
Ground
Cameras

Zodiac FR100TM Page 9 of 15
Installation Manual June 2014 • Rev. 1.2
MOUNTING PLATE
Drill four holes in the
wall using mounting
bracket as a template.
Mounting Studs

Zodiac FR100TM Page 10 of 15
Installation Manual June 2014 • Rev. 1.2
READER MOUNTING
1. Do not install the mounting plate to the reader until the last step.
2. Connect cables with terminal blocks through the gap of the mounting
plate as shown.
See Wiegand reader wiring section
.
3. If necessary, connect an Ethernet cable (RJ-45) to the RJ-45 jack through
the gap of the mounting plate.
4. If mounted as a standalone reader, use the supplied transformer and plug
the connector to the 12VDC port through the gap of the mounting plate.
5. Install the mounting plate to the wall (1.15 to 1.20 m above the ground).
See mounting plate section above for more information
.
6. Mount the reader to the mounting plate using the mounting holes and the
mounting studs and ensure it is rested steadily on the mounting plate.
7. Tighten screws at the bottom of the mounting plate to the reader.
Mounting Hole
Anchor Holes
Screws
Tamper Switch
Terminal Blocks
RJ-45 Jack
12 VDC Input
Mounting Studs
NOTE: For standalone application either use plug-in transformer OR terminal block for
power input.
Altri manuali per Zodiac FR100
1
Indice
Altri manuali Cansec Controllori di accesso IP






















