Clevertronics Clevertest and Clevertest Plus
Refer to the supplementary operation guide supplied with the Product.
After Power ON, the Status LED on a Clevertest Plus enabled fitting will display a rapid Green or Red
flashing for a period up to 2 minutes.
Zoneworks and DATA Monitored Options
Supalites with part numbers –ZW and -DATA are fitted with Zoneworks communications modules
(nodes).These fittings are monitored using either Powerline Carrier Technology that utilising the power
cable to provide data communication or a dedicated data cable to/from data routers installed on a
dedicated data trunk connected to a central Server (can also be connected via Ethernet/Internet/Fibre).
Zoneworks software on the server is used to monitor, coordinate testing and collate test data from each
fitting. Zoneworks Supalites can be commissioned by a single push of the test switch, or scanning of the
supplied barcode. The LED Test Switch indicator provides a multifunction indication of the status of the
Supalite during testing and normal operation:
LED flashes at 0.5Hz (0.5s GREEN, 0.5s Yellow)
Emergency Light Test In Progress
LED flashes at 3s On (Yellow) & 0.5s Off
In the case of the DATA version a 2-way “figure 8” cable and terminal block facilitates the connection to
the DATA network via a multi-drop bus (daisy chain connection). For further information of installation of
a Zoneworks system, please refer to the Zoneworks Users Guide and Commissioning Guide (incl. DATA
version)
DALI EM Option
Supalites with part numbers -DALI are fitted with DALI modules (nodes) that facilitate connection and
integration to 3rd Party Lighting Control Systems. Before installing the -DALI Supalite, please confirm that
the Lighting Control System has the capability to monitor DALI Emergency Luminaires. The Supalite will
be addressed and configured into the control system by the Lighting Control System Commissioning
Technicians and not Clevertronics.
Commissioned/ Un-commissioned
Emergency Light Test in progress
LED flashes at 1s On (Yellow) & 1s Off
Fitting goes into emergency mode for 10 seconds
A 2-way “figure 8” cable and terminal block facilitates the connection to the DALI network OR a 5/6way
“structured wiring system” lead and plug facilitates the power and DALI connection. DALI connections
are marked as Da Da.
L10 Supalite LED Weatherproof Emergency
Luminaire
Installation & Maintenance Instruction Leaflet
Victoria (Head Office & Manufacturing)
195 Chesterville Rd
Moorabbin VIC 3189
Phone: +61 3 9559 2700
Fax: +61 3 9559 2799
New South Wales
Phone: +61 2 8805 6400
Fax: +61 2 8805 6444
Queensland
Phone: +61 7 3442 9700
Fax: +61 7 3442 9777
South Australia/Northern Territory
Phone: +61 8 8301 8800
Fax: +61 8 8351 8286
Western Australia
Phone: +61 8 9248 3720
Fax: +61 8 9248 3725
New Zealand
Phone: +64 800 548 448
Designed in Australia to comply with the requirements of
AS2293.3: 2005 and AS/NZS CISPR15: 2011
NOTE: Standard product codes with this symbol are
enabled with Clevertest Plus capability. Please refer to the
operation guide supplied with the product for details.
(NOTE: -CTProductssupplied with the Clevertest Plus Symbol are activated with Clevertest
PLUS capability. Please refer to the operation guide supplied with the product for details).
BATT:L10 6.6V 2500mAh.200mm lead.SBS.
PCA:LEDPP MV.Drvr.18V 500mA. CT10220-L2
WP Led Head, c/w Led's & Loom, Gland
Important:
It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before installation,
ensure that the electricity supply has been switched off and isolated. Installation must be carried out in
accordance with the relevant Australian and International Standards.