Cotek CR-10 Manuale utente

CR-10
Remote Control
User’s Manual
www.cotek.com.tw

Remote control introduction
Press the ON / OFF button on the front. The SD-series starts working
normally. After switching on expect a five to ten second delay.
The SD-series will be operating in normal condition when either of the
following messages are displayed on the LCD panel screen :
LED Indications :
˙GRID: Displays incoming AC input status.
80
46 2-φ3.3
92
92
30.5
5.5 71
71
AC Input
DC-AC Inverter LED Status
AC input ON
Inverter AC Working
Inverter AC Saving
Inverter AC shunt down
Green
Green Blink
OFF
AC input OFF
Green
OFF
LED Status
˙Inverter: Displays the SD-series working statuses.
Alarm LED Status
Abnormal
Normal
Red
OFF
˙Alarm: Displays the SD-series alarm status.
1

[Up]
You can use the “up” button to scroll through
the menus or to select the value for set up
under setting mode.
[Down]
You can use the “Down” button to scroll through
the menus or to select the value for set up
under setting mode.
[Page Up]
You can use the “Page Up” button to scroll
through the menus.
[Page Down]
You can use the “Page Down” button to scroll
through the menus.
[Enter]
Confirms a selection or value.
[ON / OFF]
The SD-series can be activated by the button.
Press “ON / OFF” button, the SD-series to
startup. If you want to turn OFF the SD-series,
press the “ON / OFF” button longer than 3
seconds.
[Enter Setup Menu]
Press the button longer than 3 seconds, The
SD-series will change to “Select Menu” which
appears on the LCD screen for the user to set
functions.
LCD Remote Control Panel Selection Buttons :
˙Function :
Function
2

LCD Rear View Introduction
Jump (reference 1 )
The “J1 jump” is placed inside the remote controller.
Green Terminal (reference 2 )
PIN Function
1 ALM
2
3
CTL
-ENB
4 -VCC
J1 Jump “CTL” Input Voltage
5 ~ 60 VDC
0 V
Open Turn ON
Turn OFF
SD-series
J1 Jump “CTL” Input Voltage
5 ~ 60 VDC
0 V
Short Turn OFF
Turn OFF
SD-series
˙J1 jump “short”
˙J1 jump “open”
Note: The “J1” jump default mode is “short”.
3

WARNING!
To turn “ON” the SD-series by operating the –ENB
function of LCD Panel, the SD-series inverter cannot
be turned OFF by any other operations, only by the
MAIN “OFF” SWITCH.
ALM-Battery is common ground.
RJ-45 port, connect to inverter(reference 3 )
˙ALM (PIN1)
When the SD-series
has the warning or the
protection displayed,
simultaneously this
“ALM” pin will changing
output to 5 Volt / 10mA
control signal to provide
the user.
˙ENB (PIN3)
User can USE this
“-ENB” pin to control the
SD-series to turn ON or
turn OFF.
˙-Vcc (PIN4)
This is LCD remote control panel ground.
4

Display tree:
Operation and Instructions Entering Setup Menu:
Power Switch ON
INVERTER
Initialization..
Vi=xx.xxVo=xxx.x
FQ=xx.x Io=xx.x
User Interface
LCD Contrast
<Function 14>
LCD Auto-off
<Function 15>
RS232 Baudrate
<Function 6>
Buzzer Setting
<Function 16>
Alert Setting
<Function 17>
Shut-down retry
<Function 10>
Language
<Function 18>
O/P Voltage
<Function 5>
O/P Frequency
<Function 7>
Sync Frequency
<Function 8>
Overload Alarm
<Function 9>
Saving Level
<Function 11>
Saving Interval
<Function 12>
Bypass Relay
<Function 13>
OVP Setting
<Function 0>
OVP Recovery
<Function 1>
UVP Setting
<Function 2>
UVP Recovery
<Function 3>
UV Alarm
<Function 4>
I/P Parameter
O/P Parameter
RST to Default
Press button longer than 3 seconds. The SD-series enters the
select Menus consisting of four layers:
(1) User Interface: (2)I/P Parameter :
(3) O/P Parameter: (4)RST to Default:
Select Menu Heading:
The manual is used to show the status of the running SD-series.
The user can make selections by switching on <UP> or
<DOWN>.
5

Vi:XX.X
FQ:XX.X Io:XX.X
Vo:XXX.X
Parameter Setting:
˙User Interface
Press button before entering the “User Interface” menus.
FQ = xx.x →Display the INV frequency.
Io = xx.x →Display the INV output current.
FQ = xx.x →Display the INV frequency.
Io = xx.x →Display the INV output current.
Setting Menu
LCD Contrast 0 ~ 100
SETT<value>
1. LCD contrast : Sets the LCD screen contrast.
Default = 50%
Setting range = 0% ~ 100%
Setting Menu
LCD Auto-off 0 ~ 120
SETT<value>
2. LCD Auto-off : Sets the LCD screen backlight auto off timer.
Default = 120 seconds
Setting range = 0 ~ 120 seconds.
4. Buzzer setting : Set the LCD remote control for the buzzer sound
Default = MSG, Alert, SHDN
Setting range = 0~7
Setting Menu
RS-232
Baud rate
0
1
2
3
4
1200
2400
4800
9600
19200
SETT<value>
3. RS-232 Baud rate :
Default setting: 4800
6

Model
English
Italian
Spanish
French
German
0
1
2
3
4
SETT (RS-232)
5. Alert Setting : When alert occurs, the internal dry contact relay
will open/close.
Default = Alert, SHDN
Setting range = 0~3
7. Language : The SD-series have different languages available and
are selectable.
Default = English
Setting: English / Italian / Spanish / French / German
6. Shut-down retry : When SD-series is shut-down under OVP, UVP,
Overload or short circuit conditions, the inverter will automatically
try to restart according to the setting value.
Default = 5
Setting range: 0 ~ 15
Setting Menu
Buzzer
Setting
0
1
2
3
4
5
6
7
Disable
SHDN
Alert
Alert , SHDN
MSG
MSG , SHDN
MSG , Alert
MSG , Alert , SHDN
SETT(RS-232) Buzzer(Beep sound)
Setting Menu
RS-232
Baud rate
0
1
2
3
Disable
SHDN
Alert
Alert , SHDN
SETT (RS-232) Alert (LCD)
7

Model
12V
24V
48V
15 VDC ~ 16 VDC
30 VDC ~ 32 VDC
60 VDC ~ 64 VDC
Setting value range
Model
12V
24V
48V
13 VDC ~ 15 VDC
26 VDC ~ 30 VDC
52 VDC ~ 60 VDC
Setting value range
˙I/P Parameter
2. OVP Recovery : When the DC input voltage is higher than the OVP
setting, the SD-series shuts-down; once the input voltage falls below
the set OVP value, the SD-series will automatically restart.
Default = 15 VDC @ 12V Model, 30 VDC @ 24V Model.
60 VDC @ 48V Model
Model
12V
24V
48V
10 VDC ~ 11 VDC
20 VDC ~ 22 VDC
40 VDC ~ 44 VDC
Setting value range
Model
12V
24V
48V
11.5 VDC ~ 13.5 VDC
23 VDC ~ 27 VDC
46 VDC ~ 54 VDC
Setting value range
3. UVP Setting : Setting Under Voltage Protection (UVP) and
Shut-down on the inverter operation.
Default= 10 VDC@ 12V Model, 20 VDC @ 24V Model.
40VDC @ 48V Model
4. UVP Recovery : When the DC input voltage is below the set UVP
value, the SD-series shuts-down; Once the input voltage rises above
the set UVP value, the SD-series will automatically restart.
Default= 12.5VDC @ 12V Model, 25 VDC @ 24V Model.
50VDC @ 48V Model
1. OVP Setting : Set the Over Voltage Protection (OVP) and shutdown.
Default = 16 VDC @ 12V Model, 32 VDC @ 24V Model.
64 VDC @ 48V Model
8

NOTE:
The value of the voltage set for the “UV Alarm” should be
equal to or higher than the value set for “UVP” or else the
unit will shut-down without any audible warning.
˙O/P Parameter
Model
110V
230V
97 VAC ~ 123 VAC
194 VAC ~ 246 VAC
Setting value range
Model
110V
230V
47 Hz ~ 63 Hz
47 Hz ~ 63 Hz
Setting value range
Model
12V
24V
48V
10.5 VDC ~ 11.5 VDC
21 VDC ~ 23 VDC
42 VDC ~ 46 VDC
Setting value range
5. UV Alarm : Setting Under Voltage (UV) alarm. When the input
voltage is lower than the set value, the SD-series will sound a
“beep” to remind you that the unit is going to shut-down. In the
meantime, the contact in the internal Dry Contact Relay will
open / close.
Default= 10.5 VDC @ 12 V Model, 21 VDC @ 24 V Model.
42 VDC @ 48 V Model
1. O/P Voltage : Setting the SD-series output voltage on the
inverter operation.
Default= 110 VAC @110 V Model, 230 VAC @ 230 V Model
2. O/P Frequency : Setting the SD-series output frequency on the
inverter operation.
Default= 60 Hz @ 110 V Model, 50 Hz @ 230 V Model.
3. Sync Frequency : If a generator is distorted. The output
waveform (too low frequency) is used as AC source, the allowed
frequency window for the incoming AC power can be enlarged.
9
Indice
Altri manuali Cotek Telecomando

Cotek
Cotek CR Series Manuale utente

Cotek
Cotek CR Series Manuale utente

Cotek
Cotek CR8 Manuale utente

Cotek
Cotek CR Series Manuale utente

Cotek
Cotek CR-20 Manuale utente

Cotek
Cotek CR-1 Manuale utente

Cotek
Cotek CR-21 PLUS Manuale utente

Cotek
Cotek CR5 Manuale utente

Cotek
Cotek CR6 Manuale utente

Cotek
Cotek CR-20 Manuale utente