www.crownboiler.com | Philadelphia PA
BWC SERIES - BIMINI
TECHNICAL SPECIFICATIONS
Specifications are subject to change without notice.
All Bimini boiler models include a full one-year warranty. A
15-year limited warranty is provided for the heat exchanger.
A 5-year and a 10-year extended warranty covering parts and
labor are also available. Visit CrownBoiler.com or see your
warranty for complete details.
The Mega-Stor® indirect water heater utilizes the
energy created by your boiler to produce abundant
hot water for your home. Mega-Stor water heaters
come in a variety of sizes from 26 to 119 gallons to
meet a multitude of residential and commercial
needs.
ADDITIONAL FEATURES/BENEFITS
• Available for use with natural or LP gas
• Wall mount and floor models available
• Optional pedestal base for wall mount model
• Approved for closet installation with clearances specified in the
installation manual
• Probe low water cut-off standard
• Commercial models available, consult factory
1
2
-
Y
E
A
R
L
I
M
I
T
E
D
W
A
R
R
A
N
T
Y
MODEL NO. OF
SECS.
NATURAL AND LP GAS DIMENSIONS (INCHES) COLLAR DIAMETERS*
INPUT
MBH
HEATING
CAPACITY
MBH
NET
WATER
RATING
MBH
AFUE
%“A” “B” “C” AIR INLET D
BWC070 Mono 70 63 55 91.0 17-7/8 31-1/2 17 60/100mm Concentric Vent
BWC090 Mono 90 80 70 91.0 17-7/8 31-1/2 17 60/100mm Concentric Vent
BWC120 Mono 120 107 93 90.0 17-7/8 31-1/2 17 60/100mm Concentric Vent
BWC151 Mono 150 135 119 90.5 17-7/8 31-1/2 20-1/2 80/125mm Concentric Vent
BWC150 3 150 133 117 90.5 23-3/8 43-3/4 22-1/4 4” 3”
BWC225 4 225 202 176 91.0 27 43-3/4 22-1/4 4” 4”
IMPORTANT: THIS BOILER REQUIRES A SPECIAL VENTING SYSTEM. READ INSTRUCTIONS CAREFULLY BEFORE INSTALLING.
*See installation manual for other venting specifications.
1. Altitudes above 2,000 ft. - ratings should be reduced at a rate of 4% for each 1,000 ft. above sea level (US only)
2. The Net Water Ratings are based on a piping and pickup allowance of 1.15.
3. The manufacturer should be consulted before selecting a boiler for installations having unusual piping and pickup requirements, such as intermittent
system operation, extensive piping systems, etc.
4. Models BWC070/090/120/151 may be installed on non-carpeted combustible surfaces when mounted on optional pedestal base.
5. Models BWC150/225 may be installed on non-carpeted combustible surface.
BWC070 - BWC090 - BWC120 - BWC151 BWC150 - BWC225
BWC - 12/12
PN 980039 - R6