8
The input can only be calibrated when a correct input
signal is applied. Adjustments can be made from -10.0
to +10.0°C, and 0.1 is the smallest increment that can
be used.
Click OK to write the change to the transmitter. The
display will show ‘Waiting’, and then ‘Input Updated’.
Click Close to exit the calibration screen. (It is not
necessary to program changes to the transmitter aer
calibration.)
At the time of calibration, a date and time stamp is
recorded in the transmitter and displayed in the Input
Zero Adjust panel as shown.
Calibration information is also stored in a text le on
your computer and can be accessed by clicking Logs, or
by navigating to the folder: My Documents/TM Setup/
cal serialnumber.txt
If you change the input type (i.e. from RTD to T/C), the
calibration value will be cleared. Changing the range
scaling does not clear the calibration.
See Appendix B for information on errors & other
dialogues that may appear during zero adjustment.
KHELP INFORMATION
Transmitter Installation
Guide: PDF manual for
the attached transmitter
(or a list of manuals, if no
transmitter is currently connected)
Soware User Guide: PDF of this manual
If your computer is connected to the internet, the
Help Information links will retrieve up-to-date manuals
from the web. If there is no internet connection, the
manuals that were current at the time of publication
of this soware will be served instead.
Either ‘Web Manuals’ or ‘Local Manuals’ will be
displayed in the lower right-hand corner of the panel,
to indicate the source of the documentation.