Deif SGC 110 Manuale utente

User manual
Single Genset Controller
SGC 110
DEIF A/S · Frisenborgvej 33 · DK-7800 Skive · Tel.: +45 9614 9614 · Fax: +45 9614 9615 · [email protected] · www.deif.com
Document no.: 4189341228A

1. Introduction
1.1 About SGC 110............................................................................................................................................................................................................................ 4
1.2 Key functions............................................................................................................................................................................................................................... 4
1.3 Product overview....................................................................................................................................................................................................................... 4
1.4 Passwords..................................................................................................................................................................................................................................... 5
1.5 Overview of controller buttons...........................................................................................................................................................................................5
1.6 Legal information.......................................................................................................................................................................................................................6
2. Safety instructions
2.1 General safety instructions.................................................................................................................................................................................................. 7
2.2 Electrical safety...........................................................................................................................................................................................................................7
2.3 In operation safety.....................................................................................................................................................................................................................7
3. Technical_specifications
3.1 Terminals........................................................................................................................................................................................................................................ 8
3.2 Power supply................................................................................................................................................................................................................................8
3.3 Genset voltage and frequency measurements..........................................................................................................................................................9
3.4 Digital inputs................................................................................................................................................................................................................................ 9
3.5 Analogue resistive sensor inputs.....................................................................................................................................................................................9
3.6 Analogue inputs used as digital inputs...................................................................................................................................................................... 10
3.7 D+ Charger alternator........................................................................................................................................................................................................... 10
3.8 Sensor common point...........................................................................................................................................................................................................11
3.9 Digital outputs...........................................................................................................................................................................................................................11
3.10 Communication ports.........................................................................................................................................................................................................11
4. Installation
4.1 Dimensions.................................................................................................................................................................................................................................12
4.2 Mounting in panel....................................................................................................................................................................................................................12
4.3 Terminal details........................................................................................................................................................................................................................ 13
4.4 Typical wiring diagram......................................................................................................................................................................................................... 15
5. Monitoring mode
5.1 Monitoring mode......................................................................................................................................................................................................................16
6. Configuration mode
6.1 Configuration mode............................................................................................................................................................................................................... 17
6.2 Configurable parameters.................................................................................................................................................................................................... 17
6.2.1 Configurable parameters..............................................................................................................................................................................................17
6.2.2 Module..................................................................................................................................................................................................................................18
6.2.3 Digital inputs...................................................................................................................................................................................................................... 18
6.2.4 Analogue inputs................................................................................................................................................................................................................19
6.2.5 Outputs.................................................................................................................................................................................................................................21
6.2.6 Timers...................................................................................................................................................................................................................................21
6.2.7 Generator............................................................................................................................................................................................................................22
6.2.8 Engine.................................................................................................................................................................................................................................. 23
6.2.9 Maintenance...................................................................................................................................................................................................................... 25
6.2.10 Password ID....................................................................................................................................................................................................................25
6.3 Digital input source selection...........................................................................................................................................................................................26
6.4 Digital output source selection........................................................................................................................................................................................26
7. Running modes
7.1 Remote start/stop mode...................................................................................................................................................................................................... 28
USER MANUAL 4189341228A UK Page 2 of 34

7.2 Deep sleep mode..................................................................................................................................................................................................................... 29
7.3 Manual mode..............................................................................................................................................................................................................................29
8. Alarms
8.1 Alarms........................................................................................................................................................................................................................................... 30
9. Troubleshooting
9.1 Troubleshooting.......................................................................................................................................................................................................................33
USER MANUAL 4189341228A UK Page 3 of 34

1. Introduction
1.1 About SGC 110
This document presents information necessary for operating DEIF's SGC 110 genset controller.
SGC 110 is a modern genset controller with user friendly HMI and full graphics LCD. The controller comes with a highly versatile
software. Extensive inputs and outputs support a wide variety of industry standard features in diesel/gasoline genset applications.
The DEIF Smart Connect software offers flexibility to configure each individual input and output for a specific function or application.
All parameters can also be configured on the controller.
1.2 Key functions
• Genset controller with configurable inputs:
◦ Five digital inputs
◦ Three analogue inputs
• Six digital outputs
• Monitors and controls the genset performance effectively
• Monitors genset output voltage and frequency precisely
• Remote start/stop
• Deep sleep mode to extend the battery lifetime
• Pre-heat output for assisting engine start
• PC connectivity via USB port for customised configuration
• Backlit full graphics display with power saving feature
• Log with the latest 30 events
1.3 Product overview
Following table gives a brief overview of SGC 110 features:
Features Specifications
Digital switch input 5
Analogue resistive inputs 3
DG alternator voltage input, D+ charging alternator I/O Yes
Digital outputs 6
Event logs Yes
USB I/O port for laptop access Yes
DC battery supply voltage (with -32 V reverse protection) 8 to 28 V
Operating temperature range -20 to 65 °C
Protection class with gasket (included) IP65
USER MANUAL 4189341228A UK Page 4 of 34

1.4 Passwords
The controller is protected from set-up changes with a four digit password.
There are two password levels:
Level Access Factory setting
1 Full access (read and write) 0123
2 Limited access (read) 1234
The passwords can be changed on the controller:
1. Go to Configuration mode.
2. Log on with password level 1.
3. Use the Up and Down buttons to go to Misc Settings, select with the Start button.
4. Use the Up and Down buttons to go to the password to be changed, select with the Start button.
5. Use the Up and Down buttons to choose the first digit for the new password, select with the Start button.
6. Repeat for the next three digits.
7. When all four digits are chosen, the display shows
PASSWORD 1
Password changed
1.5 Overview of controller buttons
1. Menu navigation up button
2. Menu navigation down button
3. Stop/Config button
4. Display
5. Alarm LED
6. Start button
7. Mode selection button
USER MANUAL 4189341228A UK Page 5 of 34

Button functions
In Mode Button input Function
Manual Start Starts the engine
Manual
Stop Stops the engine
Stop (long press) Enters Configuration mode
Down + Stop (long press) Enters Programming mode
Manual
Auto
Configuration
Up
Down Scrolls through the views/parameters
Manual
Auto Up + Down (during Alarm view) Acknowledges and clears the alarm
Configuration Start Selects/saves the parameter
Configuration Up + Down (long press) Enters the Event log page
Configuration Stop (long press) Back to Manual mode
Deep sleep Any Key (for min. 1 s) Back to Manual mode
Event log page Up + Down (long press) Back to Configuration mode
Programming Up + Down (long press) Enters Manual mode
1.6 Legal information
Warranty
WARNING
The controller is not to be opened by unauthorised personnel. If the controller is opened anyway, the warranty will be lost.
Disclaimer
DEIF takes no responsibility for installation or operation of the generator set. If there is any doubt about how to install or operate the
engine/generator controlled by the SGC controller, the company responsible for the installation or the operation of the set must be
contacted.
DEIF A/S reserves the right to change any of the contents of this document without prior notice.
The English version of this document always contains the most recent and up-to-date information about the product. DEIF does not
take responsibility for the accuracy of translations, and translations might not be updated at the same time as the English document.
If there is a discrepancy, the English version prevails.
Copyright
© Copyright DEIF A/S 2020. All rights reserved.
USER MANUAL 4189341228A UK Page 6 of 34

2. Safety instructions
2.1 General safety instructions
This document includes important instructions that should be followed during installation and maintenance of the controller.
Installation and maintenance must only be carried out by authorised personnel, and always in accordance with all applicable state
and local electrical codes. Efficient and safe operation of the controller can be acquired only if the equipment is correctly operated,
configured and maintained.
The following notations found in this document can indicate potentially hazardous conditions to the operator, service personnel or
the equipment.
NOTE Highlights an essential element of a procedure to ensure correctness.
CAUTION
Indicates a procedure or practice, which could result in damage or destruction of equipment, if not strictly observed.
WARNING
Indicates a procedure or practice, which could result in injuring personnel or loss of life, if not followed correctly.
2.2 Electrical safety
• Electric shock can cause severe personal injury or death.
• Ensure that the genset is grounded before performing any installation or service.
• Generators produce high electrical voltages, and direct contact with it can cause fatal electrical shock. Prevent contact with
terminals, bare wires, connections, etc., while the generator and related equipment are running. Do not tamper with interlocks.
• To handle the maximum electrical current, the wires used for electrical connections and wirings must be of appropriate size.
2.3 In operation safety
• Before installing the controller, ensure that all power voltage supplies are positively turned off at the source. Disconnect the
generator’s battery cables and remove the panel fuse to prevent accidental start up. Disconnect the cable from the battery post,
indicated by a NEGATIVE, NEG, or (–) first. Reconnect the negative cable last. Failure to do so will result in hazardous and
possibly fatal electrical shock.
• Remove the electric power supply before removing the controller or touching other electrical parts.
• Use extreme caution when working on electrical components. High voltage can cause injury or death.
• With floors of metal or concrete, use rubber insulation mats placed on dry wood platforms when working near the generator or
other electrical equipment.
• Do not wear damp clothing (particularly wet shoes) or allow skin surface to be damp when handling electrical equipment.
• Do not operate any electrical device or wires while standing in water, while barefoot, or while hands or feet are wet. It may result
in severe electrical shock.
• Do not wear jewellery. Jewellery can cause a short circuit within electrical contacts and cause shock or burning.
In case of an accident caused by electric shock, immediately shut down the electrical power source. If this is not possible, try to
release the victim from the live conductor. Avoid direct contact with the victim. Use a non-conducting object (for example a rope or a
wooden stick) to release the victim from the live conductor. If the victim is unconscious, apply first aid and get immediate medical
help.
USER MANUAL 4189341228A UK Page 7 of 34

3. Technical_specifications
3.1 Terminals
The SGC 110 uses two types of terminal blocks:
Connectors of 3.5 mm pitch Connectors of 5.08 mm pitch
Table 3.1 Terminals
Connector type Pitch Male (on controller)* Female (mating part)* Quantity
4-pin 3.5 mm 5441294 5441223 2
6-pin 3.5 mm 5441317 5441249 1
8-pin 3.5 mm 5441320 5441252 1
10-pin 3.5 mm 5443962 5447560 1
2-pin 5.08 mm 5447353 5441980 1
4-pin 10.16 mm 5474274 5453499 1
*Note: Phoenix (Phoenix Contact (I) Pvt. Ltd.)
3.2 Power supply
Category Specification
Controller terminals 1 (Ground)
2 (Battery or DC+)
Supply voltage range Nominal voltage: 12/24 V DC
Operating range: 8 to 28 V DC
Cranking drop out period 50 ms
Maximum reverse voltage protection -32 V DC
Measurement accuracy (battery voltage) ±1 % full scale
Resolution 0.1 V
Maximum current consumption ~ 200 mA, 12/24 V DC (excluding the current load for the DC
outputs)
Standby current consumption (LCD backlight off) 124 mA, 12 V DC
123 mA, 24 V DC
Deep sleep current 20 mA, 12/24 V DC
USER MANUAL 4189341228A UK Page 8 of 34

3.3 Genset voltage and frequency measurements
Category Specifications
Controller terminals
27 (Neutral)
28 (L3)
29 (L2)
30 (L1)
Measurement type True RMS
Phase-to-neutral voltage 32 to 300 V AC RMS
Phase-to-phase voltage 32 to 520 V AC RMS
Voltage accuracy ±2 % of full scale for phase-to-phase
Voltage resolution 1 V AC RMS for phase-to-neutral
2 V AC RMS for phase-to-phase
Frequency range 5 to 75 Hz
Frequency accuracy 0.25 % of full scale
Frequency resolution 0.1 Hz
NOTE For single phase applications, it is mandatory to connect the genset phase and neutral cables to the genset controller's
phase L1 and neutral terminals.
3.4 Digital inputs
Category Specifications
Controller terminals 10, 11, 12, 21, 22
Number of inputs 5
Type Negative sensing (connect to ground for activation)
Software configurable options
Low Lub Oil Pressure (LLOP) Switch, High Water Temperature, and more
(see Controller overview, Configurable parameters in the User manual for
more details).
3.5 Analogue resistive sensor inputs
Category Specifications
Controller terminals
24 (Engine temperature)
25 (Fuel level sensor)
26 (Oil pressure)
Number of inputs 3
Type Ratio-metric sensing
Range 10 to 5000 Ω (terminal 24)
10 to 1000 Ω (terminal 25 and 26)
Open circuit detection Above 5.5 kΩ (terminal 24)
Above 1.5 kΩ (terminal 25 and 26)
Measurement accuracy ±2% of full scale (up to 1000 Ω)
Connection method Connect the sensor output terminals between the genset
controller terminal and the battery ground terminal
USER MANUAL 4189341228A UK Page 9 of 34

SCP connection
SCP connections for Analogue inputs 1 to 3*:
Battery
Engine body
Sensor
input
Sensor
common
T erminal 41
Terminal 2
Terminal 1
Supply
SGC 1xx series
Analogue
resistive
sensor
*SCP connections for Analogue input 2 used as Fuel level sensor with the reference configured as Battery Negative
Battery
Sensor
input
Sensor
common
Terminal 2
Terminal 1
Supply
Analogue
resistive
sensor
SGC 1xx series
3.6 Analogue inputs used as digital inputs
Analogue inputs can be used as digital inputs when wired as shown.
F1
8-28
V DC
+
-
3.7 D+ Charger alternator
Category Specifications
Controller terminal 7
Voltage range 0 to VBATT
VBATT = 8 to 28 V DC
Excitation PWM (power limited to 3 W, 12 V/250 mA)
Accuracy ±1 % of full scale
USER MANUAL 4189341228A UK Page 10 of 34
Indice
Altri manuali Deif Controllori

Deif
Deif AGC-4 Manuale utente

Deif
Deif Multi-line 2 Manuale utente

Deif
Deif AGC 150 Manuale utente

Deif
Deif SGC 410 Manuale utente

Deif
Deif AGC 200 Series Manuale utente

Deif
Deif CGC 200 Manuale utente

Deif
Deif AGC 200 Series Manuale utente

Deif
Deif SGC 120 Manuale utente

Deif
Deif iE 250 Manuale utente

Deif
Deif SGC 420 Mk II Manuale utente

Deif
Deif DVC 310 Manuale di installazione e funzionamento

Deif
Deif PICUS PPM 300 Manuale utente

Deif
Deif CGC 400 Guida del prodotto

Deif
Deif AGC 200 Series Manuale utente

Deif
Deif AGC 150 Manuale utente

Deif
Deif SGC 420 Manuale utente

Deif
Deif SGC 420 Manuale utente

Deif
Deif AGC 200 Manuale utente

Deif
Deif AGC-4 Mk II Manuale utente

Deif
Deif GPC 300 Manuale utente