EMKO ESM-3710 Manuale utente

ESM-3710 77x35 DIN Size Temperature Controller
- 3 Digits Display
- NTC Input or,
PTC Input or,
J type thermocouple Input or,
K type thermocouple Input or,
2-Wire PT 100 Input or,
2-Wire PT 1000 Input (It must be determined in order)
- ON/OFF temperature control
- Selectable heating or cooling function
- Selection of operation with hysteresis
- Adjustable temperature offset
- Set value low limit and set value high limit boundaries
- Relay or SSR driver output
- Operation selection of compressor operates continuously, stops
or operates periodically in case of probe defect
- Compressor protection delays
- Password protection for programming mode
ESM-3710 77 x 35 DIN Size
Digital, ON / OFF Temperature Controller
Instruction Manual. ENG ESM-3710 02 V08 07/13

Instruction manual of ESM-3710 Temperature Controller consists of two main sections.
Explanation of these sections are below. Also, there are other sections which include order
information and technical specifications of the device. All titles and page numbers in instruction
manual are in “CONTENTS” section. User can reach to any title with section number.
Installation:
In this section, physical dimensions of the device, panel mounting, electrical wiring,
physical and electrical installation of the device to the system are explained.
Operation
Also in these sections, there are warnings to prevent serious injury while doing the
physical and electrical mounting or using the device.
Explanation of the symbols which are used in these sections are given below.
and Parameters:
In this section user interface of the device, accessing to the parameters, description of the
parameters are explained.
ABOUT INSTRUCTION MANUAL
a
c
i
2
This symbol is used to determine the dangerous situations as a result of an electric
shock. User must pay attention to these warnings definitely.
This symbol is used for safety warnings. User must pay attention to these
warnings.
This symbol is used to determine the important notes about functions and usage of
the device.

1.PREFACE............................................................................................................................................
1.1 GENERAL SPECIFICATIONS
1.2 ORDERING INFORMATION
1.3 WARRANTY
1.4 MAINTENANCE
2.INSTALLATION....................................................................................................................................
2.1 GENERAL DESCRIPTION
2.2 FRONT VIEW AND DIMENSIONS OF ESM-3710 TEMPERATURE CONTROLLER
2.3 PANEL CUT-OUT
2.4 ENVIRONMENTAL RATINGS
2.5 PANEL MOUNTING
2.6 INSTALLATION FIXING CLAMP
2.7 REMOVING FROM THE PANEL
3.ELECTRIAL WIRINGS.........................................................................................................................
3.1 TERMINAL LAYOUT AND CONNECTION INSTRUCTIONS
3.2 ELECTRICAL WIRING DIAGRAM
3.3 VIEW OF THE DEVICE LABEL
3.5 TEMPERATURE SENSOR INPUT CONNECTION
3.5.1 TC (THERMOCOUPLE) CONNECTION
3.5.2 PTC AND NTC CONNECTION
3.5.3 PT-100 AND PT-1000 CONNECTION
3.6 GALVANIC ISOLATION TEST VALUES OF ESM-3710 TEMPERATURE CONTROLLER
3.7 OUTPUT CONNECTIONS
3.7.1 RELAY OUTPUT CONNECTION
3.7.2 SSR DRIVER OUTPUT CONNECTION
4.FRONT PANEL DEFINITION AND ACCESSING TO THE MENUS....................................................
4.2 CHANGING AND SAVING SET VALUE
4.3 PROGRAM PARAMETERS
4.4 WORKING GRAPHICS OF ESM-3710 TEMPERATURE CONTROLLER
4.5 EASY ACCESS DIAGRAM OF PROGRAMMING MODE PARAMETERS
4.6 ENTERING TO THE PROGRAMMING MODE, CHANGING AND SAVING PARAMETERS
5.FAILURE MESSAGES IN ESM-3710 TEMPERATURE CONTROLLER............................................
6.SPECIFICATIONS................................................................................................................................
7.OTHER INFORMATIONS....................................................................................................................
3.4 SUPPLY VOLTAGE INPUT CONNECTION OF THE DEVICE
4.1 OBSERVATION OF SOFTWARE REVISION ON THE DISPLAYS
Contents
Page 5
Page 26
Page 19
Page 12
Page 7
Page 26
3
Page 27

4
Manufacturer’s Name : EMKO ELEKTRONIK A.S.
Manufacturer’s Address : DOSAB, Karanfil Sk., No:6,
16369 Bursa, TURKEY
The manufacturer hereby declares that the product:
Product Name : Temperature Controller Unit
Type Number : ESM-3710
Product Category : Electrical equipment for measurement, control and
laboratory use
Conforms to the following directives :
2006 / 95 / EC The Low Voltage Directive
2004 / 108 / EC The Electromagnetic Compatibility Directive
has been designed and manufactured to the following specifications:
EN 61000-6-4:2007 EMC Generic Emission Standard for Industrial Environments
EN 61000-6-2:2005 EMC Generic Immunity Standard for Industrial Environments
EN 61010-1:2001 Safety Requirements for electrical equipment for measurement, control
and laboratory use
When and Where Issued Authorized Signature
th
16 October 2009 Name : Serpil YAKIN
Bursa-TURKEY Position : Quality Manager
EU DECLARATION OF CONFORMITY

1.Preface
1.1 General Specifications
ESM-3710
Optional
Standard Control Output
Alarm Output
NTC
PTC
J or K Type TC
2-wire PT 100
2-wire PT 1000
Output-1
(SSr Driver Output)
Output-1 (Relay Output)
Control Output
Alarm Output
Heating or Cooling
Function
ON/OFF Operation
ESM-3710 series temperature controllers are designed for measuring and controlling
temperature. They can be used in many applications with their On / Off control form, heating and
cooling control form and easy-use properties.
Some application fields which they are used are below:
Application Fields
Glass
Plastic
Petro-Chemistry
Textile
Automative
Machine production industries
Applications
Heating
Baking Ovens
Incubators
Storages
Air Conditioning
Temperature Sensor
Input
Power Supply
Input
Standard
230 V V(±15%) , 50/60Hz
Optional Supply Input
115 V V(±15%) , 50/60Hz
24 V V(±15%) , 50/60Hz
24 V W(-15%,+10%),
50/60Hz
10...30 V Z
5

1.2 Ordering Information
All order information of ESM-3710
Temperature Controller are given on the
table at left. User may form appropriate
device configuration from information and
codes that at the table and convert it to the
ordering codes.
Firstly, supply voltage then other
specifications must be determined. Please
fill the order code blanks according to your
needs.
Please contact us, if your needs are
out of the standards.
VSymbol means Vac,
ZSymbol means Vdc,
Symbol means Vac/dcW
c
6
1.3 Warranty
EMKO Elektronik warrants that the equipment delivered is free from defects in material and
workmanship. This warranty is provided for a period of two years. The warranty period starts from
the delivery date. This warranty is in force if duty and responsibilities which are determined in
warranty document and instruction manual performs by the customer completely.
1.4 Maintenance
Repairs should only be performed by trained and specialized personnel. Cut power to the device
before accessing internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene etc.). Use of
these solvents can reduce the mechanical reliability of the device. Use a cloth dampened in ethyl
alcohol or water to clean the external plastic case.
A BC D E FG HI /
/
UV W Z/
/
0 00 2 0 0
1Relay Output ( resistive load 10 A@250 V V, 1 NO + 1NC )
Output-1
E
Supply VoltageA
Input Type
BC Scale(°C)
ESM-3710 (77x35 DIN Size)
24V V( ± 15% ) 50/60Hz
3
115V V( ± 15% ) 50/60Hz
4
230V V( ± 15% ) 50/60Hz
5
10...30 V Z
8
9Customer
2SSR Driver Output (Maximum 28 mA, 15 V Z)
00
12
05
09
J ,Fe CuNi IEC584.1(ITS90)
PTC (Note-1) -50°C 150°C
0°C 800°C
-19.9°C 99.9°C
PT 100 , IEC751(ITS90)
10 K ,NiCr Ni IEC584.1(ITS90)
-50°C 400°C
0°C 999°C
11 PT 100 , IEC751(ITS90)
14 -50°C 400°C
PT 1000 , IEC751(ITS90)
13 -19.9°C 99.9°C
PT 1000 , IEC751(ITS90)
15 PTC (Note-1) -19.9°C 99.9°C
Temp. Sensor which is given with ESM 3710
V
0None
1PTC-M6L40.K1.5 (PTC Air Probe with 1.5 m silicon cable)
2PTCS-M6L30.K1.5.1/8” (PTC Liquid Probe with 1.5 m silicon
cable)
Customer
3NTC-M5L20.K1.5 (NTC Probe, thermoplastic moulded with
1.5 m cable for cooling application)
4NTC-M6L50.K1.5 (NTC Probe, stainless steel housing with
1.5 m cable for cooling application)
9
Note-1 : If input type is selected PTC or NTC (BC = 12, 15, 18, 19 ),
Temperature sensor is given with the device. For this reason,
If input type is selected as PTC, sensor type (V = 0,1 or 2) or
If input type is selected as NTC, sensor type (V = 0,3 or 4) must be
declared in ordering information.
19 -19.9°C 99.9°C
-50°C 100°C
18
NTC (Note-1)
NTC (Note-1)
24V W( -15%,+10% ) 50/60Hz
2

7
In package ,
- One piece unit
- Two pieces mounting clamps
- One piece instruction manual
A visual inspection of this product for possible damage occured during shipment is
recommended before installation. It is your responsibility to ensure that qualified
mechanical and electrical technicians install this product.
If there is danger of serious accident resulting from a failure or defect in this unit, power
off the system and separate the electrical connection of the device from the system.
The unit is normally supplied without a power supply switch or a fuse. Use power switch
and fuse as required.
Be sure to use the rated power supply voltage to protect the unit against damage and to
prevent failure.
Keep the power off until all of the wiring is completed so that electric shock and trouble
with the unit can be prevented.
Never attempt to disassemble, modify or repair this unit. Tampering with the unit may
results in malfunction, electric shock or fire.
Do not use the unit in combustible or explosive gaseous atmospheres.
During the equipment is putted in hole on the metal panel while mechanical installation
some metal burrs can cause injury on hands, you must be careful.
Montage of the product on a system must be done with it’s fixing clamps. Do not do the
montage of the device with inappropriate fixing clamp. Be sure that device will not fall
while doing the montage.
It is your responsibility if this equipment is used in a manner not specified in this
instruction manual.
Before beginning installation of this product, please read the instruction
manual and warnings below carefully.
2.Installation
c

2.1 General Description
2.2 Front View and Dimensions of ESM-3710 Temperature Controller
77 mm / 3.03 inch
35 mm / 1.38 inch
Temperature Controller
ESM - 3710
SET
°C
SV
P
Mounting Clamp
Front Panel
IP65 protection
NEMA 4X
Panel surface
(maximum thickness 15 mm / 0.59 inch)
8

2.3 Panel Cut-Out
29 mm / 1.14 inch
71 mm / 2.79 inch
Maximum 15 mm / 0.59 inch
58.5 mm / 2.30 inch
4 mm /0.16 inch
9
110 mm / 4.33 inch (min)
50 mm / 1.97 inch (min)

c
1
2
1-Before mounting the device in your
panel, make sure that the cut-out is of
the right size.
2-Insert the device through the cut-out.
If the mounting clamps are on the unit,
put out them before inserting the unit to
the panel.
10
Operating Temperature : 0 to 50 °C
Max. Operating Humidity : 90% Rh (non-condensing)
Altitude : Up to 2000 m.
Operating Conditions
Forbidden Conditions:
Corrosive atmosphere
Explosive atmosphere
Home applications (The unit is only for industrial applications)
2.4 Environmental Ratings
2.5 Panel Mounting
c
During installation into a metal panel, care should be taken to avoid injury from
metal burrs which might be present. The equipment can loosen from vibration
and become dislodged if installation parts are not properly tightened. These
precautions for the safety of the person who does the panel mounting.
Indice
Altri manuali EMKO Regolatori di temperatura

EMKO
EMKO ESM-3723 Manuale utente

EMKO
EMKO ESM-4410 Manuale utente

EMKO
EMKO ESM-3711-H Manuale utente

EMKO
EMKO ESM-1510-N Manuale utente

EMKO
EMKO ESM-3712-HC Manuale utente

EMKO
EMKO ESM-9910.5.12.0.1/01.00/2.0.0.0 Manuale utente

EMKO
EMKO ESM-9910 Manuale utente

EMKO
EMKO ESM-3710-N Manuale utente

EMKO
EMKO ESM-3710-N Manuale utente

EMKO
EMKO ESM-7710 Manuale utente






















