EMKO ESM-4410 Manuale utente

ESM-4410 48 x 48 1/16 DIN Temperature Controller
-3D
- Selectable heating and cooling function
- Operating type selection with hysteresis
- Adjustment of temperature offset value
- Minimum pulling time adjustment for control outputs
- Password protection for programming mode
igits display
- NTC Input or,
PTC Input or,
J type thermocouple or,
K type thermocouple or,
PT-100 2-wire or 3-wire temperature input
( It must be determined in order )
- ON/OFF control form
ESM-4410 48 x 48 1/16 DIN
Digital, On/Off Temperature Controller
Instruction Manual. ENG ESM-4410 02 V03 04/08

Instruction manual of ESM-4410 Temperature Controller consists of three main sections.
Explanation of these sections are below. Also, there are other sections which include order
information and technical specifications of the device. All titles and page numbers in instruction
manual are in section. User can reach to any title with section number.
In this section, physical dimensions of the device, panel mounting, electrical wiring are
explained.
In this section, user interface of the device, how to access to the parameters, description
of the parameters are explained.
Configurable control function that is on the device is explained.
Also in these sections, there are warnings to prevent serious injury while doing the
physical and electrical mounting or using the device.
Explanation of the symbols which are used in these sections are given below.
“CONTENTS”
Installation:
Operation and Parameters:
Control Algorithm:
This symbol is used to determine the dangerous situations as a result of an electric
shock. User must pay attention to these warnings definitely.
a
cThis symbol is used for safety warnings. User must pay attention to these
warnings.
This symbol is used to determine the important notes about functions and usage of
the device.
i
ABOUT INSTRUCTION MANUAL
2

Page 5
Page 18
Page 12
Page 7
CONTENTS
1.PREFACE............................................................................................................................................
2.INSTALLATION....................................................................................................................................
3.ELECTRICAL WIRINGS......................................................................................................................
4.FRONT PANEL DEFINITION AND ACCESSING TO THE MENUS....................................................
5.PARAMETERS....................................................................................................................................
6.FAILURE MESSAGE IN ESM-4410 TEMPERATURE CONTROLLERS............................................
7.CONTROL ALGORITHM.....................................................................................................................
8.SPECIFICATIONS................................................................................................................................
1.1 GENERAL SPECIFICATIONS
1.2 ORDERING INFORMATION
1.3 WARRANTY
1.4 MAINTENANCE
2.1 GENERAL DESCRIPTION
2.2 FRONT VIEW AND DIMENSIONS OF ESM-4410 TEMPERATURE CONTROLLER
2.4 ENVIRONMENTAL RATINGS
2.5 PANEL MOUNTING
2.6 INSTALLATION FIXING CLAMP
2.7 REMOVING FROM THE PANEL
3.1 TERMINAL LAYOUT AND CONNECTION INSTRUCTIONS
3.2 ELECTRICAL WIRING DIAGRAM
3.3 LABELS FOR ESM-4410 TEMPERATURE CONTROLLER
INPUT CONNECTION
3.5.1 TC (THERMOCOUPLE) CONNECTION
3.5.2 RTD CONNECTIONS
3.5.3 PTC AND NTC CONNECTIONS
3.6 GALVANIC ISOLATION TEST VALUES OF ESM-4410 TEMPERATURE CONTROLLER
3.7 OUTPUT ( RELAY OUTPUT ) CONNECTION
4.1 FRONT PANEL DEFINITION FOR ESM-4410
4.2 OBSERVATION OF ESM-4410 TEMPERATURE CONTROLLER SOFTWARE REVISION
4.3 CHANGING AND SAVING SET VALUE
4.4 ENTERING TO PROGRAMMING MODE, CHANGING AND SAVING PARAMETERS
5.1 SET PARAMETER
5.2 PROGRAM PARAMETERS
7.1 ON/OFF CONTROL
7.1.1 ON/OFF CONTROL IN ESM-XX10 TEMPERATURE CONTROLLERS
2.3 PANEL CUT-OUT
3.4 SUPPLY VOLTAGE INPUT CONNECTION OF THE DEVICE
3.5 TEMPERATURE
Page 28
Page 27
Page 30
Page 29
3

Manufacturer Company Name : Emko Elektronik A.S.
Manufacturer Company Address: DOSAB, Karanfil Sokak, No:6, 16369 Bursa, Turkiye
The manufacturer hereby declares that the product conforms to the following
standards and conditions.
Product Name :
Model Number :
Type Number :
Product Category :
Conforms to the following directives :
Temperature Controller
ESM-4410
ESM-4410
Electrical equipment for measurement, control and laboratory use
73 / 23 / EEC The Low Voltage Directive as amended by 93 / 68 / EEC
89 / 336 / EEC The Electromagnetic Compatibility Directive
EN 61000-6-4:2001 EMC Generic Emission Standard for the Industrial Environment
EN 61000-6-2:2001 EMC Generic Immunity Standard for the Industrial Environment
EN 61010-1:2001 Safety Requirements for electrical equipment for measurement, control and
laboratory use
Has been designed and manufactured according to the following specifications
EU DECLARATION OF CONFORMITY
4

1.1 General Specifications
ESM-4410
Standard
Output (Relay
Output)
Glass
Plastic
Petro-Chemistry
Textile
Automative
Machine Production Industries
Application Fields
1.Preface
ESM series temperature controllers are designed for measuring and controlling
temperature. They can be used in many applications with On/Off control form and heating and
cooling selection. Some application fields which they are used are listed below:
Temperature Input
Supply Voltage
Input
Control Output
Alarm Output
Heating or Cooling
Function
ON/OFF Operation
NTC
PTC
JorKTypeTC
2or PT1003 wire
Standard
230 V (±%15) , 50/60 HzV
Optional Supply Voltage
Inputs
115 V (±%15) , 50/60 HzV
24 V (±%15) , 50/60 HzV
24 V ( - %15, + %10 )
50/60 Hz
W
5

1.2 Ordering Information
c
1.3 Warranty
EMKO Elektronik warrants that the equipment delivered is free from defects in material and
workmanship. This warranty is provided for a period of two years. The warranty period starts from
the delivery date. This warranty is in force if duty and responsibilities which are determined in
warranty document and instruction manual performs by the customer completely.
1.4 Maintenance
Repairs should only be performed by trained and specialized personnel. Cut power to the device
before accessing internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene etc.). Use of
these solvents can reduce the mechanical reliability of the device. Use a cloth dampened in ethyl
alcohol or water to clean the external plastic case.
All order information of ESM-4410
Temperature Controller are given on the
table at left. User may form appropriate
device configuration from information and
codes that at the table and convert it to the
ordering codes.
Firstly, supply voltage then other
specifications must be determined. Please
fill the order code blanks according to your
needs.
Please contact us, if your needs are
out of the standards.
V
Z
Vac,
Vdc,
Vacdc
Þ
Þ
ÞW
ESM-4410 (48x48 1/16 DIN)
ABCD E FGHI /
/
UVWZ/
/
1000200
1
00
Output-1
E
Output-2FG
None
Supply Voltage
24 V (±15%) 50/60 HzV
A
3
Customer
9
115 V (±15%) 50/60 HzV
4
230 V (±15%) 50/60 HzV
5
12
05
09
J ,Fe CuNi IEC584.1(ITS90)
PTC (Note-1)
Input Type
BC Scale(°C)
-50°C 150°C
0°C 800°C
-19.9°C 99.9°C
PT 100 , IEC751(ITS90)
10 K ,NiCr Ni IEC584.1(ITS90)
400°C
0°C 999°C
PT 100 , IEC751(ITS90) 0°C
PTC (Note-1)
15 -19.9°C 99.9°C
03
Temp.Sensor which is given with ESM-4410
V
0None
1PTC-M6L40.K1.5
(PTC Air probe with 1.5 m silicon cable)
2PTCS-M6L30.K1.5.1/8”(PTC Liquid probe with 1.5 m silicon cable)
Relay Output(7 A@250 V at resistive load, 1NO)
19 -19.9°C 99.9°C
-50°C 100°C
18
NTC (Note-1)
NTC (Note-1)
Note-1 : If input type is selected PTC or NTC (BC = 12, 15, 18, 19 ),
Temperature sensor is given with the device. For this reason,
If input type is selected as PTC, sensor type (V = 0,1 or 2) or
If input type is selected as NTC, sensor type (V = 0,3 or 4) must be
declared in ordering information.
Customer
3NTC-M5L20.K1.5 (NTC Probe, thermoplastic moulded with
1.5 m cable for cooling application)
4NTC-M6L50.K1.5 (NTC Probe, stainless steel housing with
1.5 m cable for cooling application)
9
224 V ( - %15, + %10 ) 50/60 HzW
6

In package ,
- One piece unit
- One piece instruction manual
A visual inspection of this product for possible damage occured during shipment is
recommended before installation. It is your responsibility to ensure that qualified
mechanical and electrical technicians install this product.
If there is danger of serious accident resulting from a failure or defect in this unit, power
off the system and the electrical connection of the device from the system.
The unit is normally supplied without a power switch or a fuse. Use power switch and fuse
as required.
Be sure to use the rated power supply voltage to protect the unit against damage and to
prevent failure.
Keep the power off until all of the wiring is completed so that electric shock and trouble
with the unit can be prevented.
Never attempt to disassemble, modify or repair this unit. Tampering with the unit may
results in malfunction, electric shock or fire.
Do not use the unit in combustible or explosive gaseous atmospheres.
During the equipment is putted in hole on the metal panel while mechanical installation
some metal burrs can cause injury on hands, you must be careful.
Montage of the product on a system must be done with it’s own fixing clamps. Do not do
the montage of the device with inappropriate fixing clamps. Be sure that device will not fall
while doing the montage.
It is your responsibility if this equipment is used in a manner not specified in this
instruction manual.
- Two pieces mounting clamps
separate
Before beginning installation of this product, please read the instruction
manual and warnings below carefully.
2.Installation
c
7

2.1 General Description
2.2 Front View and Dimensions of ESM-4410 Temperature Controller
84 mm / 3.31 inch
ESM-4410
SET
SET
OUT PROG
P
48 mm/ 1.89 inch
48 mm/ 1.89 inch
Maximum 5 0.2 inchmm /
11±1mm/0.43 inch
Mounting Clamp
Panel surface
(maximum thickness 5 mm / 0.2 inch)
Front Panel
IP65 protection
NEMA 4X
ESM-4410
8

2.3 Panel Cut-Out
65 mm / 2.56 inch (min)
65 mm / 2.56 inch (min)
46 mm / 1.81 inch (min)
46 mm / 1.81 inch (min)
9

c
Operating Temperature :
Max. Operating Humidity :
Altitude :
0to50°C
90 Rh (non-condensing)
Up to 2000 m.
%
Operating Conditions
Forbidden Conditions:
Corrosive atmosphere
Explosive atmosphere
Home applications (The unit is only for industrial applications)
2.4 Environmental Ratings
2.5 Panel Mounting
c
During installation into a metal panel, care should be taken to avoid injury from
metal burrs which might be present. The equipment can loosen from vibration
and become dislodged if installation parts are not properly tightened. These
precautions for the safety of the person who does the panel mounting.
1-Before mounting the device in your
panel, make sure that the cut-out is of
the right size.
2-Check front panel gasket position
3-Insert the device through the cut-
out. If the mounting clamps are on the
unit, put out them before inserting the
unit to the panel.
1
2
3
ESM-4410
10
Altri manuali per ESM-4410
1
Indice
Altri manuali EMKO Regolatori di temperatura

EMKO
EMKO ESM-3712-HCN Manuale utente

EMKO
EMKO ESM-9910.5.12.0.1/01.00/2.0.0.0 Manuale utente

EMKO
EMKO ESM-3712-HCN Manuale utente

EMKO
EMKO ESM-3710-N Manuale utente

EMKO
EMKO ESM Series Manuale utente

EMKO
EMKO ESM-1510-N Manuale utente

EMKO
EMKO ESM-3710-N Manuale utente

EMKO
EMKO ESM-4420 Manuale utente

EMKO
EMKO ESM-9910 Manuale utente

EMKO
EMKO ESM-7710 Manuale utente