Entrematic HVLS series Manuale utente

User’s Manual
Installation, Operations,
Maintenance and Parts
Part No. 6020031A
Do not install, operate or service this product unless you
have read and understand the Safety Practices, Warnings,
and Installation and Operating Instructions contained in
this User’s Manual. Failure to do so could result in death
or serious injury.
This manual applies to fans
manufactured beginning
November 2016 with the serial
number C61174800 and higher.
Commercial HVLS Fans

© Entrematic Group AB 2015
2 6020031A — Commercial HVLS Fans November 2016
You may nd safety signal words such as DANGER, WARNING, CAUTION or NOTICE throughout this User’s
Manual. Their use is explained below:
Indicates an imminently hazardous situation which,
if not avoided, will result in death or serious injury.
Indicates a potentially hazardous situation which, if
not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, if
not avoided may result in minor or moderate injury.
Notice is used to address practices not related to
personal injury.
This is the safety alert symbol. It is used
to alert you to potential personal injury
hazards. Obey all safety messages that
follow this symbol to avoid possible death or injury.
SAFETY SIGNAL WORDS
Introduction.................................................................2
Safety Signal Words ..................................................2
Safety Practices..........................................................3
Owner’s Responsibilities ............................................4
Fan Kit ........................................................................5
Hardware....................................................................6
Installation Considerations .........................................7
Fan Mount ..................................................................9
Components .............................................................12
TABLE OF CONTENTS
Installation ................................................................13
Operating Instructions ..............................................20
Planned Maintenance...............................................21
Troubleshooting........................................................22
Fire Control System Fan Shutdown..........................24
Parts List...................................................................25
Warranty ...................................................................27
Distributor Information ..............................................28
INTRODUCTION
Welcome and thank you for choosing this commercial fan from Entrematic
This User's Manual contains basic information that you need to safely install and operate your fan. Please
read and keep this User's Manual before using your new fan. For more information, please consult website at
www.entrematicfans.com.

© Entrematic Group AB 2015
November 2016 6020031A — Commercial HVLS Fans 3
SAFETY PRACTICES
READ AND SAVE THESE INSTRUCTIONS.
READ THESE SAFETY PRACTICES BEFORE
INSTALLING, OPERATING OR SERVICING THE FAN.
Failure to follow these safety practices could result in
death or serious injury.
READ AND FOLLOW THE OPERATING INSTRUCTIONS
IN THIS MANUAL BEFORE OPERATING THE FAN. If you
do not understand the instructions, ask your supervisor
to teach you how to use the fan.
To reduce the risk of electric shock, do not expose to
water or rain.
Support directly from building structure.
To reduce the risk of re, electric shock and injury to
persons, HVLS fan motor assemblies must be installed
with the blade assemblies that are marked on their
cartons to indicate the suitability with this model. Other
blade assemblies cannot be substituted.
To reduce the risk of re or electric shock, do not use
this fan with any solid-state speed control device
Be certain to follow the instructions in this manual.
If you do not understand the instructions, ask your
supervisor to explain them to you or call your authorized
local distributor.
To reduce the risk of injury to persons, install fan so that
the blade is at least 3.05m (10') above the oor.
INSTALLATION AND OPERATION:
Installation of the equipment must comply with local and
national electrical codes and must be in accordance with
ANSI/NFPA 70 clauses 400.7 and 400.8.
Do not use this commercial fan until you have received proper
training. Improper use could result in property damage,
bodily injury and/or death. Read and follow the complete
OPERATING INSTRUCTIONS on page 20 before use. If
you do not understand the instructions, ask your supervisor
to explain them to you or call your local distributor.
DO NOT USE THE FAN IF IT APPEARS DAMAGED OR
DOES NOT OPERATE PROPERLY. Inform your supervisor
immediately.
Do not operate the fan until all personnel, building structure
and moveable equipment are clear of all moving parts. Install
guards as required.
Do not install the fan unit onto structure of insufcient
strength. Consult a professional engineer or registered
architect. Improper installation of the fan could result in
death or serious injury.
For fans that will be subjected to high cross winds (open
bay doors or air conditioning diffuser ducts) the fan must be
at least one fan diameter (as measured from the end of the
winglet) from open bays or A/C ducts mounted below the
blade plane or there must be at least one fan diameter (as
measured from the end of the winglet) for A/C ducts mounted
at or above the blade plane.
MAINTENANCE AND SERVICE:
Before service, inspection, or cleaning make certain
that the power is disconnected and properly locked off.
If the fan does not operate properly using the procedures
in this manual, BE CERTAIN TO REMOVE POWER FROM
THE UNIT AND LOCK-OUT THE DISCONNECT ON THE
POWER CIRCUIT. Call your local distributor for service.
Keep your body clear of moving parts at all times.
All electrical troubleshooting and repair must be done by a
qualied technician and meet all applicable codes.

© Entrematic Group AB 2015
4 6020031A — Commercial HVLS Fans November 2016
OWNER’S RESPONSIBILITIES
The owner’s responsibilities include the following:
The owner should recognize the inherent danger of the
interface between the commercial fan and shop worker. The
owner should, therefore, train and instruct operators in the
safe use of the commercial fan.
Nameplates, cautions, instructions and posted warnings shall
not be obscured from the view of operating or maintenance
personnel for whom such warnings are intended. Warnings
which are worn or non-legible should be replaced.
Manufacturer’s recommended periodic maintenance and
inspection procedures in effect at date of shipment shall be
followed, and written records of the performance of these
procedures should be kept.
Commercial fans that are structurally damaged or have
experienced impacts from external sources, shall be removed
from service, inspected by the manufacturer’s authorized
representative, and repaired as needed before being placed
back in service.
The owner shall see that all nameplates and caution and
instruction markings or labels are in place and that the
appropriate operating and maintenance manuals are provided
to users.
Modications or alterations of commercial fans shall be made
only with written permission of the original manufacturer.

© Entrematic Group AB 2015
November 2016 6020031A — Commercial HVLS Fans 5
PACKING KIT
1. Blade Box – 5 blades
2. Fan Motor Box
a. Motor assembly with cover.
b. Remote control.
c. Controller box.
d. Mounting hardware.
e. Power and communication cables.
REQUIRED TOOLS
• Wrenches: 9/16
• Sockets: 1/2, 9/16
• Spirit level, short
• Torque wrench: 15-60 Ft-lbs (for use with sockets)
• Tape measure
• T-15 Torx (included)
• T-40 Torx (included)
PRIOR TO FAN INSTALLATION:
1. Ensure blade length matches fan model size.
3. Ensure all mounting hardware is present.
NATIONAL FIRE PROTECTION ASSOCIATION STANDARD
In accordance with NFPA 13 Standard from the National Fire
Prevention Association as referenced in sections 12.1.4 and
11.1.7: High Volume Low Speed (HVLS) Fans: The installation
of HVLS fans in buildings equipped with sprinklers, including
ESFR sprinklers, shall comply with the following:
• The maximum fan diameter shall be 14 feet (4.3 m).
• The fan shall be approximately centered between four
adjacent sprinklers.
• The vertical clearance from the fan to sprinkler deector
shall be a minimum of 3 feet (0.9 m).
• All fans shall be interlocked to shut down immediately
upon receiving a water ow signal from the alarm system
in accordance with the requirements of NFPA 72- National
Fire Alarm and Signaling Code.
FAN KIT
Fig. 1
Power and
communication cables
Motor assembly
with cover
Remote control Controller box
Mounting
hardware
Down
tube
Blade assemblies
Bottom cover

© Entrematic Group AB 2015
6 6020031A — Commercial HVLS Fans November 2016
HARDWARE
Fan mount
6017852 (x4)
Clamp plate
Down tube mount
6017748 (x2)
3/8-16UNC x 3-1/4" hex bolt
grade 5
serrated head
6015118 (x2)
3/8-16UNC hex nut
grade 5
serrated head
Motor mount hardware
6017838 (x4)
5/16" lock washer
6017835(x4)
5/16-18UNC x 3/4" Torx screw
grade 5
6017872 (x1)
T40 Torx wrench
Fan mount
6017873 (x4)
3/8-16UNC x 2-1/2" hex bolt
grade 5
serrated head
6015118 (x4)
3/8-16UNC hex nut
grade 5
serrated head
Blade hardware
6017837 (x10)
5/16-18UNC x 1-3/4" hex bolt
grade 5
serrated head
Bottom cover hardware
6017870 (x3)
8-32UNC x 1/4" Torx screw
6017871 (x1)
T15 Torx wrench

© Entrematic Group AB 2015
November 2016 6020031A — Commercial HVLS Fans 7
INSTALLATION CONSIDERATIONS
NOTE:
Angle mount has 45° of motion. The
extension lengths shown are minimum
recommendations only, based solely of roof
pitch and fan diameter. Other considerations
must be evaluated when determining
extension requirements, such as placement
of lights, sprinkler systems, HVAC systems,
etc. In addition, OSHA requirements state
that fan blades must be a minimum of 10'
above the oor.
Fig. 2
36" exclusion zone
(18" radius)
[both sides]
36" min.
(to wall)
10' min.
(to floor)
Do not mount directly under or within exclusion zone or
in line with HVAC supply discharge vent.
Fan Size Extension size (Ft) Max Roof Angle Allowable (degrees)
6Ft 1.5 17
6Ft 2 20
6Ft 3 35
6Ft 4 40
8Ft 1.5 10
8Ft 2 15
8Ft 3 25
8Ft 4 32
10Ft 1.5 10
10Ft 2 12
10Ft 3 19
10Ft 4 28
12Ft 1.5 8
12Ft 2 10
12Ft 3 17
12Ft 4 25
14Ft 1.5 6
14Ft 2 8
14Ft 3 15
14Ft 4 21

© Entrematic Group AB 2015
8 6020031A — Commercial HVLS Fans November 2016
INSTALLATION CONSIDERATIONS, continued
PLACEMENT AND SPACING
Consult your local distributor to help you plan the most
efcient installation of your fans.
Ensure fan placement is such that the fans blades are a
minimum of 10' from any manned working suface (oor or
mezzanine)
Ensure fan blade does not extend into exclusion zone.
Extensions are available if required. See Fig. 2.
Avoid mounting fans directly under lights or skylights to
avoid visual strobing affect.
NOTE:
If the fan is part of a networked system, ensure placement is
in accordance with the building layout.
NOTE:
Be certain to comply with all local and national codes during
installation.
For fans that will be subjected to high cross winds (open
bay doors, outdoor applications or air conditioning
diffuser ducts) the fan must be at least one fan diameter
(as measured from the end of the winglet) from open
bays or A/C ducts mounted below the blade plane or
there must be at least one fan diameter (as measured
from the end of the winglet) for A/C ducts mounted at or
above the blade plane.
In addition, all outdoor mounted fans must be protected
from exposure from the elements. Consult your local
distributor for outdoor patio applications.

© Entrematic Group AB 2015
November 2016 6020031A — Commercial HVLS Fans 9
FAN MOUNT (TYPICAL MOUNTING TYPES)
I-beam
Solid beam
Truss
Z-purlin
I-BEAM MOUNTED
See page 9 for I-beam mounting instructions.
SOLID BEAM MOUNTED
See page 9 for solid beam mounting instructions.
TRUSS MOUNTED
See page 10 for truss mounting instructions.
Z-PURLIN MOUNTED
See page 10 for z-purlin mounting instructions.

© Entrematic Group AB 2015
10 6020031A — Commercial HVLS Fans November 2016
FAN MOUNT (TYPICAL MOUNTING TYPES), continued
If building support beam is not level, ensure proper fan
clearance using the mounting information shown on
page 6 or add mounting extensions as required to ensure
clearance. See Fig 2.
I-BEAM MOUNTING
1. Locate fan centered square to the bottom ange of the
I-beam.
2. Locate and secure the clamp plates (6017852) using the
provided 3/8-16UNC hex serrated ange nuts and 3/8-
16UNC X 2 1/2" long bolts. See Fig. 3.
NOTE:
Ensure that the clamp plates overlap the I-beam ange by
at least 30%.
3. Torque the nuts to 20-28 ft-lbs.
SOLID BEAM MOUNTING
(6018175 — CONCRETE; 6018026 — WOOD)
1. Locate the beam bracket (6018108). Ensure that the
bottom ange of the bracket is below the bottom of the
beam and square to the beam.
NOTE:
The vertical ange of the beam bracket must be square with
respect to the oor. Shim as required.
2. Using the holes in the beam bracket as a template, mark
and drill at least four (4) 9/16" dia. holes through the beam.
Space the holes as widely as practical. See Fig. 4.
3. Locate both beam brackets with respect to the holes and
fasten using 3/8" dia. grade 5 bolts (not provided). Torque
to 20-28 ft-lbs. Locking hardware (nuts and washers)
required.
Do not use lag bolt style fasteners to secure the solid
beam bracket.
Fig. 3
Fig. 4