Troubleshooting Manual
18SEER Condensing & Air Handler

Troubleshooting
2
THANK YOU
Congratulations on your purchase and welcome to the Family.
Your new Air Conditioner combines high-efficiency operation with portable convenience.
By following the operating and care instructions in this manual, your air conditioner will
provide you with many years of reliable service.
Please visit our website
www.eqkhvac.com
For any questions or Technical Support,

Parameter point check table
2
TROUBLESHOOTING
1. Top discharge outdoor unit
For 18S-EHV*24WD2V, 18S-EHV*36WD2V
Function description for the corresponding position:
No. Content No. Content
1 Compressor wiring terminal 12 High/Low pressure switch ports
2 DC fan motor wiring terminal 13 AC fan motor wiring terminal
3Transformer 14 Four-way valve control port
4 Outdoor display board wiring terminal 15 Crankcase Heating zone control terminal
5 Reserved 16 Chassis Electric Heater control terminal
6 24V wire controller interface 17 Solenoid valve2 control terminal
7 EXV drive port 18 Power supply connecting terminal
8 Exhaust temperature sensor port(T5) 19 Power supply connecting terminal
9 Outdoor ambient temperature sensor port(T4) 20/21 Relay
10 Condenser temperature sensor port(T3) 22 Inductor wiring terminal 1
11 Pressure sensors ports 23 Inductor wiring terminal 2

3
TROUBLESHOOTING
For 18S-EHV*48WD2V, 18S-EHV*60WD2V
Function description for the corresponding position:
No. Content No. Content
1 Compressor wiring terminal 12 AC fan motor wiring terminal
2 DC fan motor wiring terminal 13 Four-way valve control port
3Transformer 14 Crankcase Heating zone control terminal
4 Outdoor display board wiring terminal 15 Chassis Electric Heater control terminal
5 24V wire controller interface 16 Solenoid valve control terminal
6 EXV drive port 17 Power supply connecting terminal
7 Exhaust temperature sensor port(T5) 18 Power supply connecting terminal
8 Outdoor ambient temperature sensor port(T4) 19 Relay
9 Condenser temperature sensor port(T3) 20 Relay
10 Pressure sensors ports 21 Inductor wiring terminal 1
11 High/Low pressure switch ports 22 Inductor wiring terminal 2

4
TROUBLESHOOTING
For 18S-EHV*24WD2H, 18S-EHV*36WD2H 18S-EHV*48WD2H 18S-EHV*60WD2H
Function description for the corresponding position:
No. Content No. Content
1 DC fan motor wiring terminal 8 Output port of transformer(11V)
2 Reserved 9 Dip switch to adjust fan speed
3 Chassis Electric Heater control terminal 10 Power supply connecting terminal(L1)
4 Reserved 11 Fan power cord input port(L1)
5 24V wire controller interface 12 Input power cord transformer port
6 Output port of transformer(24V) 13 Power supply connecting terminal(L2)
7 Fuse 14 Fan power cord input port(L2)
2. Air handing unit

5
TROUBLESHOOTING
Error code
(1) The error codes for outdoor unit as follows:
Definitions of malfunction Error code
T4 Outdoor ambient temperature sensor error E4
T5 Discharge temperature sensor error E5
T3 Condenser temperature sensor error E6
AC under voltage protection E9
EEPROM error E10
IPM modular sensor error E12
HLP Pressure sensor error E13
T3 or T5 sensor disconnect error E14
High pressure switch error E15
Communication error of main chip and IPM chip H0
T3 sensor high temperature error(In cooling mode, 20 times P5 error within 180mins) H1
High pressure switch error(20 times P1 error within 150 mins) H2
High pressure abnormal in heating mode (20 times P13 error within 180 mins) H3
IPM modular high temp error (20 times P8 within 120 mins) H4
Low pressure error (20 times P2 within 100 mins) H5
Discharge temperature abnormal error(20 times P4 within 100 mins) H6
Wet operation error (20 times P12 within 200 mins) H7
T3 condenser sensor disconnect error (20 times E14 within 100 mins) H8
Discharge temp sensor disconnect error(20 times E14 within 180 mins) H12
High pressure protection P1
Low pressure protection P2
DC over current protection P3
T5 Discharge temperature abnormal error P4
T3 Condenser sensor high temp protection(In cooling mode) P5
IPM module protection P6
IPM high temperature protection (Ft)M high temperature protection (Ft) P8
DC fan motor error P9
Wet operation error P12
High pressure abnormal error(In heating mode) P13

6
TROUBLESHOOTING
High compression ratio protection P14
Low compression ratio protection P15
DC cable bus low voltage protection L1
DC cable bus high voltage protection L2
MCE fault / sync / closed loop L4
Zero speed protection L5
Compressor phase loss protection ratio protection L7
Compressor stalls L8
Frequency limitation or decline by high pressure L9
Frequency limitation by voltage LA
Frequency limitation by condenser temp. LC
Frequency limitation by discharge temp LD
Frequency limitation by IPM modular high temp LE
Frequency limitation by current LF
Oil return d0
Defrost dF
Force cooling dH

7
TROUBLESHOOTING
(2) Troubleshooting by error code
E4/E5/E6 (T4/T5/T3 temperature sensors error)
Diagnosis Handling
T5/TP T4 T3
E10 (EEPROM failure)
Diagnosis Handling
Check the connection
between the sensor and PCB
The sensor should be
connected firmly and correctly
Error
Check if the sensor is damaged
OK
Replace with a new sensor, and insert
it in the corresponding position
Yes
Replace the main board
No
Power off and re-power on to
see whether it is normal
If there is still abnormal
replace the mainboard

8
TROUBLESHOOTING
E9 ( AC under voltage protection )
Diagnosis Handling
E12 (IPM modular sensor error)
Diagnosis Handling
The power supply wire should
be connected firmly and correctly
Check if the power supply
wire is reliably connected
Check if the wire diameter meets
the requirements in the manual
Yes
Replace the power cord
to the right diameter
Check if the compressor
wiring is correct
Yes
The power supply
wire interface
It should be connect correctly
according to the wiring diagram
Yes
If there is still abnormal
replace the mainboard
No
Power off and re-power on to
see whether it is normal
The compressor
wire interface
No
No
No
Power off and re-power on to
see whether it is normal
If there is still abnormal
replace the mainboard

9
TROUBLESHOOTING
E13 (HLP Pressure sensor error)
Diagnosis Handling
E14/H8/H12 (T3 or T5 sensor disconnect error )
Diagnosis Handling
Check the connection
between the sensor and PCB
The sensor should be
connected firmly and correctly
Error
Measure the value of outdoor
unit pressure sensor
Compare it with the pressure
value of the pressure gauge
OK
If the difference is large,
replace with a new sensor, and
weld in the correct position
If the difference is small,
replace the mainboard
The pressure sensor should be
soldered in the correct position
Check the connection
between the sensor and PCB
The sensor should be
connected firmly and correctly
Error
OK
Replace the sensor