SIGA-CT1 Single Input Module Installation Sheet
Description
The SIGA-CT1 Single Input Module is an addressable device
used to connect a Class B initiating device circuit (IDC) to a
Signature loop controller.
The module requires one address on the signaling line circuit
(SLC). Addresses are assigned electronically. There are no
address switches.
Diagnostic LEDs provide visible indication of the state of the
module:
•Normal: green LED flashes
•Alarm/active: red LED flashes
Personality codes
The module requires the loop controller to download a
personality code that determines how the module operates.
Personality codes determine the operation of the circuit and
whether the activation is latched or not. Table 1 lists the
personality codes available for this module.
Table 1: Personality codes
Code
Description UL/ULC EN 54-18
1
Alarm – NO latching (Class B) (default) P
2
Alarm – NO delayed latching (Class B) P
3
Active - NO nonlatching (Class B) PP
4
Active - NO latching (Class B) PP
18
Alarm - soft short latching, European
Style C (Class B)
P
Installation
Install this device in accordance with applicable requirements
of the latest editions of the local codes and standards and the
local authority having jurisdiction.
Notes
•The module is shipped from the factory as an assembled
unit; it contains no user-serviceable parts and should not
be disassembled.
•This module does not operate without electrical power. As
fires frequently cause power interruption, discuss further
safeguards with the local fire protection specialist.
•This module does not support conventional smoke
detectors.
To install the module:
1. Write the address assigned to the module on the label
provided, and then apply the label to the module. Remove
the serial number label from the detector, and then attach
it to the project documentation.
2. Wire the module as shown in “Wiring” on page 2.
3. Using the self-tapping screw provided, mount the wall
plate to the module. Refer to Figure 1.
4. Using the two machine screws provided, mount the wall
plate (with the module attached) to one of the compatible
electrical boxes listed in “Specifications” on page 2.

2 / 4 P/N 387021P-EN • REV 12 • ISS 23JUL13
Figure 1: Mounting the SIGA-CT1 module
(1) Compatible electrical box
(2)
SIGA-CT1 module
(3) Wall plate, white (single-gang)
(4) #6-32 × 5/8 in. (16 mm) screw
(5)
#4 × 1/2 in. (13 mm) screw
Wiring
Wire in accordance with applicable requirements of the latest
editions of the local codes and standards and the local
authority having jurisdiction.
Note: When stripping wire ends, exposing more wire may
cause a ground fault; exposing less wire may result in a faulty
connection.
To wire the module:
1. Verify that all field wiring is free of opens, shorts, and
ground faults.
2. Strip 1/4 in. (about 6 mm) from the ends of all wires that
connect to the terminal block of the module.
3. Make all wiring connections as shown in Figure 2.
Notes
•Refer to the Signature loop controller installation sheet for
SLC wiring specifications for additional details.
•All wiring is power-limited and supervised.
•A test resistor is supplied with the SIGA-CT1 to prevent
trouble signals on unused circuits during installation.
When connecting field wires, remove the test resistors and
install a UL/ULC Listed 47 KΩ EOLR at the end of the
circuit.
Figure 2: Wiring diagram
(1) EOL resistor (PN EOL-47)
(2)
22 kΩ resistor for use with
personality code 18
(3)
Typical NO initiating device
(4)
Max. 10 VDC @ 350 µA
(5) Red LED (alarm/active)
(6) Green LED (normal)
(7)
Signaling line circuit (from
previous device)
(8)
Signaling line circuit (to next
device)
Specifications
Operating voltage
15.20 to 19.95 VDC
Current
Standby
Activated
300 µA
450 µA
Ground fault impedance
10 kΩ
Initiating device circuit (IDC)
EOL resistor value
Circuit resistance
Circuit capacitance
47 kΩ, UL/ULC Listed
50 Ω (25 Ω per wire), max.
0.1 µF max.
Circuit designation
Signaling line circuit
Notification line circuit
Class A, Style 6 or Class B, Style 4
Class B, Style B
Wire sizes
12 to 18 AWG wire (0.75 to 2.5 mm²)
Compatible electrical boxes
2-1/2 in. (64 mm) deep single-gang
box; 4-in. square box 1-1/2 in (38 mm)
deep with single-gang cover
LPCB/CPD electrical box
Requirements
Minimum (W × H × D)
Plastic box with cover plate, no gaps or
unused holes
2.4 × 3.5 × 1.5 in. (60 × 85 × 38 mm)
Ope
rating environment
Temperature
Relative humidity
32 to 120°F (0 to 49°C)
0 to 93%, noncondensing
Storage temperature range
−4 to 140°F (−20 to 60°C)
(1)
(2) (3)
(4)
(4)
(5)
7
8
12
3
4
+ +
– –
(1)
(3)
(4)
(6)
(8)(7)
(5)
(2)
(4)
(1)
(3)

P/N 387021P-EN • REV 12 • ISS 23JUL13 3 / 4
Regulatory information
Manufacturer
Edwards, A Division of UTC Fire & Security
Americas Corporation, Inc.
8985 Town Center Parkway, Bradenton, FL
34202, USA
Authorized EU manufacturing representative:
UTC Fire & Security B.V.
Kelvinstraat 7, 6003 DH Weert, Netherlands
Year of
manufacture
The first two digits of the DATE MFG number
(located on the product identification label) are
the year of manufacture.
North American
standards
CAN/ULC-S527, UL 864
, UL 1638, CE; FCC Part
15, Subpart J, Class B; DOCClass/MDC class B
FCC compliance
This device complies with part 15 of the FCC
Rules. Operation is subject to the following two
conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any
interference received, including interference that
may cause undesired operation.
EU compliance
LPCB
EN 54-18: 2005 Input/output devices
CPD certificates
0832-CPD-1019
LPCB reference
262y/08
2002/96/EC (WEEE directive): Products marked
with this symbol cannot be disposed of as
unsorted municipal waste in the European Union.
For proper recycling, return this product to your
local supplier upon the purchase of equivalent
new equipment, or dispose of it at designated
collection points. For more information see:
www.recyclethis.info.
Contact information
For contact information, see www.est-fire.com.

4 / 4 P/N 387021P-EN • REV 12 • ISS 23JUL13
Altri manuali EST Sistema I/O
Manuali Sistema I/O popolari di altre marche

WAGO
WAGO 750-344 Manuale utente

Teknim
Teknim TWM-1887 Manuale di istruzioni

Intelligent Appliance
Intelligent Appliance IA-2662-E Manuale utente

BERGHOF
BERGHOF ECC DIO 16/16 Manuale di istruzioni

Advantech
Advantech PCM-27J3AU Manuale di installazione e funzionamento

Festo
Festo CP-E08-M12-CL Manuale utente