General information
3
1 General information
Support for cleaning and maintenance
This document provides support for cleaning and
maintaining the product. The required steps are listed
in detail here.
Take note of the date of the cleaning or maintenance
and any faults that may have occurred. This facilitates
troubleshooting for the expert (system operator,
heating technician...).
For services (such as commissioning, mainte-
nance, fault fixing) provided by ETA customer
service, the service reports are provided in digital form.
For clarity, you should staple these reports to this
document or enclose them.
Commissioning data
Enter the manufacturing number of the product
(printed on the type plate), the date of commissioning
as well as the heating technician who commissioned
the system.
Copyright
All contents of this document are property of ETA
Heiztechnik GmbH and are protected by copyright.
Any reproduction, transfer to third parties or use for
other purposes is prohibited without written permission
from the owner.
Subject to technical changes
We reserve the right to make technical modifications
without notice. Printing and typesetting errors or
changes of any kind made in the interim are not cause
for claims. Individual configurations depicted or
described here are only available optionally. In the
event of contradictions between individual documents
regarding delivery scope, the information in our current
price list applies.
Explanation of symbols
Instructions and information
Layout of safety instructions
SIGNAL WORD!
Type and source of danger
Possible effects
• Measures for avoiding the danger
Types of safety instruction
CAUTION!
On non-compliance with this safety instruction, there is
a risk of material damage.
WARNING!
On non-compliance with this safety instruction, there is
a risk of physical injury.
DANGER!
On non-compliance with this safety instruction, there is
a risk of major physical injury.
Commissioning data
Manufacturing number:
________________________________________
Commissioned on:
_________________________________________
Commissioned by (company):
_________________________________________
_________________________________________
_________________________________________

4 www.eta.co.at
Maintenance notes Cleaning and maintenance
2 Cleaning and maintenance
2.1 Maintenance notes
Performing regular cleaning and maintenance
To ensure satisfactory functionality, cleaning and
maintenance must be performed at regular intervals.
You will receive a timely reminder about this from the
ETAtouch control system.
Cleaning of the boiler must be carried out at least
once a year, or when requested by the control
system. Maintenance is necessary at least every
3 years, or when requested by the control system. We
recommend that you perform maintenance annually.
You can also enter into a service agreement for your
heating system. Find out more from your heating
contractor or customer service.
All tasks where the maintenance table reads
"Customer" or "Customer or expert" in the column
"To be carried out by" can be carried out by any trained
adult. Instruction may be provided by the heating
technician or our customer service.
Steps that are marked with "Expert" only can only be
carried out by the heating technician or our customer
service.
Operation only by trained personnel
The product may be operated by trained adults only.
Training may be provided by the heating technician or
our customer service. Please read the associated doc-
umentation carefully in order to avoid errors during
operation and maintenance.
Persons who lack experience and knowledge as well
as children may not operate, clean, or maintain the
product.
Display maintenance steps on the screen
With this boiler, the maintenance steps can also be
displayed on the ETAtouch control system screen. The
required activities will be explained to you step-by-step
and supplemented with detailed graphics. Each
maintenance is saved and the details can be viewed at
any time. So you can maintain a long-term overview of
the maintenance carried out. Of course, the
maintenance can also be carried out using the service
guide, without the support of the ETAtouch control
system.
To access maintenance, switch to settings in the boiler
function block ( [Settings] button) and then select
the function [Maintenance].
Fig. 2-1: Overview (example)
You can also access this overview by pressing
the maintenance switch. Also when the message
appears that maintenance of the boiler is required.
In the overview the different maintenance intervals are
listed in the upper area. This includes the maintenance
already carried out. With the button, information
about the selected maintenance is displayed.
Maintenance that you can carry out as an end
customer is labelled with the symbol. All others are
reserved for specialists and require authorisation.
Press the button to start the maintenance. The
individual steps are displayed on the screen. You can
switch to the next or the previous screen respectively
with the arrow keys on the left and right side of the
screen.
Fig. 2-2: Maintenance step (example)

Cleaning and maintenance Maintenance notes
5
Follow the on-screen instructions and carry out all
steps carefully. Enter your name at the end of
maintenance ( button) and save the maintenance
with the button.
Fig. 2-3: End of maintenance
To end maintenance prematurely, press the right
arrow key several times until you get to the end.
There you can end the maintenance with the
button. Cancellation during a maintenance step is not
possible.
Explanation of the maintenance switch
The maintenance switch on the boiler is needed for
performing maintenance with the aid of the [Main-
tenance] function in the ETAtouch control system. This
displays the individual maintenance steps on the boiler
screen.
With this variant the heating mode is stopped, but
the boiler remains on at the mains switch. So that
all drives are disconnected, the safety chain of the
boiler is disrupted with the maintenance switch. The
screen will display a message when it is time to actuate
the maintenance switch.
Fig. 2-4: Maintenance switch
The maintenance switch is marked with the
symbol and has two settings.
•"1" = regular operation
This is the standard position of the maintenance
switch. The boiler can execute heating mode in this
position.
•"0" = maintenance mode
In this position, all drives are disconnected to
perform maintenance. The circuit boards,
however, are still live.
Explanation of pictograms
Switch the boiler on/off with the mains
switch.
Perform a visual check of the components.
Clean the components with a soft cloth, for
example.
Remove deposits with a vacuum cleaner or
an ash vacuum.
Remove deposits with the poker.
Remove deposits with the cleaning brush.
Replace the wear parts (e.g., seals) with new
items.
Lubricate the components. The lubricant to
use is listed in the respective step.
Mount the components (e.g., screws or nuts)
by hand only, without tools.
Tighten the components (e.g., screws or
nuts) with a tool.
Install the components with some force (e.g.,
the retaining tube or the Lambda probe).
Handle the components carefully, since they
break very easily.
Measure or check dimensions or clearances
on the components.
Mark the components so that the correct
position can be found, for example, when
mounting.

6 www.eta.co.at
Maintenance notes Cleaning and maintenance
Clean panels
If necessary, clean the panels of the boiler and the
ETAtouch screen with a moist cloth.
Under no circumstances use aggressive
solvents, chemicals or scouring agents. They can
lead to stress cracks and damage.
Wear a protective mask to avoid injuries to
the airways.
Seal the components. The sealant to use is
listed in the respective step.
Use adhesive to affix the seals, for example.
Only blow out the components with your
mouth.
Affix a seal. The required cross-section and
sealing material are given at each step.
Tighten the screws or nuts alternately and
evenly.
Do not use compressed air to clean the
components.
Do not use cleaning brushes to clean the
components.
Do not use an ash vacuum or vacuum
cleaner.
Do not lubricate the components.
No water or moisture in this area.
No leaks in the components, e.g. screw
connection or maintenance cover.

Cleaning and maintenance Maintenance notes
7

8 www.eta.co.at
Maintenance openings in the boiler Cleaning and maintenance
2.2 Maintenance openings in the
boiler
Maintenance openings and components
1 Heat exchanger cover
2 Fill level sensor for pellet hopper
3 Vacuum turbine for pellet transport
4 Firebed switch
5 Stoker drive chain
6 Actuator for secondary air
7Ignition
8 Maintenance cover of the combustion chamber
9 Position switch for ash box

Cleaning and maintenance Maintenance openings in the boiler
9
1 Safety valve
2 Draught fan
3 Lambda probe
4 Water pressure sensor
5 Filling and draining valve
6 Actuator for primary air
7 Drive chain for de-ashing
8 Grate drive chain

10 www.eta.co.at
Maintenance table Cleaning and maintenance
2.3 Maintenance table
Clean the boiler at least once per year, or when requested by the control system. Maintenance is necessary at
least every 3 years, or when requested by the control system. We recommend you perform maintenance
annually.
Tasks Regular
ly
Cleaning
annually
Maintenan
ce
at least
every 3
years
to be
performed by
Empty the ash box
• Empty the ash box
• Check seals
X X X Customer
Check the pressure of the heating system X X X Customer
Check the safety devices
• Visual check of the safety valves
• Visual check of the thermal relief valve
X X Customer or
specialist
Chimney
• Clean the flue tube
• Flush the chimney's condensate drain
X X Customer or
specialist
Clean the combustion chamber
• Clean inside of the secondary combustion chamber
• Clean the inner walls of the combustion chamber
• Clean the ignition tube
• Check the movability of the firebed switch
• Check seal on the maintenance cover
X X Customer or
specialist
Clean the draught fan XSpecialist
Clean the temperature sensor XSpecialist
Clean the heat exchanger
• Clean the topside of the heat exchanger
• Check the heat exchanger tubes
• Clean the lambda probe
• Check seal on heat exchanger cover
XSpecialist
Check the combustion chamber
• Checking the firebed lever and firebed switch
• Dismantle the ignition and clean the ignition tube
XSpecialist
Check the pellet hopper
• Clean the fill level sensor
• Clean the strainer
XSpecialist
Check the stoker unit
• Check the stoker drive chain XSpecialist
Check the drive chains
• Check the grate drive chain
• Check the de-ashing drive chain
XSpecialist
Check the air valves for primary and secondary air XSpecialist
Checking the ash box position switch XSpecialist
Calibrate the lambda probe XSpecialist
Reset the maintenance counter XSpecialist
Indice
Altri manuali eta Caldaia

eta
eta HACK Guida rapida

eta
eta SH Touch Manuale utente

eta
eta PelletsCompact Guida rapida

eta
eta SH20 Manuale di istruzioni

eta
eta SH Manuale utente

eta
eta eHACK 80 Manuale utente

eta
eta ePEK 140 Manuale di istruzioni

eta
eta ePE-K Manuale utente

eta
eta HACK Manuale utente

eta
eta HACK 20 Manuale di istruzioni

eta
eta ePE-K 100-130 kW Manuale utente

eta
eta 13180 LP-D Manuale utente

eta
eta PE-K 180 Manuale di istruzioni

eta
eta ePE-K 140 Manuale utente

eta
eta eHACK 180 Manuale utente

eta
eta PE-K Manuale utente

eta
eta 110 Manuale utente

eta
eta VR 250 Manuale utente

eta
eta Hack 200 kW Manuale utente

eta
eta eHACK 20-50 kW Manuale utente