Hoval TopVent TV Manuale utente

TopVent®TV
Recirculation unit for heating
spaces up to 6 m in height
Original operating manual
Art.No. 4 216 284-en-01 / Page 1
TopVent®TV
Design, installation and operation

1 Use 3
1.1 Intended use 3
1.2 User group 3
2 Safety 4
2.1 Symbols 4
2.2 Operational safety 4
3 Construction and operation 5
3.1 Unit construction 5
3.2 Operating modes 6
4 Technical data 7
4.1 Application limits 7
4.2 Flow rate, product parameters 7
4.3 Heat output 7
4.4 Sound data 8
4.5 Dimensions and weights 8
4.6 Specication texts 8
5 Transport and installation 9
5.1 Delivery 9
5.2 Requirements for the installation site 9
5.3 Installation 10
5.4 Hydraulic installation 11
5.5 Electrical installation 12
6 Operation 15
6.1 Initial commissioning 15
6.2 Operation 15
7 Maintenance and repair 16
7.1 Safety 16
7.2 Maintenance 16
7.3 Repair 16
8 Dismantling 17
9 Disposal 17
Art.No. 4 216 284-en-01 / Page 2
TopVent®TV
Content

1 Use
1.1 Intended use
TopVent® TV units are recirculation units intended for heating spaces up to 6 m in
height. They have the following functions:
■ Heating (with connection to a hot water supply)
■ Recirculation operation
■ Air distribution via air outlet louvre
Intended use also includes compliance with the operating instructions. Any usage
over and above this use is considered to be not as intended. The manufacturer
can accept no liability for damage resulting from improper use.
1.2 User group
The units are only allowed to be installed, operated and maintained by authorised
and instructed personnel who are well acquainted with the units and are informed
about possible dangers.
The operating instructions are for operating engineers and technicians as well as
specialists in building, heating and ventilation technology.
TopVent®TV
Use
Art.No. 4 216 284-en-01 / Page 3

2 Safety
2.1 Symbols
Caution
This symbol warns against risk of injury. Please heed all instructions desig-
nated by this symbol to prevent injuries and/or death.
Attention
This symbol warns against property damage. Please heed the respective
instructions to prevent risk of damage to the unit and its functions.
Notice
This symbol denotes information about the economic use of the equipment
or special tips.
2.2 Operational safety
The unit is built to conform to the state-of-the-art and is operationally safe.
Despite every precaution being taken, potential and not immediately obvious risks
always remain, for example:
■ Dangers when working with the electrical system
■ Parts (e.g. tools) can fall down below when working on the ventilation unit.
■ Malfunctions as a result of defective parts
■ Hazards from hot water when working on the hot water supply
Therefore:
■ Please read the operating instructions before unpacking, installing, commis-
sioning and before maintaining the equipment.
■ Store the operating instructions so that they are easily accessible.
■ Observe any attached information and warning signs.
■ Immediately replace damaged or removed informational and warning signs.
■ Follow the local safety and accident prevention regulations at all times.
■ Disconnect the power supply and wait at least 5 minutes before opening the
unit.
■ When working in the unit, take precautions against unprotected, sharp metal
edges.
■ The unit may only be installed, operated and serviced by authorised, trained
and instructed skilled personnel:
– Specialists as dened by these operating instructions are those persons
who, based on their training, knowledge and experience as well as their
knowledge of the relevant regulations and guidelines, can carry out the work
assigned to them and recognise potential hazards.
■ Unauthorised reconguration or modication of the unit is not permitted.
TopVent®TV
Safety
Art.No. 4 216 284-en-01 / Page 4

3 Construction and operation
The TopVent® TV is used to heat in recirculation operation; it was developed
specially for use in rooms up to 6 m in height. The unit is installed on the wall or
under the ceiling. It takes in room air, heats it in the heating coil and blows it back
into the room through the air outlet louvre.
There are 3 unit sizes, which are each equipped with an innitely variable fan and
a custom-made heating coil.
3.1 Unit construction
The TopVent® TV consists of the following components:
■ Heat exchanger consisting of copper tubes and aluminium ns
■ Axial fan with energy-saving EC motor and ow-optimised fan blades, innitely
variable, maintenance-free and quiet with a high degree of efciency
■ Compact casing in modern industrial design, consisting of high-quality ABS,
robust and easy to clean
■ Suspension set for installing the unit on the ceiling or the wall
■ Air outlet louvre with vanes for manual adjustment of air distribution
Suspension set
Fan
Casing
Heat exchanger
Air outlet louvre
Fig. 1: Unit construction
TopVent®TV
Construction and operation
Art.No. 4 216 284-en-01 / Page 5

3.2 Operating modes
The TopVent® TV operates in on/off mode. The EasyTronic EC room temperature
controller regulates the operation of the unit.
EasyTronic EC
The EasyTronic EC is a simple room temperature controller without a timer. A
maximum of 10 TopVent® units can be connected to 1 controller.
Functions
■ Recording the room temperature with the integrated temperature sensor
■ Room temperature control in on/off mode: If the room temperature falls below
the setpoint value, the connected TopVent® units switch on. Upon reaching the
setpoint value, the units switch off again.
■ Controlling the TopVent® units using a door contact switch: The connected units
are switched on via door contact if the door is open (digital input).
■ Controlling the fan speed: The required speed can be innitely controlled.
■ Pump or valve control: The EasyTronic EC provides a signal for switching a
pump or a valve (digital output).
Fig. 2: EasyTronic EC room temperature controller
Technical data
Electrical supply
110…230 VAC, ±10%, 50/60 Hz
Power consumption max. 1.3 W
Temperature range 0...50 °C
Protection rating IP 30, class 2
Dimensions (W x H x D) 128 x 80 x 56 mm
Installation In a 3-gang ush-mounted box
or on the supplied base
Table 1: Technical data of the EasyTronic EC
TopVent®TV
Construction and operation
Art.No. 4 216 284-en-01 / Page 6

4 Technical data
4.1 Application limits
Maximum operating pressure 1600 kPa
Maximum heating medium temperature 90 °C
Maximum supply air temperature 60 °C
Maximum extract air temperature 50 °C
The units cannot be used in:
■ Areas where there is danger of explosion
■ Places with a corrosive or aggressive environment
■ Damp locations
■ Spaces with a large amount of dust
Table 2: Application limits
4.2 Flow rate, product parameters
Type TV-2 TV-4 TV-5
Nominal air ow rate m³/h 2100 4850 5700
Power consumption kW 0.10 0.25 0.37
Current consumption
A
0.51 1.30 1.70
Supply voltage
VAC
230 230 230
Frequency Hz 50 50 50
Max. mounting height m5.5 5.5 5.5
Max. horizontal reach m14.0 22.0 25.0
Table 3: Technical data
4.3 Heat output
Temperature of the
heating medium
80/60 °C 60/40 °C
Type troom Q tS∆pWmWQ tS∆pWmW
°C kW °C kPa l/h kW °C kPa l/h
TV-2 15 13.9 34.8 6.7 610 8.3 26.6 3.2 360
20 12.6 37.9 5.6 560 6.8 29.7 2.3 300
TV-4 15 33.5 35.6 11.5 1480 19.4 26.9 4.8 850
20 30.3 38.6 9.5 1340 15.9 29.8 3.5 700
TV-5 15 50.2 41.3 15.7 2220 29.2 30.3 6.5 1280
20 45.4 43.8 13.0 2000 23.9 32.5 4.7 980
Legend: troom = Room air temperature
Q = Heat output
tS = Supply air temperature
∆pW = Water pressure drop
mW = Water quantity
Table 4: Heat output
TopVent®TV
Technical data
Art.No. 4 216 284-en-01 / Page 7

4.4 Sound data
Type TV-2 TV-4 TV-5
Sound pressure level (at a distance of 5 m) 1) dB(A)
50 54 56
Total sound power level
dB(A)
72 76 78
1) Reference: room volume 1500 m³
Table 5: Sound levels
4.5 Dimensions and weights
A C
D
A
B
Type TV-2 TV-4 TV-5
A mm 530 700 700
Bmm 381 550 550
Cmm 517 610 610
Dmm 395 425 425
Water content of the coil l1.12 2.16 3.10
Connection (external thread) "R ¾ R ¾ R ¾
Weight kg 16.2 23.0 24.4
Table 6: Dimensions and weights
4.6 Specification texts
TopVent®TV – Recirculation unit for heating spaces up to 6 m in height
Sturdy casing made of ABS with pigment additive for UV protection, front in
RAL 9016 (Trafc white) and back in RAL 7037 (Dusty grey); heat exchanger
consisting of copper tubes and aluminium ns; axial fan with highly efcient EC
motor, innitely variable, maintenance-free and quiet, protection rating IP 44,
insulation class F; rear-mounted terminal box; air outlet louvre with vanes for
manual adjustment of air distribution; including suspension set for wall or ceiling
installation.
Return
Flow
TopVent®TV
Technical data
Art.No. 4 216 284-en-01 / Page 8

5 Transport and installation
Caution
Risk of injury from incorrect handling. Transport, assembly and installation
work may only be performed by specialists. Observe safety and accident
prevention regulations.
5.1 Delivery
TopVent® TV units are packed in cardboard boxes and delivered on a pallet.
■ The scope of delivery includes:
– Recirculation unit heater
– Suspension set
– Accessories for installation
■ Ensure that the unit is undamaged.
■ Report any missing parts, wrong deliveries and possible transport damage
immediately in writing.
5.2 Requirements for the installation site
■ Position the units according to the system layout. Comply with the minimum
and maximum distances.
■ All air inlet and air outlet openings must be freely accessible. The supply air jet
must be free to spread out unhindered.
X
Y
X
≥
0.4 m
Y
Size TV-2 TV-4 TV-5
Distance X m3 … 7 6 … 12 6 … 12
Distance Y m2.5 … 5.5 2.5 … 5.5 2.5 … 5.5
Minimum distance to the ceiling/wall m0.4 0.4 0.4
Table 7: Minimum and maximum distances
Fig. 3: Examples of unit arrangement for wall installation (top view)
TopVent®TV
Transport and installation
Art.No. 4 216 284-en-01 / Page 9

5.3 Installation
Caution
Risk of injury caused by falling load and improper handling. During
installation:
–
Wear protective equipment (fall protection, safety helmet, safety shoes).
– Do not stand under suspended loads.
– Use cranes or forklifts with sufcient load-bearing capacity.
Preparation
■ Make sure that the following items are on hand for the assembly:
– Installation platform
– Drill Ø 16 mm
– Socket wrench, width 17
– Socket or open-end wrench, width 13
Installation
■ Install the retaining bracket:
– Cut 1 opening at the top and at the bottom of the casing with the drill (Ø
16 mm, see in Fig. 5).
– Insert the assembly bush into the top opening.
– Position the retaining bracket over the openings.
– Insert M10 screws into the bushes.
– Turn the retaining bracket to the desired position in relation to the unit.
– Tighten the screws to secure the position.
– Place the plugs on the retaining bracket.
■ Install both mounting angles with the M8 screws onto the retaining bracket.
– 3 different inclination angles can be used.
■ Install the unit on the wall or on the ceiling (on-site fastening material).
– Use the packaging box as a drilling template.
± 60°
Fig. 4: Angle of rotation, left/right 60°
M8 screw with spring washer, nut
and washers (2 sets)
Mounting angles (x2)
Retaining bracket
M10 screw (x2)
Plug (x2)
Assembly bush
Opening
Fig. 5: Unit installation
TopVent®TV
Transport and installation
Art.No. 4 216 284-en-01 / Page 10