Huawei SmartLogger2000-10-B-JP Manuale utente

HUAWEI TECHNOLOGIES CO., LTD.
SmartLogger2000-10-B-JP
Quick Guide (Japan)
Issue: 03
Part number: 31507917
Date: 2019-06-30

No.
Port (Silk
Screen
)
Function
Description
1
RF1, RF2
Reserved
Reserved.
2
12V
OUT
12 V DC output
Provides 12
V DC power supply with a maximum
current
of 100 mA.
3
12V
IN
12 V DC input
Connects
to the power adapter.
4
USB
USB port
Connects a USB flash drive.
5
SFP1, SFP2
Ethernet optical
port
Connects
to an ATB or another cascaded
SmartLogger
.
6
ETH1, ETH2
Ethernet electrical
port
Connects to an Ethernet LAN switch,
router or
PC
device.
7
DO
Digital output (DO)
Relay output.
1
1Overview
Port Description
1.2
1. The information in this document is subject to change without notice. Every effort has been
made in the preparation of this document to ensure accuracy of the contents. However, all
statements, information, and recommendations in this document do not constitute a warranty of
any kind, express or implied.
2. Before installing the device, carefully read the SmartLogger2000 User Manual to get familiar
with the product information and precautions. SmartLogger is short for SmartLogger2000-10-B-
JP in the following text.
3. Install and use the device according to this document and the user manual. Otherwise, the
device may be damaged. Use insulated tools when installing the device.
4. This section describes the installation and cable connection operations using the SmartLogger
applied in the non-SmartACU2000 smart array controller (smart array controller for short)
scenario as an example.
Copyright © Huawei Technologies Co., Ltd. 2019. All rights reserved.
Model
PLC (MBUS) Module
Configured?
Remarks
SmartLogger2000
-10-B-JP
Yes
The built
-in Bluetooth module supports
both Android APP and IOS APP.
Model Description
1.1

No.
Port (Silk
Screen
)
Function
Description
8
COM1
–COM6
RS485
communications
Six RS485 ports that can be connected to devices
such
as the inverter, cubicle, electricity meter, or EMI.
9
Default
Default key
Resets and restarts the Bluetooth module or resets
the
SmartLogger IP address to the default IP address
(
valid within 5 minutes). The default IP address is
192.168.0.10.
10
AC1, AC2
AC power cable
ports
Connects to A, B, and C three
-
phase inputs, and used
for
power line communication (PLC/MBUS) with the
inverter
. If PLC (MBUS) function is not used, you do
not have to connect cables to these ports.
11
Shell
grounding
N/A
12
AI1
–AI8
Analog input (AI)
AI1: 0
–10 V input voltage (passive); AI2–AI4: 4–
20 mA
and 0
–20 mA input current (passive); AI5–AI8: 4–20
mA and 0
–20 mA input current (active)
13
AO1
–AO6
Analog output
(AO)
4
–20 mA, 0–20 mA current output.
14
DI1
–DI8
Digital input (DI)
Connects to a dry contact input
.
2Typical Cable Connection Scenarios
2
2.1
2.1 Non-Smart Array Controller Scenario
2.1
1. If the SmartLogger communicates with an inverter over an AC power cable, three fuses, and a
3P3E switch need to be installed to prevent device damage in the case of short circuits.
2. If the SmartLogger communicates with an inverter over an AC power cable, the cable from the
3P3E switch to the fuses and the cable from the busbar to the fuses both need to be prepared
by the customer. Recommended cable: three-core armor cable with the operating voltage to the
ground greater than or equal to 600 V and the cross-sectional area of a single core wire being 4
mm2.
3. The power cable delivered with the SmartLogger is 1 meter long, the power adapter cable is 1.5
meters long, the network cable is 2.2 meters long, and the AC power cable is 1.5 meters long.
Reserve the installation positions for components based on the cable lengths.

2Typical Cable Connection Scenarios
3
RS485/PLC (MBUS) +Optical Fiber
Component
Recommended Model or
Specifications
Component Source
Quantity
SmartLogger
SmartLogger2000
Purchased from Huawei
1 PCS
RS485 signal
SPD
X4B
-05
Purchased from Huawei
3 PCS
ATB
CT
-GZF2PJ-8 or CT-GPH-A-8
Purchased from Huawei
1 PCS
Fuse
Rated voltage ≥
500 V; rated
current: 6 A
Prepared by the
customer
3 PCS
3P3E switch
The switch has a rated insulation voltage
of 600 V, a rated current of 15 A, and
three poles. Kawamura NX53E
-15W
switch is recommended.
Prepared by the
customer
1 PCS
Socket
Connects to the power
adapter
Prepared by the
customer
1 PCS
Smart Array Controller Scenario
2.2
The following describes the application scenario where the SmartLogger is inside the smart array
controller SmartACU200-C-A or SmartACU2000-C-A-PID.
NOTE

4
1. The general input power cable for the smart array controller needs to be prepared by the
customer. Recommended cable: four-core armor cable with the operating voltage to the ground
greater than or equal to 600 V and the cross-sectional area of a single core being 4 mm2
2. If the SmartLogger communicates with an inverter over an AC power cable, the cable from the
3P3E switch to the fuses and the cable from the busbar to the fuses both need to be prepared
by the customer. Recommended cable: three-core armor cable with the operating voltage to the
ground greater than or equal to 600 V and the cross-sectional area of a single core wire being 4
mm2.
3. The SmartLogger and the three RS485 signal surge protective devices (SPDs) used by the
SmartLogger have been installed before delivery.
4. The SmartLogger PGND cable, AC power cable, power adapter and its power cable, and the
communications cable between the SmartLogger and the RS485 signal SPD have been
installed before delivery.
5. The PID module and inductor are configured only in the smart array controller (with a PID
module) and have been installed before delivery.
RS485/PLC (MBUS) +Optical Fiber

Component
Recommended Model or
Specifications
Component
Source
Quantity
P
ID module
P
ID01
Factory
-installed
1 PCS
PID inductor (working
with the PID module)
EIFI50ohm
Factory
-installed
1 PCS
SmartLogger
SmartLogger2000
Factory
-installed
1 PCS
RS485 signal SPD
SPM01A
Factory
-installed
3 PCS
ATB
CT
-GZF2PJ-8 or CT-GPH-A-8
Purchased
from
Huawei
1 PCS
Fuse
Rated voltage ≥
500 V; rated
current: 6 A
Prepared by
customer
3 PCS
3P3E switch
The switch has a rated insulation voltage of
600 V, a rated current of 15 A, and three
poles. Kawamura NX53E
-15W switch is
recommended.
Prepared by
customer
1 PCS
Installation Space (Unit: mm)
3.1
3Installing the SmartLogger
Chassis dimensions (including mounting ears)
Installation clearances
Installation clearances
Wall-mounting
Guide rail-mounting
Chassis dimensions
(including the guide rail mounting brackets)
5

6
Install the SmartLogger on a wall that is flat and has the bearing capacity to securely hold the
SmartLogger which weighs 3800 g.
Wall-mounting
Installation Mode
3.2
1. Determine mounting holes
based on the hole positions
in the mounting ears, and
mark the mounting holes
using a marker.
If you need to use a ladder to install the device on a high position, take measures to protect
yourself from falling down.
2. Drill holes by using a hammer drill and install expansion sleeves, washers, and tapping screws.
Unit: mm
Screw assembly for wall-mounting:
(1) ST3.5 tapping screw
(2) Washer
(3) Expansion sleeve
Unit: mm
3. Put the tapping screws through the SmartLogger mounting ears and washers into the mounting
holes in the wall.

Guide rail-mounting
Huawei does not provide the SmartLogger guide rail. If the customer chooses this installation mode,
the customer must prepare a 35 mm standard guide rail.
Unit: mm
1. Remove the mounting ears from the
SmartLogger using a Phillips screwdriver. 2. Secure the guide rail clamps using M4x8
screws removed from the mounting ears, and
tighten the screws to a torque of 1.2 N·m.
1. Secure the guide rail before mounting the
SmartLogger.
2. Verify that the length of the guide rail is
sufficient for securing the SmartLogger.
The recommended length is 450 mm or
greater.
7
4. Tighten the tapping screws to a torque of 0.3 N·m using a torque screwdriver.
NOTE

8
5Installing Ground Cable
3. Mount the SmartLogger onto the guide rail. 4. Install the guide rails fastener using M4x12
screws, and tighten the screws to a torque
wrench of 1.2 N·m.
4Installing the RS485 SPD
Installing the SmartLogger Ground Cable
5.1
1. The SmartLogger provides six COM ports. To connect a COM port on the SmartLogger to a
COM port on an outdoor device, you are recommended to connect an RS485 signal SPD to
strengthen the surge protection capability.
2. Each RS485 signal SPD can connect to two COM ports. Each SmartLogger can be configured
with a maximum of three RS485 signal SPDs.
3. When the RS485 signal SPD is to be installed in a non-smart array controller, you are
recommended to install it on a guide rail.
4. If the SmartLogger is installed on a guide rail, the RS485 SPD can share the guide rail with the
SmartLogger. In this case, the recommended guide rail length is 600 mm or greater.
5. Secure the guide rail before mounting the RS485 SPD.
NOTE

9
1. It is recommended that 4–6 mm2or 12–10 AWG outdoor copper-core cables be used as ground
cables. Ground cables must be securely connected.
2. To enhance the corrosion resistance of the ground terminal, apply silica gel or paint on it after
connecting the PGND cable.
6Connecting Cables to COM Ports
1. The SmartLogger can connect to an inverter, an EMI, a power meter, a cubicle, and a PID
module through its COM ports.
2. The SmartLogger provides six COM ports. To connect a COM port on the SmartLogger to a
COM port on an outdoor device, you are recommended to connect an RS485 signal SPD to
strengthen the surge protection capability.
Installing the RS485 SPD Ground Cable
5.2
An outdoor copper-core cable with a cross-sectional area of 4 mm2or 12 AWG is recommended.
1. Prepare a ground cable with an appropriate length, and strip 8 mm of the insulation layer from
one end.
2. Insert the stripped part into port 3 of the RS485 signal SPD.
3. Tighten the screw on port 3 using a flat-head screwdriver to secure the core wire.
Connect the other end of the ground cable to the ground bar.
OT-M6
M6 (1 PCS)
1.4 N·m
NOTE
NOTE
Questo manuale è adatto per i seguenti modelli
1
Indice
Altri manuali Huawei Registratore di dati

Huawei
Huawei SmartLogger3000 Manuale utente

Huawei
Huawei FusionModule2000 V500R003C10 Manuale operativo

Huawei
Huawei FusionModule 1000A20 Manuale utente

Huawei
Huawei SmartLogger3000 Manuale utente

Huawei
Huawei SmartLogger3000 Manuale utente

Huawei
Huawei Atlas 500 Guida di riferimento rapido

Huawei
Huawei FusionModule1000A20 Manuale operativo

Huawei
Huawei FusionModule 1000B Manuale operativo

Huawei
Huawei SmartLogger1000 Manuale utente

Huawei
Huawei FusionModule500 Specifiche tecniche