
User Information
Safety Relays from IDEM SCR-7
H04
Ver. A
E61-329-00
Maintenace
The device must be checked once per month for proper
function and for signs of tampering and bypassing of the
safety function.
Techn. Data
Corresponds to the standards EN 60204-1; EN ISO 13849-1 ; EN 62061
Operating voltage AC/DC 24V
Rated Supply Frequency AC: 50-60Hz
Permissible deviation + / - 10%
Power consumption DC 24V AC 24V
approx. 4.5W approx. 8.5VA
Control voltage at S11 DC 24V
Control current S11..S14 approx. 250mA
Safety contacts 7 NO contacts
Auxiliary contacts 4 NC contacts
Auxiliary transistor outputs (O1, O2) DC 24V / 30mA, over current protected
Max. switching voltage AC 250V
Safety contact breaking capacity AC: 250V, 2000VA, 8A for ohmic load
(6 switching cycles/ min)
(13-14, 23-24, 33-34,43-44, 53-54, 63-64, 73-74) 250V, 3A for AC-15
DC: 40V, 320W, 8A for ohmic load
(6 switching cycles/ min)
24V, 3A for DC-13
Max. total current through all 7 contact up to Ta=40°C:
35A 10mm spacing between the devices
20A no spacing between the devices
Auxiliary contacts braking capacity AC: 250V, 2000VA, 8A for ohmic load
(81-82, 91-92, 101-102,101-112) DC: 40V, 320W, 8A for ohmic load
Minimum contact load 24V, 20mA
Contact fuses 10A gG
Line cross section 0.14 - 2.5mm2
Max. length of control line 1000m at 0.75 mm2
Contact material AgSnO2
Contact service life mech. approx. 1 x 107, electr. 1 x 105operating cycles
Test voltage 2.5kV (control voltage / contacts)
Rated impulse withstand voltage, leakage path/air gap 4kV (DIN VDE 0110-1)
Rated insulation voltage 250V
Degree of protection IP20
Temperature range -15°C bis +40°C
Degree of contamination 2 (DIN VDE 0110-1)
Overvoltage category 3 (DIN VDE 0110-1)
Weight approx. 350g
Mounting DIN rail according to EN 60715 TH35
Note:
Additional data can be requested from the manufacturer for
applications that deviate from these conditions.
Safety
Characteristics
According to
EN ISO 13849-1
The device is certified according to EN ISO 13849-1 up to a
Performance Level of PL e.
Device cannot be switched on again after an emergency
stop:
•
Check whether the emergency stop circuit was closed
again.
•
Was the start button opened before closing of the emer-
gency stop circuit (with manual start)?
•
Is the feedback loop closed?
If the fault still exists, perform the steps listed under
“Commissioning Procedure”.
If these steps do not remedy the fault either, return the
device to the manufacturer for examination.
Opening the device is impermissible and will void the
warranty.
Device does not switch on:
•
Check the wiring by comparing it to the wiring diagrams.
•
Check the safety switch used for correct function and
adjustment.
•
Check whether the emergency stop circuit is closed.
•
Check whether the start button (with manual start) is
closed.
•
Check the operating voltage at A1 and A2.
•
Is the feedback loop closed?
What to Do in
Case of a Fault?
The device is otherwise maintenance
free, provided that it was installed pro-
perly.
Safety characteristics according to EN ISO 13849-1 for all variants of SCR-7
Load (DC-13; 24V) <= 0,1A <= 1A <= 2A
T10d [years] 20 20 20
Category 4 4 4
PL e e e
PFHd [1/h] 2,47E-08 2,47E-08 2,47E-08
nop [cycle / year] <= 500.000 <= 350.000 <= 100.000