KATEK Steca PylonTech US2000B Manuale utente

Using PylonTech Lithium Battery Packs with the
Steca Solarix PLI 5000-48 Inverter Charger
Latest update: 03.07.2018
Page 1 of 3
Recommended Steca Solarix PLI 5000-48 setup for
the PylonTech US2000B, US2000Bplus, US3000B or
Phantom-S Li-Ion battery models
The following setup and settings have been selected through co-
operation between Steca Elektronik GmbH and Pylon Technologies Co.,
Ltd. (PylonTech). They represent recommended values for cyclical
applications as are typical in many solar PV applications with a depth
of discharge (DOD) of approximately 80%. This recommendation is
applicable to the PylonTech US2000B, US2000Bplus, US3000B
and Phantom-S battery models. We recommend using at least 4 pcs.
of the US2000B / US2000Bplus / Phantom-S or 3 pcs. of the US3000B
battery packs in parallel to reliably sustain the 5 kW full power
© Pylon Technologies Co., Ltd.
the batteries. Install one fuse or circuit breaker in each the
positive and negative cable between the battery bank and Solarix PLI with a rating of at least 150 Adc (slow).
Additionally, it is recommended to use a surge protector (SPD) on the battery terminals that
protects from voltages above 60 to 65 Vdc (example: Citel DS230S-48DC or similar), as well as on the PV side
(Citel DS240S-110DC or similar). If using more than 4 battery packs (or 3 for the US3000B), make sure to use
two battery cable pairs in parallel between the battery and the Solarix PLIs, each with their own fuses.
Make sure to always follow the requirements and guidelines from the battery manufacturer and
verify the settings with the data sheet of your batteries before applying them. Please contact
your retailer in case of uncertainty. Read the Steca Solarix PLI and battery manuals before
applying these settings. Follow your local regulations.
Installation Overview
KATEK Memmingen GmbH | Mammostraße 1 | 87700 Memmingen | Germany | [email protected] | www.steca.de

Please note that the overview above does not include AC breakers, AC surge protectors (SPD), residual current
devices (RCD), earth / ground cables, or other safety equipment that may be required in the country of
installation. Ensure that the system is installed by a professional according to national electrical safety standards.
Steca Solarix PLI Settings
The following settings refer to the Steca Solarix PLI 5000-48 inverter / charger,
connected to an array of PV modules and the aforementioned PylonTech 48 V
batteries. Please refer to the Solarix PLI manual for further explanation on the
mentioned setting programs:
Maximum charging current:
oProgram 02 set to a value equal to or lower than number of used
US2000B / US2000Bplus / Phantom-S battery packs x 25 A; or the
number of used US3000B battery packs x 37 A.
Example if using 4 pcs. of US2000Bplus: 4 x 25 A = 100 A. Therefore
the maximum charging current must be set to
100 A or lower.
•Battery type:
oProgram 05 User-defined (USE)
•Switch to AC input set-point (relevant when using “SBU” or “Solar first” modes in program 01):
oProgram 12 48 V
•Switch back to solar / battery set-point (relevant when using “SBU” or “Solar first” modes in program 01):
oProgram 13 51 V
Charger source priority (this is assuming you wish to utilise as much solar power as possible, if you do
not, then choose another setting):
o
oProgram 16 Solar first (CSO)
Program 11 (maximum AC input charging current) 2A
The reason “Solar first” is recommended here as opposed to “Only solar”, is that when the
battery is in a low-voltage state and the Solarix PLI switches to AC input / grid operation, the
Solarix PLI inverter’s self-consumption of approximately 50 W is still provided by the battery.
To compensate for this (and thus prevent the battery voltage from dropping too low if there are
prolonged periods without sunshine), it is recommended to charge the battery very slightly
(less than 100 W when setting program 11 to 2A as recommended), when the Solarix PLI is in
AC input / grid mode. This ensures that the battery will not be gradually depleted when the grid
is available and there is no sunshine. Choosing a higher value than 2A would reduce the energy
cost-savings potential from this system.
Steca Solarix PLI 5000-48
Using PylonTech Lithium Battery Packs with the
Steca Solarix PLI 5000-48 Inverter Charger
Latest update: 03.07.2018
Page 2 of 3
KATEK Memmingen GmbH | Mammostraße 1 | 87700 Memmingen | Germany | [email protected] | www.steca.de

•Boost charging voltage:
oProgram 26 53.2 V
•Float charging voltage:
oProgram 27 53.1 V
•Low DC / battery cut-off voltage:
oProgram 29 47.5 V
•Boost charging time:
oProgram 32 60 minutes
•Battery equalisation:
oProgram 33 Battery equalisation disable (EdS)
Note: if there is a critical condition detected in the battery, the PylonTech battery will shut
down for safety reasons. To re-start the system, the battery must be started manually.
Only once the battery has started up can the Solarix PLI 5000-48 power up again.
Using PylonTech Lithium Battery Packs with the
Steca Solarix PLI 5000-48 Inverter Charger
Latest update: 03.07.2018
Page 3 of 3
KATEK Memmingen GmbH | Mammostraße 1 | 87700 Memmingen | Germany | [email protected] | www.steca.de
Questo manuale è adatto per i seguenti modelli
3
Indice

















