Kimo CPE 311-S Manuale utente

Configuration of CPE 310-S and CPE 311-S
transmitters by keypad


Table of contents
1. Introduction..........................................................................................................................................5
1.1. Description of the transmitter.......................................................................................................5
1.2. Description of the keys.................................................................................................................5
1.3. Protection tips of the sensor........................................................................................................5
2. Modbus................................................................................................................................................6
2.1. Configuration of parameters........................................................................................................6
2.2. unctions......................................................................................................................................6
2.3. Access code to register................................................................................................................6
3. Access to the different functions.........................................................................................................9
4. 100: Configure the transmitter.......................................................................................................10
4.1. Access to the serial number: 100............................................................................................10
4.2. Access to the firmware version: 101........................................................................................10
4.3. Lock the keypad: 140..............................................................................................................10
4.4. Modify the safety code: 141.....................................................................................................10
4.5. Configure the Modbus communication (optional)......................................................................11
4.5.1 Set the slave number: 150.................................................................................................11
4.5.2 Set the speed communication: 151...................................................................................11
4.6. Activate the options....................................................................................................................11
4.7. Back to factory settings: 190...................................................................................................12
5. 200: Configuration of the channels and measurement units.........................................................13
5.1. Activate a channel......................................................................................................................13
5.2. Assign a measurement unit to a channel...................................................................................13
6. 300: Manage the analogue outputs...............................................................................................14
6.1. Set the analogue outputs...........................................................................................................14
6.2. Set the ranges of the analogue outputs.....................................................................................14
6.3. Output diagnostic.......................................................................................................................15
6.3.1 Connection configuration.....................................................................................................15
6.3.2 Perform the output diagnostic.............................................................................................16
7. 400: Manage the alarms.................................................................................................................17
8. 500: Set the pressure measurement.............................................................................................20
8.1. Perform an auto-zero.................................................................................................................20
8.2. Integration of the pressure measurement..................................................................................20
8.3. Delay times between 2 auto-zeros............................................................................................20
8.4. Add a coefficient.........................................................................................................................21
8.5. Add an offset..............................................................................................................................21
9. unctions recap and Modbus connections.......................................................................................22
9.1. 100: configure the transmitter.................................................................................................22
9.2. 200: configure the channels and the measurement units......................................................22
9.3. 300: manage the analogue outputs........................................................................................22
9.4. 400: manage the alarms.........................................................................................................23
9.5. 500: set the measurement......................................................................................................24


1. Introduction
1.1. Description of the transmitter
The CPE 310-S and CPE 311-S can be configured via the keypad. It is possib e to set the measurement units, to activate or
not a channe ,...
Principle: the different settings are in the form of fo ders and sub-fo ders numbers. The digita codes are fu y detai ed in
this manua .
1.2. Description of the keys
–Up key: increments a va ue or a eve
–Down key: decrements a va ue or a eve
–OK key: va idates an input
–Esc key: cance s the input or goes back to the previous step
1.3. Protection tips of the sensor
It's extremely unwise to remove the protection tip of our hygrometry probes as
the sensitive e ement is very fragi e even to ight contacts. However, if you
have to remove the protection tip, take a possib e precautions and avoid any
contact with the sensitive e ement.
To remove the protection tip, unscrew it or unc ip it.
Introduction 5
Up key
Down key
OK key
Esc key
10 Pa
Channe 1 indicator ight Channe 3 indicator ight
Channe 2 indicator ight
Front access for
pressure adjustement
Front access to the
mini-Din connector for
PC connection
Protection tip
to unscrew
Protection tip
to unscrew
Sensitive
eement
Sensitive
eement

2. Modbus
2.1. Configuration of parameters
•Communication speed: between 2400 and 115200 bauds, 19200 bauds by defau t
•Data bits: 8 bits
•Stop bit: 1 bit
•Parity: None
•Flow control: None
•Transmitter addressin : between 1 and 255 (automatica y answers the requests from address 0)
•Data sendin : made by words of 2 bytes, in the fo owing order: most-significant then east-significant byte
2.2. Functions
•Re ister function: Function 03
•Re ister writin : Function 16
•Communication loop test: Function 08
2.3. Access code to register
•Re isters type:
Type Size Description Format
U8 1 byte Unsigned integer 8 bits Byte 1
Examp e with a va ue of 24 (0x18) 0x18
Type Size Description Format
U16 2 bytes Unsigned integer 16
bits
Byte 2 Byte 1
Examp e with a va ue of 300 (0x012C)0x01 0x2C
Type Size Description Format
U32 4 bytes Unsigned integer 32
bits
Byte 2 Byte 1 Byte 4 Byte 3
Examp e with a va ue of 1 096 861 217 (0x4160C621)0xC6 0x21 0x41 0x60
Type Size Description Format
Rea 4 bytes Rea 32 bits Byte 2 Byte 1 Byte 4 Byte 3
Examp e with a va ue of 153.5 (0x43198000)0x80 0x00 0x43 0x19
Type Size Description Format
Enumeration 1 byte See Enumeration tab e
page 8
Same as U8
Boo ean 1 byte True = 1 ; Fa se = 0 Same as U8
6Modbus

Type Size Description Example
Seria number 8 octets C ass (1 byte)
Range (1 byte)
Year (2 bytes)
Month (1 byte)
Number (3 bytes)
'3' (0x33)
'F' (0x46)
13 (0x000D)
8 (0x08)
98765 (0x0181CD)
Format
Byte 2 (range) Byte1 (c ass) Byte 4 (year) Byte 3
(year)
Byte 6
(number)
Byte 5
(month)
Byte 8
(number)
Byte 7
(number)
0x46 0x33 0x00 0x0D 0xCD 0x08 0x01 0x81
Example with 3F13898765: 0x0181CD08000D4633
Alarms and relays status – Modbus code: 7000
Encoded on 4 octets (U32)
Byte 2 Byte 1
b8 – b15 b7 – b4 b3 b2 b1 b0
Unused Unused Unused Channe 3 Channe 2 Channe 1
A arm state*
(*)1: the channe is in a arm state / 0: the channe is not in a arm state
Byte 4 Byte 3
b31 – b28 b27 b26 b25 b24 b23 – b20 b19 b18 b17 b16
Unused Re ay 4** Re ay 3** Re ay 2** Re ay 1** Unused Unused A arm 3*** A arm 2*** A arm 1***
(**)1: the re ay is triggered / 0: the re ay is not triggered
(***)1: the a arm is activated / 0: the a arm is deactivated
•Values – Modbus code: 7010 (channe 1)
7040 (channe 2)
7070 (channe 3)
•Number of di its after the decimal point – Modbus code: 7020 (channe 1)
7050 (channe 2)
7080 (channe 3)
•Unit – Modbus code: 7030 (channe 1)
7060 (channe 2)
7090 (channe 3)
List of units:
Field Unit Value
None 0
Temperature °C 16
°F 17
Hy rometry %HR 32
g/Kg 33
Modbus 7

Kj/KG 34
°C td 35
°F td 36
°C Tw 37
°F Tw 38
Pressure
kPa 50
inWg 51
hPa 52
mbar 53
mmHg 54
mmH2O 55
daPa 56
Pa 57
Air velocity
m/s 64
fpm 65
km/h 66
Combustion ppm 112
“Enumerations” table:
Correspondin values 0 1 2 3 4 5 6 7
Modbus Com speed 2400 4800 9600 19200 38400 115200 Unused
Channel x Unit See ist of unit
Channel x Transmitter none probe 1 probe 2 modu e Unused
Output x Type 4 - 20 mA 0 - 20 mA 0 - 10 V 0 - 5 V 0 - 1 V Unused
Output x Dia nostic Deactivate 0% 50% 100% Unused
Alarm x Mode Deactivate Rising edge Fa ing edge Monitoring Transmitt
er state Unused
Alarm x Security Negative Positive Unused
Relay x Selection OFF ON A arm 1 A arm 2 A arm 3 Unused
8Modbus

3. Access to the different functions
This step is compulsory for each confi uration.
First, to access to the transmitter functions, and for safety, a safety code must be entered. The defau t safety code is 0101.
•The transmitter must be energized.
➢Connect the transmitter.
➢Wait unti the initia izing period is over.
➢Press OK.
“Code” is displayed with “0000”. The 1st 0 blinks.
➢Press OK to go to the 2nd 0.
It blinks.
➢Press Up key to disp ay 1 then press OK.
The rd 0 blinks.
➢Press OK to go to the 4th 0.
➢Press Up key to disp ay 1 then press OK.
The following screen is displayed:
“F 100” is for the number of the configuration fo der. There are 5 fo ders:
•F 100: fo der of the transmitter configuration. See page 10.
•F 200: fo der of the channe s and measurement units. Seer page 13.
•F 300: fo der of the ana ogue outputs. See page 14.
•F 400: fo der of the a arms. See page 17.
•F 500: fo der of the channe s, integration and autozero configuration. See page 20.
To se ect the required fo der:
“F 100” is displayed and 1 is blinking.
➢Press Up key unti the number of the required fo der is disp ayed (F 100, F 200, F 300 or F 500).
➢Press OK.
Access to the different functions 9
Code
0101
F 100

4. F 100: Configure the transmitter
This fo der a ows to configure the fo owing parameters of the transmitter: safety code, modbus, options and factory
configuration.
It a so indicates the seria number and the firmware version of the transmitter.
4.1. Access to the serial number F100
The seria number a ows to get activation codes for the options.
F 100 is displayed (see previous page).
➢Press OK.
“F 100” is displayed with the serial number of the transmitter that scrolls below.
4.2. Access to the firmware version F101
F100 folder is displayed.
➢Press Up key.
“F 101” is displayed with the version number that scrolls below (e.g: 1.00)
4.3. Lock the keypad F 140
For more safety and to avoid any hand ing mistake, it is possib e to ock the keys.
F101 sub-folder is displayed.
➢Press Up key.
“F 140” is displayed with “0” indicating that the locking is on.
➢Press OK.
“0” blinks.
➢Press Up or Down key, “1” b inks, then press OK.
“LOCK” is displayed for a few seconds then the transmitter backs to the displaying of measured values.
All the keys are inactive.
To activate them again:
➢Press OK for 10 seconds.
“LOCK” is displayed for a few seconds then the transmitter goes back to the displaying of measured values and
keys are active again.
4.4. Modify the safety code F141
It is possib e to modify the safety code.
F140 sub-folder is displayed.
➢Press Up key.
“F 141” is displayed with the safety code below.
➢Press OK.
The 1st zero blinks.
➢Press Up or Down key to modify the digit then press OK.
The 2nd digit blinks.
➢Press Up or Down key to modify the digit then press OK.
The rd digit blinks.
➢Press Up or Down key to modify the digit then press OK.
The 4th digit blinks.
➢Press Up or Down key to modify the digit then press OK.
“OK”» is displayed.
➢Press OK to va idate the modification of the code or Esc to cance .
The transmitter goes back to the displaying of the F141 folder with the new code indicated below.
10 F 100: Configure the trans itter
Questo manuale è adatto per i seguenti modelli
1
Indice
Altri manuali Kimo Trasmettitore

Kimo
Kimo Class 300 Manuale utente

Kimo
Kimo Class 200 Manuale utente

Kimo
Kimo HM 50 Manuale di istruzioni

Kimo
Kimo TG 100 Manuale di istruzioni

Kimo
Kimo CP 111 Manuale di istruzioni

Kimo
Kimo C310 Manuale utente

Kimo
Kimo 210-R Series Manuale utente

Kimo
Kimo CA 310 Manuale utente

Kimo
Kimo CPE 300 Manuale utente

Kimo
Kimo ATE 310 Manuale utente