Koldwave 5AK39BFA Manuale di istruzioni

IOM5AKEN-2
1
Koldwave 5AK39 and 5AK65 Series Installation,
Operation & Maintenance Manual
Model No._______________________ Serial No._______________________________
Koldwave 4830 Transport Drive Dallas, TX 75247 Ph: 214-638-6010
www.koldwave.com
ATTENTION: READ THIS MANUAL, FACTORY INSTALLED OPTIONS MANUAL,
UNIT SUBMITTAL DATA SHEETS AND ALL LABELS ATTACHED TO THE UNIT
CAREFULY BEFORE ATTEMPTING TO INSTALL, OPERATE OR SERVICE
THESE UNITS. CHECK DATA PLATES FOR ELECTRICAL SPECIFICATIONS
AND MAKE CERTAIN THAT THESE AGREE WITH THOSE AT THE POINT OF
INSTALLATION. RECORD THE UNIT MODEL AND SERIAL NUMBER IN THE
SPACE PROVIDED. RETAIN THIS DOCUMENT FOR FUTURE REFERENCE.
IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR
MAINTENANCE CAN CAUSE PROPERTY DAMAGE, INJURY OR DEATH. THIS
APPLIANCE MUST BE INSTALLED BY A LICENSED CONTRACTOR OR
QUALIFIED SERVICE PERSONNEL. READ THESE INSTALLATION, OPERATING
AND MAINTENANCE INSTRUCTIONS THOROUGHLY BEFORE INSTALLING OR
SERVICING THE UNIT.
WARNING: INSTALL, OPERATE AND MAINTAIN UNIT IN ACCORDANCE WITH
MANUFACTURER’S INSTRUCTIONS TO AVOID ANY DETURING FACTORS
THAT MAY CAUSE PERSONAL INJURY OR PROPERTY DAMAGE.
INSTALLER’S RESPONSIBILITY: THIS EQUIPMENT HAS BEEN RUN TESTED
AND INSPECTED THOROUGHLY. IT HAS BEEN SHIPPED FREE FROM
DEFECTS FROM OUR FACTORY. HOWEVER, DURING SHIPMENT AND
INSTALLATION, PROBLEMS SUCH AS LOOSE WIRES, LEAKS, OR LOOSE
FASTENERS MAY OCCUR. IT IS THE INSTALLER’S RESPONSIBILITY TO
INSPECT AND NOTIFY FACORY OF ANY PROBLEMS THAT MAY BE FOUND.

IOM5AKEN-2
2
Table of Contents:
GENERAL INFORMATION...................................................................................................... 4
INSTALLATION INSTRUCTIONS .......................................................................................... 5
ELECTRICAL REQUIREMENTS....................................................................................................... 5
SERVICE CORD............................................................................................................................. 5
SPECIFICATION AND ELECTRIC DATA............................................................................. 6
SERVICEABILITY...................................................................................................................... 7
5AK39 UPPER LEFT SIDE VIEW................................................................................................... 7
5AK39 UPPER RIGHT SIDE VIEW................................................................................................. 8
5AK39 UPPER LEFT SIDE VIEW................................................................................................... 9
5AK39 UPPER RIGHT SIDE VIEW............................................................................................... 10
5AK65 LOWER LEFT SIDE VIEW ............................................................................................... 11
5AK65 UPPER LEFT SIDE VIEW................................................................................................. 12
5AK65 FRONT VIEW ................................................................................................................. 12
AIR FILTER ............................................................................................................................... 13
CONDENSATE REMOVAL..................................................................................................... 13
GENERAL FLOW PATTERN ................................................................................................. 14
SAFETY CONTROLS ............................................................................................................... 14
UNIT OPERATION ................................................................................................................... 15
UNIT POWER ON:....................................................................................................................... 15
FAN HI:...................................................................................................................................... 15
FAN LO:..................................................................................................................................... 15
COOLING HI:.............................................................................................................................. 15
COOLING LO:............................................................................................................................. 15
TEMPERATURE SETTING: ........................................................................................................... 15
UNIT OFF:.................................................................................................................................. 15
OTHER SETTINGS:...................................................................................................................... 15
COMPRESSOR OFF TIME:............................................................................................................ 15
SELF RECOVERY MODE (*):....................................................................................................... 15
CHECK ALARMS:........................................................................................................................ 16
OPTIONAL REMOTE CONTROL: .................................................................................................. 16
INSPECTION AND REPAIR OF ELECTRICAL SYSTEM................................................ 17
COMPRESSOR AND FAN MOTOR CAPACITORS............................................................................ 17
INSPECTION AND REPAIR OF REFRIGERANT SYSTEM............................................. 17
PREVENTATIVE MAINTENANCE....................................................................................... 17

IOM5AKEN-2
3
ELECTRICAL DIAGRAM....................................................................................................... 19
5AK39, 5AK65 208V/1PH ....................................................................................................... 19
5AK39, 5AK65 230V/1PH ....................................................................................................... 20
5AK65 208V/3PH WITH 208V/1PH PUMP................................................................................ 21
5AK65 230V/3PH WITH 230V/1PH PUMP................................................................................ 22
5AK65 460V/3PH WITH 277V/1PH PUMP................................................................................ 23
TROUBLE SHOOTING GUIDE.............................................................................................. 24
TROUBLE SHOOTING GUIDE CONTINUED..................................................................... 25
TROUBLE SHOOTING GUIDE CONTINUED..................................................................... 26
TROUBLE SHOOTING GUIDE CONTINUED..................................................................... 27
TROUBLE SHOOTING GUIDE CONTINUED..................................................................... 28
TROUBLE SHOOTING GUIDE CONTINUED..................................................................... 29

4
General Information
The Koldwave 5AK Series Air Conditioners
are portable, air-cooled air conditioners/zone
coolers suitable for indoor/outdoor use. The
Koldwave air-conditioner cools an entire
area by discharging air through its supply
grille. This self-contained unit is also
designed to direct cool air to specific areas
or objects through (optional) flexible
snozzles®. This provides precision cooling
for heat-sensitive equipment, production
processes and personnel.
Each unit is completely self-contained with
the entire refrigeration system, electrical
components, condenser and evaporator
housed in one cabinet. The Koldwave unit
is provided with heavy-duty casters. Two
swivel-locking casters prevent sliding; two
stationary casters provide handling ease for
relocation.
Model 5AK65
NOMENCLATURE
Example 5AK 14 B G A 1 A A
Code MD US R V C SS EC CC
Field 1,2,3 4,5 6 7 8 9 10 11
1,2,3 – MODEL (MD)
5AK – Air Cooled Portable
4,5 – UNIT SIZE (US)
AK – Air Cooled Models
39 – 36,800 Btuh
65 – 61,200 Btuh
6 - REFRIGERANT (R)
B – R410A
7 – VOLTAGE (V)
A – 208/3/60 (used only on 5AK65)
B – 230/3/60 (used only on 5AK65)
C – 460/3/60 (used only on 5AK65)
F – 208/1/60
G – 230/1/60
8 – CONFIGURATION (C)
A – Front Discharge with Adjustable Grilles
9 – CONFIGURATION (SS)
1 – Stainless Steel
2 – Painted (5AK65 only)
10 – EVAPORATOR COIL (EC)
A – Standard Copper/Aluminum
11 – CONDENSER COIL (CC)
A – Standard Copper/Aluminum

5
Installation Instructions
Electrical Requirements
Check the power supply to make certain it is
within 10% of the voltage listed on the data
plate located on the back of the unit.
Operating the unit on improper voltage
will void the product warranty.
Refer to the Rating Plate for voltage and
current information.
Each unit should have a dedicated circuit
breaker.
Service Cord
MODEL VOLTAGE PLUG TYPE
5AK39 208-230/1/60 6 – 30P
5AK65 240/1/60 Field wired240/3/60
460/3/60
Extension cords used with the Koldwave
units should match the plug configuration of
the service cord provided on the unit. The
extension cord must be equipped with an
equipment grounding conductor, a
grounding type attachment plug, and a
grounding type attachment connector. The
cord must also have a rating suitable for the
voltage and ampacity.
The Koldwave 5AK65 is a field wired unit
which requires a field supplied electrical
service disconnect. Check the unit
nameplate for the correct voltage, phase and
maximum fuse size for the electrical service
for the unit. A high voltage terminal block is
provided in the unit’s control box for the
electrical connection. Route the electrical
power leads through the electrical knockouts
provided on either side of the control box.
Install the required electrical service wiring
in accordance with all applicable codes.
IMPORTANT: Following the installation
and preventative maintenance instructions
can extend the length of service you
receive from your Koldwave unit.

6
Specification and Electric Data
39 65
ELECTRIC DATA *** ### *** ###
Voltage/Phase/Hertz 230/1/60 230/1/60 230/3/60 460/3/60
Amperage 22.7 49.7 26.1 15.4
Fuse Size (Amps) 30 60 40 30
Watts 4666 8380
REFRIGERANT CHARGE
R410A (Ounces) 116 176
UNIT DIMENSIONS (INCHES)
Height with Casters 69 78
Height without Casters 64 73
Width 40.5 40.25
Depth 31.5 31.5
Evaporator Filter (qty) (1) 13.75 x 29.75 x 0.88 (1) 29.75 x 17.75 x 0.88
Condenser Filter (qty) (1) 23 x 29.5 x 0.88 (1) 29.5 x 29 x 0.88
NET UNIT WEIGHT (LBS.) 590 650
SHIPPING WEIGHT (LBS.) 620 700
Time delay fuses and circuit breakers are recommended.
*** Electrical ratings per U.L Standard 484 at 95°F DB/75° WB on high speed at 230VAC single phase
except 5AK65 at 230VAC three phase.
### Electrical ratings estimated from component nameplate ratings on high speed.

7
Serviceability
The Koldwave unit has removable panels to provide full service accessibility.
5AK39 Upper Left Side View
Thermostatic
Expansion
Valve
Evaporator
Coil
Evaporator
Blower
Suction Line
Liquid Line

8
5AK39 Upper Right Side View
Evaporator
Blowe
r
Evaporator
Coil
Evaporator
Blower
Motor

9
5AK39 Upper Left Side View
Evaporator
Blowe
r
Drain Pan
Hose
Discharge
Line Service
Port
Suction Line
Service Port
Compressor
Liquid Line
Filter/Drie
r
Condenser
Coil

10
5AK39 Upper Right Side View
Condenser
Blowe
r
Condenser
Blower
Motor
Condensate
Pum
p
Evaporator
Drain Pan
Hose
Condenser
Coil
Condensate
Pump Drain
Line
Questo manuale è adatto per i seguenti modelli
6
Indice
Altri manuali Koldwave Condizionatore d'aria

Koldwave
Koldwave 6CC10BEA2AA00 Manuale utente

Koldwave
Koldwave 5WK Series Manuale utente

Koldwave
Koldwave AIRMASTER 2AK1011 Manuale utente

Koldwave
Koldwave 6KK21BGA2AA00 Manuale utente

Koldwave
Koldwave Kompac 4WK07 Manuale utente

Koldwave
Koldwave KWV-20 Manuale di istruzioni

Koldwave
Koldwave K6HK144BBA2ACA0 Manuale utente

Koldwave
Koldwave AIRMASTER 3AK Manuale utente

Koldwave
Koldwave K6CC10BEA2AA00 Manuale utente

Koldwave
Koldwave 6HK60-IOM-1 Manuale utente