Mandik FDMB Guida

www.mandik.co.uk
MANDÍK, a. s. • Dobříšská 550 • 267 24 Hostomice • Czech Republic • Tel.: +420 311 706 742 • E-Mail: [email protected]
Manufacturer
MANDIK UK Ltd • 130 Aztec West • Bristol BS32 4UB • United Kingdom • Tel.: +44 117 4526376 • E-Mail: [email protected]
Authorized representative
FDMB
Fire damper
Technical Documentation
Installation, Commissioning, Operation, Maintenance and Service Manual
TPM 164/22
Version 2022-12-20

FDMB - Fire damperPage 2 Version 2022-12-20
TPM 164/22
These technical specifications state a row of manufactured sizes and models of fire dampers FDMB.
It is valid for production, designing, ordering, delivery, maintenance and operation.
CONTENT
I. GENERAL.....................................................................................................................................................................................3
Description..............................................................................................................................................................................3
Design.....................................................................................................................................................................................4
Design with mechanical control..........................................................................................................................................4
Design with actuating mechanism.......................................................................................................................................6
Communication and control module MDCM.....................................................................................................................11
Dimensions...........................................................................................................................................................................12
Technical parameters............................................................................................................................................................14
Placement and Assembly......................................................................................................................................................20
Statement of installations.....................................................................................................................................................22
Installation in solid wall construction................................................................................................................................23
Installation outside solid wall construction.......................................................................................................................25
Installation in gypsum wall construction...........................................................................................................................27
Installation outside gypsum wall construction..................................................................................................................30
Installation in solid ceiling construction............................................................................................................................32
Shaft wall...........................................................................................................................................................................33
Suspension systems..............................................................................................................................................................35
Duct connection....................................................................................................................................................................37
II. TECHNICAL DATA.....................................................................................................................................................................38
Pressure loss.........................................................................................................................................................................38
Noise data.............................................................................................................................................................................40
III. MATERIAL, FINISHING.............................................................................................................................................................41
Material................................................................................................................................................................................41
IV. INSPECTION, TESTING.............................................................................................................................................................41
V. TRANSPORTATION AND STORAGE...........................................................................................................................................42
Logistic terms........................................................................................................................................................................42
VI. ASSEMBLY, ATTENDANCE AND MAINTENANCE......................................................................................................................42
Assembly...............................................................................................................................................................................42
Entry into service and revisions.........................................................................................................................................46
Spare parts.........................................................................................................................................................................47
VII. PRODUCT DATA.....................................................................................................................................................................48
Data label..............................................................................................................................................................................48
VIII. ORDERING INFORMATION....................................................................................................................................................48
Ordering key.........................................................................................................................................................................48

Page 3Version 2022-12-20 FDMB - Fire damper
TPM 164/22
I. GENERAL
Description
Working conditions
■Exact damper function is provided under the following conditions
■maximum air velocity 12 m/s
■underpressure max. -1200 Pa
■the air circulation in the whole damper section must be secured as steady on whole surface.
■Dampers can be installed in position with horizontal or vertical blade axis.
■Dampers can be installed in position with actuating mechanism on top or on the side of damper.
■Dampers are suitable for systems without abrasive, chemical and adhesive particles.
■Dampers are designed for macroclimatic areas with mild climate according to EN 60 721-3-3, class 3K22.
■Temperature in the place of installation is permitted to range from -30°C to +50°C.
Fire dampers are shutters in ducts of air-conditioning devices
that prevent spreading the fire and combustion products
from one fire segment to the other one by means of closing
the duct in the points of fire separating constructions.
Dampers blade automatically closes air duct using a shutting
spring or an actuating mechanism back spring. Closing spring
is released either by pushing of the button or by thermal fuse.
The back spring of the actuating mechanism is started when
the thermoelectrical starting mechanism BAT is activated,
when a reset button on BAT is pushed or when a power
supply of the actuating mechanism is stopped.
The damper is sealed with a silicon packing against smoke
penetration after closing the blade. At the same time, the
damper blade is bedded in a material which enlarges its
capacity and air proofs the air duct.
Dampers have two inspection holes.
Damper FDMB with actuating mechanism Damper FDMB with mechanical control
Damper characteristics
■CE certified acc. to EN 15650
■Tested in accordance with EN 1366-2
■Classified acc. to EN 13501-3+A1
■External Casing leakage: A<160 or B<160 class B, A≥160 and B≥160 class C
■Internal leakage min. class 2 acc. to EN 1751
■Cycling test in class C10000 acc. to EN 15650
■Corrosion resistant acc. to EN 15650
■Certificate of constancy of performance UKCA No. TBD* & UKNI No. TBD*
■Certificate of constancy of performance CE No. 1391-CPR-2020/0136
■Declaration of Perfomance UKCA & UKNI No. PM/FDMB/02/22/1
■Declaration of Perfomance CE No. PM/FDMB/01/22/5
■Hygienic assessment of fire dampers - Report No. 1.6/pos/19/19c * Document in process

FDMB - Fire damperPage 4 Version 2022-12-20
TPM 164/22
Design
Design with mechanical control
■Design .01 with mechanical control can be complemented
with a limit switch signalling of the damper blade position
"CLOSED".
■Cable is connected directly to limit switch.
■Limit switch detail → see page 5
Design .11
■Design .01 with mechanical control can be complemented
with a terminal switches signaling of the damper blade
position "CLOSED" and "OPEN".
■Limit switches are connected via damper casing, cables
are connected directly to limit switches.
■Limit switch detail → see page 5
Design .80
■Design with mechanical control with a thermal protective
fuse which actuates the shutting device, after the nominal
start temperature 72°C has been reached.
■Automatic initiation of the shutting device is not activated
if the temperature does not exceed 70°C.
■In case that other start temperatures are required,
thermal fuses with nominal start temperature +104°C or
+147°C can be supplied (this requirement must be
specified in the order).
Design .01
ATTENTION:
■Mechanisms are produced in five designs M1 to M4, dif-
ference is only in size of inner spring, which closes the fire
damper.
■For the size of fire dampers is always assigned the size of
mechanism → see pages 14 to 19
■It is not recommended to use different size of mechanism,
than given by the manufacturer, otherwise, there is a risk
of fire damper destruction.
Design .01
Design .11
Limit switch
“CLOSED”
Design .80
Limit switch
“CLOSED”
Limit switch
“OPEN”

Page 5Version 2022-12-20 FDMB - Fire damper
TPM 164/22
Nominal voltage and maximal current AC 230V / 5A
Class of protection IP 67
Working temperature
-25°C … +120°C
Limit switch G905-300E03W1
This limit switch is possible to connect in following two versions
■CUT-OFF if the arm is moving … connect wire 1+2
■SWITCH-ON if the arm is moving … connect wire 1+4
1(COM) - black wire
2(NC) - gray wire
4(NO) - blue wire
Mechanical control
Fusible link

FDMB - Fire damperPage 6 Version 2022-12-20
TPM 164/22
Design with actuating mechanism
■The dampers are equipped by Belimo actuators with
spring return and thermoelectric activation device of BFL,
BFN or BF depending on the damper size (further mentio-
ned as „actuators“).
■After being connected to power supply 230V or AC/DC
24V, the actuating mechanism displaces the damper
blade into operation position "OPEN" and at the same
time it pre-stretches its back spring.
■When the actuating mechanism is under voltage, the
damper blade is in the position "OPEN" and the back
spring is pre-stretched.
■Time needed for full opening of the flap blade from the
position "CLOSED" to the position "OPEN" is maximum
120 sec. If the actuating power supply is cut off (due to
loss of supply voltage, or pushing the reset button on the
thermoelectrical starting mechanism BAT), the back
spring displaces the damper blade into the breakdown
position "CLOSED".
■The time of displacing the blade from the position "OPEN"
to the position "CLOSED" takes maximum 20 sec.
■In case that the power supply is restored again (the blade
can be in any position), the actuating mechanism starts to
re-displace the damper blade into the position "OPEN".
■A thermoelectrical starting mechanism BAT, which
contains two thermal fuses Tf1 and Tf2, is a part of the
actuating mechanism.
■These fuses are activated when temperature +72°C has
been exceeded (the fuse Tf1 when the temperature
around the damper and the fuses Tf2 when the
temperature inside the air-conditioning ducting has been
exceeded).
■After the thermal fuse Tf1 or Tf2 has been activated, the
power supply is permanently and irreversibly cut off and
the actuating mechanism, by means of the pre-stretched
spring, displaces the damper blade into the breakdown
position "CLOSED".
■Signalisation of damper blade position "OPEN" a "CLOSE"
is provided by two limit switches.
Design .40 and .50
Design .40 and .50
Actuating mechanism
Thermoelectrical starting
mechanism BAT

Page 7Version 2022-12-20 FDMB - Fire damper
TPM 164/22
Actuator BELIMO BFL 230-T
Actuator BELIMO BFL 24-T(-ST)
BELIMO - 4 N.m
Actuator BELIMO BFL 230-T, BFL 24-T(-ST)
Actuator BELIMO - 4 Nm BFL 230-T BFL 24-12(-ST)
Power voltage AC 230 V
50/60Hz
AC/DC 24 V
50/60Hz
Power consumption - motoring
- holding
3,5/5 W
1,1/2,1 W
2,5/4 W
0,8/1,4 W
Dimensioning 6,5/10 VA (Imax 4 A @ 5 ms) 4/6 VA (Imax 8,3 A @ 5 ms)
Protection class II III
Degree of protection IP 54
Running time - motor
- spring return
< 60 s
~ 20 s
Ambient temperature
- normal duty
- safety duty
- non-operating temperature
-30°C … +55°C
The safe position will be attained up to max. +75°C
-40°C … +55°C
Connection - motor
- auxiliary switch
cable 1 m, 2 x 0,75 mm² (BFL 24-T-ST) with 3-pin plug-in connectors
cable 1 m, 6 x 0,75 mm² (BFL 24-T-ST) with 6-pin plug-in connectors
Thermal trips duct outside temperature +72°C
duct inside temperature +72°C
S2S1 S3 S5S4 S6
2
1
<5° <80°
N L1
BAT
Tf Tf LED
S2S1 S3 S5S4 S6
2
1
<5° <80°
BAT
Tf Tf LED

FDMB - Fire damperPage 8 Version 2022-12-20
TPM 164/22
Actuator BELIMO BFN 24-T(-ST)
BELIMO - 9 N.m
Actuator BELIMO BFN 230-T, BFN 24-T(-ST)
Actuator BELIMO - 9 Nm BFN 230-T BFN 24-12(-ST)
Power voltage AC 230 V
50/60Hz
AC/DC 24 V
50/60Hz
Power consumption - motoring
- holding
3,5/5 W
1,1/2,1 W
2,5/4 W
0,8/1,4 W
Dimensioning 6,5/10 VA (Imax 4 A @ 5 ms) 4/6 VA (Imax 8,3 A @ 5 ms)
Protection class II III
Degree of protection IP 54
Running time - motor
- spring return
< 60 s
~ 20 s
Ambient temperature
- normal duty
- safety duty
- non-operating temperature
-30°C … +55°C
The safe position will be attained up to max. +75°C
-40°C … +55°C
Connection - motor
- auxiliary switch
cable 1 m, 2 x 0,75 mm² (BFN 24-T-ST) with 3-pin plug-in connectors
cable 1 m, 6 x 0,75 mm² (BFN 24-T-ST) with 6-pin plug-in connectors
Thermal trips duct outside temperature +72°C
duct inside temperature +72°C
Actuator BELIMO BFN 230-T
S2S1 S3 S5S4 S6
2
1
<5° <80°
N L1
BAT
Tf Tf LED
S2S1 S3 S5S4 S6
2
1
<5° <80°
BAT
Tf Tf LED

Page 9Version 2022-12-20 FDMB - Fire damper
TPM 164/22
Actuator BELIMO BF 230-TN
Actuator BELIMO BF 230-TN, BF 24-TN(-ST)
Actuator BELIMO - 40 Nm BF 230-TN BF 24-TN(-ST)
Power voltage AC 230 V
50/60Hz
AC/DC 24 V
50/60Hz
Power consumption - motoring
- holding
8 W
3 W
7 W
2 W
Dimensioning 12,5 VA (Imax 500 mA @ 5 ms) 10 VA (Imax 8,3 A @ 5 ms)
Protection class II III
Degree of protection IP 54
Running time - motor
- spring return
120 s
~ 16 s
Ambient temperature
- normal duty
- safety duty
- non-operating temperature
-30°C … +50°C
The safe position will be attained up to max. +75°C
-40°C … +50°C
Connection - motor
- auxiliary switch
cable 1 m, 2 x 0,75 mm²
cable 1 m, 6 x 0,75 mm²
(BF 24-T-ST) with plug-in connectors
Thermal trips Tf1: duct outside temperature Duct +72°C
Tf2/Tf3: duct intside temperature Duct +72°C
BELIMO - 40 N.m
Actuator BELIMO BF 24-TN (-ST)
S2S1 S3 S5S4 S6
2
1
<5° <80°
N L1
BAT
Tf Tf LED
S2S1 S3 S5S4 S6
2
1
<5° <80°
BAT
Tf Tf LED

FDMB - Fire damperPage 10 Version 2022-12-20
TPM 164/22
Thermoelectrical starting mechanism BAT 72
Power voltage AC/DC 24 V
50/60Hz
Rated current 1 A
AC/DC throughput resistance <1 Ω
Protection class III
Degree of protection IP 54
Probe length 65 mm
Ambient temperature
Storage temperature
Ambient humidity
-30°C … +50°C
-40°C … +50°C
Max. 95% RH, non-condensing
Connection supply Cable 1 m, 2 x 0.5 mm², Betaflam cable heatresistant up to 145°C
Response temperature thermal fuse Duct inside temperature 72°C
Duct outside temperature 72°C
Thermoelectrical starting mechanism BAT
■If the thermal fuse Tf1 breaks (for a temperature close to
the fire damper), it is necessary to replace the actuating
mechanism. Thermoelectric starting mechanism BAT is
integral part of the actuating mechanism.
■If the thermal fuse Tf2 (for temperature in the duct) is
interrupted, it is enough to replace only the spare part
ZBAT72.
■When one of the thermal fuses responds, the supply
voltage is interrupted permanently and irreversibly.
■The function (interruption of the supply voltage) can be
checked by pressing the test button.
■Installation is carried out with the pre-assembled, self-
drilling and self-tapping screws.
Temperature thermal fuse
Spare parts are only supplied on the basis of an order.
BELIMO ZBAT 72
Black (BK) = 72°C (standard)
Altri manuali per FDMB
5
Indice
Altri manuali Mandik Serranda tagliafuoco e tagliafumo

Mandik
Mandik FDMA-PM Manuale utente

Mandik
Mandik FDMB Manuale utente

Mandik
Mandik SEDS-R Manuale utente

Mandik
Mandik FDMR Manuale utente

Mandik
Mandik SEDS-L Manuale utente

Mandik
Mandik SEDS-L Guida

Mandik
Mandik VCDM Manuale

Mandik
Mandik alnor FDMD Manuale utente

Mandik
Mandik MSD Manuale utente

Mandik
Mandik FDMC Manuale utente

Mandik
Mandik NKTM Manuale utente

Mandik
Mandik FDMQ Manuale utente

Mandik
Mandik FDMD Manuale utente

Mandik
Mandik SEDS Manuale utente

Mandik
Mandik FDMC Guida alla configurazione

Mandik
Mandik MSD Guida

Mandik
Mandik SEDM-L Manuale utente

Mandik
Mandik SEDM-L Manuale utente

Mandik
Mandik FDMQ Manuale utente

Mandik
Mandik FDMR 60 Manuale utente