Mennekes ME 30CDS1A-M2 Manuale utente

DS/CDS Disconnect Switches
Wiring and Mounting Instructions
277 Fairfield Road
Fairfield, NJ 07004
©2020 MENNEKES ELECTRONICS INC. 973-882-8333
SPECIFICATIONS SUBJECT TO CHANGE www.MENNEKES.com
WIRING DIAGRAM TERMINAL SPECIFICATIONS
*If needed – pull down with screwdriver in slot.
Tilt upward on load side of switch to release.
Conduit Connection and Grounding Instructions - For Enclosures Not Prepared with Conduit Entry Holes
NOTES: - Use of a UL Listed liquid-tight hub or connector fitting is required to maintain NEMA 4X, 12 or IP69K Rating.
- Use of a UL Listed hub or grounding bushing system is required for metallic grounding applications ¾” max.
- Grounding bushings are not required with non-metallic conduit.
1. Conduit Holes – cut holes in enclosure at drill point locations only. Drill points are provided as a guide. See Fig. 6 for DS and Fig. 7 for CDS details.
Use of a standard hole saw is the preferred method.
2. Conduit Connections
a. Metallic – secure the conduit hub onto the conduit. Then secure the conduit hub into a prepared enclosure hole using the hub nut and/or
grounding bushing inside the enclosure. Use the wiring diagram illustrated on the Wiring Instructions. Phase conductors and separate equipment
grounding conductor (if present) should be sized in accordance with N.E.C. FOLLOW GROUNDING INSTRUCTIONS BELOW
b. Non-Metallic Conduit – secure conduit to the conduit connector (hub) either before or after the conduit connector is secured into an enclosure hole
using the connector locknut. Use the wiring diagram illustrated on the Wiring Instructions. Size phase conductors and separate equipment ground to
N.E.C. FOLLOW GROUNDING INSTRUCTIONS BELOW
Grounding Instructions
IF A METALLIC CONDUIT SYSTEM IS USED TO PROVIDE THE
EQUIPMENT GROUND:
Metal conduit fittings with a ground screw on lock nut/bushing must
be utilized (not provided). Attach a properly sized ground wire (not
provided) to each ground nut/bushing screw. Secure the opposite
ends of the wire to a terminal on the green/yellow ground block
(provided on metal din rail). NOTE: Only one wire per terminal of
ground block. The “jumper” wires and ground block complete the
grounding path.
IF A SEPARATE EQUIPMENT GROUNDING CONDUCTOR IN
THE CONDUIT IS USED:
Connect the grounding conductor to the green/yellow ground block
mounted on the metal din rail. NOTE: Only one wire per terminal of
ground block.
SHORT CIRCUIT PROTECTION ACCORDING TO UL
These units are suitable for use on circuits capable of delivering not
more than 65,000 RMS Symmetrical Amperes at 600Vac Maximum.
25 & 30Amp
Torque
40Amp
Torque
Switch
#12 - 10 AWG
11 Ibs./in.
#8 AWG
13-16 Ibs./in.
Ground
#12-10 AWG
20 Ibs./in.
#10-8 AWG
20 Ibs./in.
Auxiliary
#14 AWG
4 Ibs./in.
#12 AWG
7 Ibs./in.
HP Ratings
Catalog Number
1 Ø
240VAC
3 Ø
240VAC
3Ø
480VAC
3 Ø
600VAC
ME 30CDS1A-M2
30A
5
10
20
25
ME 20DS1A-M2
25A
3
7.5
15
20
ME 30DS1A-M2
30A
5
10
20
25
ME 40DS1A-M2
40A
5
15
25
30
HP RATINGS

DS/CDS Disconnect Switches
Wiring and Mounting Instructions
277 Fairfield Road
Fairfield, NJ 07004
©2020 MENNEKES ELECTRONICS INC. 973-882-8333
SPECIFICATIONS SUBJECT TO CHANGE www.MENNEKES.com
NOTICE:
1. Turn off power feed to switch before installing or servicing.
2. This unit provides no overcurrent protection.
3. Select conductors in accordance with the 75°C column of
Ampacity Table 310.15(B)(16) of the National Electrical Code.
To Remove and Replace Front Cover
Fully loosen screws (Do Not Remove) located in four corners of cover. See Fig. 5
Pull cover away from bottom of enclosure. To replace cover, reverse above procedure.
A slight rotation of the switch handle may be needed to align the cover. Do not force.
Do not over-torque. Tighten cover screws and mounting feet to 13 in.lb.
Internal Mounting Method for DS/CDS Box
1. Position Box upright using ON/OFF as Reference.
2. With cover off, remove the (4) water seal caps by turning counterclockwise, a
quarter turn. (See Fig 1a)
For DS Box: See Fig. 1 for water seal cap locations and mounting details. For
CDS Box: See Fig. 2 for water seal cap locations and mounting details.
3. Mark mounting hole locations (Figs. 1) on mounting surface and prepare as
required for hardware to be used.
4. Mount Unit on Secure Flat Vertical Surface using flathead hardware (not
provided) up to ¼” max. (See Fig 1b)
5. Reinstall Sealing Caps by rotating clockwise, a quarter turn to maintain Type
4X, IP69K rating. (See Fig. 1c)
6. Reinstall Cover and Tighten 4 Cover Screws to 13in.lb max. See Fig. 5
External Mounting with Mounting Feet for DS/CDS Box
1. Position Box upright using ON/OFF as Reference.
2. With cover off, remove the (4) water seal caps by turning a quarter turn, counterclockwise. See Fig. 3a.
For DS Box: See Fig. 3 for water seal cap locations and where mounting feet are attached.
For CDS Box: See Fig. 4 for water seal cap locations and where mounting feet are attached.
3. Position external mounting feet as desired in 1 of 3 positions. See Fig 3 for DS Box; Fig 4 for CDS Box. Secure
mounting feet to enclosure with provided screws. Tighten to 13 in. lb max. See Fig. 3b.
4. Reinstall Sealing Caps by turning a quarter turn clockwise to maintain Type 4X, IP69K rating. (See Fig. 3c)
5. Mounting Feet accept up to ¼” hardware (not provided). Mark mounting pattern to selected mounting foot
pattern. See Figs. 3 or 4. Prepare surface as required for hardware and mount to Flat Vertical Surface.
6. Reinstall Cover and Tighten 4 Cover Screws to 13 in.lb max. See Fig. 5